Where Goodman puts the capacity code, what each code means, and the readings that look like capacity but are not. Read out of 3 documents Goodman publishes itself, named further down with the date each was fetched.
Starting the decoder. The capacity tables below this box are already loaded, so you can read your code off them now.
Nominal capacity from a model number is a nameplate convention, not a measurement. Actual delivered capacity depends on the matched indoor unit, line set, airflow and conditions. Confirm against the data plate's BTU/h rating and the AHRI certificate for the matched system.
Goodman Capacity Codes and Tonnage
R-410A GSX and GSZ generation
Capacity sits at positions 6-8, the 3 digit group after the SEER digits. Example: GSX140361KA.
Transcribed from the manufacturer's own capacity legend for the Goodman / Amana scheme. The capacity, not just the position, is printed in a document this tool holds.
| Code | Nominal BTU/h | Tons | Code / 12 |
|---|---|---|---|
| 018 | 18,000 | 1.5 | same answer |
| 019 | 18,000 | 1.5 | 1.58, so the division is wrong here |
| 024 | 24,000 | 2 | same answer |
| 025 | 24,000 | 2 | 2.08, so the division is wrong here |
| 030 | 30,000 | 2.5 | same answer |
| 031 | 30,000 | 2.5 | 2.58, so the division is wrong here |
| 036 | 36,000 | 3 | same answer |
| 037 | 36,000 | 3 | 3.08, so the division is wrong here |
| 042 | 42,000 | 3.5 | same answer |
| 043 | 42,000 | 3.5 | 3.58, so the division is wrong here |
| 048 | 48,000 | 4 | same answer |
| 060 | 60,000 | 5 | same answer |
Table transcribed from Product Specifications SS-GSX14 (SS-GSX14, 1/19), published by apps.goodmanmfg.com, fetched 2026-07-24.
R-32 GLXS and GLZS generation
Capacity sits at positions 8-9, a 2 digit code rather than the older 3 digit one. Example: GLXS4BA3610AA.
Read from the model-number position a manufacturer nomenclature document defines. That document defines where the capacity code sits; the capacity figure itself is this tool's reading of it.
| Code | Nominal BTU/h | Tons | Code / 12 |
|---|---|---|---|
| 18 | 18,000 | 1.5 | same answer |
| 24 | 24,000 | 2 | same answer |
| 30 | 30,000 | 2.5 | same answer |
| 36 | 36,000 | 3 | same answer |
| 42 | 42,000 | 3.5 | same answer |
| 48 | 48,000 | 4 | same answer |
| 60 | 60,000 | 5 | same answer |
Table transcribed from Product Specifications SS-GLXS4B-R32 (SS-GLXS4B-R32, 03/26), published by goodmanmfg.com, fetched 2026-07-24.
The Goodman codes that dividing by 12 gets wrong
The usual shortcut is that a capacity code is the nominal BTU/h divided by 1,000, so dividing it by 12 gives the tonnage. Goodman prints 5 codes where that arithmetic disagrees with Goodman's own table, and the table is what the equipment is sold against:
| Code | Goodman prints | Code / 12 gives |
|---|---|---|
| 019 | 1.5 tons | 1.58 |
| 025 | 2 tons | 2.08 |
| 031 | 2.5 tons | 2.58 |
| 037 | 3 tons | 3.08 |
| 043 | 3.5 tons | 3.58 |
These are not derivable, only transcribable, which is why this decoder carries Goodman's printed table rather than a formula. If you meet one of these codes in the field, arithmetic will land you between two real sizes, and the printed table is the only thing that resolves it.
Worked example: Goodman GSX140361KA
Capacity code 036 at characters 6-8 of GSX140361KA: 36,000 BTU/h, which is 3 tons at 12,000 BTU/h per ton. The capacity code in the Goodman/Amana split layout. SS-GSX14 rates GSX140361** at 36,000 BTU/h in the row it heads "Nom Cool (BTU/h)", so both figures are transcribed rather than calculated from the code.
- Efficiency: 14 SEER. The SEER rating in the GSX14 prefix.
- Refrigerant: R-410A. Goodman position 3 "X Condenser R-410A" per SS-GSX14.
- Product type: AC condenser. Position 3 unit type X.
Goodman has 2 documented layouts: R-410A GSX and GSZ generation reads capacity at positions 6-8; R-32 GLXS and GLZS generation reads capacity at positions 8-9. They put the capacity in different places, so a rule written for one and applied to the other is how a right-looking number ends up under the wrong heading.
What is specific to Goodman
Models this decoder refuses rather than guesses
An undocumented code publishes nothing. Each of these would produce a plausible number by general arithmetic, and the decoder returns no match instead, because no Goodman document supports it.
| Model | What the decoder returns | Why |
|---|---|---|
| GSX140091KA | no match | 009 sits on the universal ladder but appears in no Goodman or Amana capacity table, so no tonnage is published. |
| GSX140151KA | no match | 015 is the same case as 009: arithmetically valid, documented by neither brand. |
The Goodman documents behind this page
Published by apps.goodmanmfg.com. Fetched 2026-07-24. Covers the R-410A GSX generation: the Nominal Capacity table including every off-ladder code, corroborated inside the same document by its Product Specifications rated-BTU/h table.
