HVAC Decoder
American Standard Tonnage From Model Number
Where American Standard puts the capacity code, what each code means, and the readings that look like capacity but are not. Read out of 3 documents American Standard publishes itself, named further down with the date each was read.
Starting the