Published by goodmanmfg.com. Fetched 2026-07-24. Covers the R-32 GLXS and GLZS layout: position 1 G for Goodman Brand, position 2 L for R-32 Splits System, Nominal Capacity at positions 8-9, and the Efficiency (SEER2) Nominal tier RANGES. This is the document whose nomenclature legend contradicts its own rated-capacity table.
Published by goodmanmfg.com. Fetched 2026-08-27. Covers the R-32 HEAT PUMP half of the GLXS/GLZS layout, and it is cited for ONE thing: its Nominal Capacity legend prints "30 - 2½ tons", which is one of the independent readings that refute SS-GLXS4B-R32's "30 - 2 Tons". Its capacity codes are TWO digits (18, 24, 30, 36, 42, 48, 60) and its own model list uses two digits to match (GLZS4BA3010A*). It sources no position claim this tool does not already take from SS-GLXS4B-R32.
Frequently asked questions
How do I find the tonnage of a Goodman unit from the model number?
Read the capacity code: on Goodman it sits at positions 6-8, the 3 digit group after the SEER digits. On GSX140361KA that code is 036, which is 36,000 BTU/h, or 3 tons, because one ton of cooling is 12,000 BTU/h. Use the OUTDOOR unit's model number for system cooling capacity; the indoor air handler or coil carries its own number. This position comes from Goodman's own SS-GSX14, not from a third-party chart.
Can I just divide the Goodman capacity code by 12?
Not on every code. Goodman prints 5 capacity codes where that division gives the wrong answer: 019 is 1.5 tons where dividing gives 1.58, 025 is 2 tons where dividing gives 2.08, 031 is 2.5 tons where dividing gives 2.58, 037 is 3 tons where dividing gives 3.08, 043 is 3.5 tons where dividing gives 3.58. Those values come from Goodman's own printed table rather than from arithmetic, which is the whole reason the table exists. On every other code in the table the division does work.
Where is the model number on a Goodman unit?
On the data plate on the outdoor condenser, where Goodman prints the model above the seria. It is labeled M/N, MODEL or MODEL NO., usually printed directly above or beside the serial number. The model number describes what the unit is, including its capacity. The serial number describes when it was built and carries no capacity information at all.
Which Goodman document is this based on?
Product Specifications SS-GSX14 (SS-GSX14, 1/19), published by apps.goodmanmfg.com and fetched 2026-07-24, which covers the R-410A GSX generation: the Nominal Capacity table including every off-ladder code, corroborated inside the same document by its Product Specifications rated-BTU/h table. Product Specifications SS-GLXS4B-R32 (SS-GLXS4B-R32, 03/26), published by goodmanmfg.com and fetched 2026-07-24, which covers the R-32 GLXS and GLZS layout: position 1 G for Goodman Brand, position 2 L for R-32 Splits System, Nominal Capacity at positions 8-9, and the Efficiency (SEER2) Nominal tier RANGES. This is the document whose nomenclature legend contradicts its own rated-capacity table. Product Specifications SS-GLZS4B-R32 (SS-GLZS4B-R32, 07/26), published by goodmanmfg.com and fetched 2026-08-27, which covers the R-32 HEAT PUMP half of the GLXS/GLZS layout, and it is cited for ONE thing: its Nominal Capacity legend prints "30 - 2½ tons", which is one of the independent readings that refute SS-GLXS4B-R32's "30 - 2 Tons". Its capacity codes are TWO digits (18, 24, 30, 36, 42, 48, 60) and its own model list uses two digits to match (GLZS4BA3010A*). It sources no position claim this tool does not already take from SS-GLXS4B-R32. Every capacity value on this page traces to one of those documents, and each is named with the date it was fetched so you can pull it yourself.
Is the decoded tonnage the size I should install?
No. Nominal tonnage is what the unit was built to deliver, not what the building needs, and the old unit may have been oversized or sized before insulation and window changes. Treat it as a starting clue and run a load calculation before matching a replacement. Actual delivered capacity also depends on the matched indoor unit, line set, airflow and conditions.
Related tools
Tonnage From Model Number (all brands)
The full decoder: 40+ brands, the universal capacity ladder, and the brands whose own tables override it.
Goodman Serial Number Lookup
The model number gives the size. The serial gives the age and the refrigerant era. Decode Goodman build dates.
BTU / HVAC Load Calculator
Size the actual load by climate zone, insulation and windows, then check it against the decoded nominal tonnage.
MCA / MOCP Breaker & Wire Size
Got the size? Size the circuit next: nameplate MCA and MOCP to wire, breaker and ground per NEC Article 440.
Other brands with their own manufacturer nomenclature document: Carrier tonnage by model number, Trane tonnage by model number, Lennox tonnage by model number, Amana tonnage by model number.
Got the tonnage? Check it against the actual load.
The old unit's nominal size is a clue, not a load calculation. Oversized systems short-cycle and dehumidify poorly. Run the numbers before you match a replacement.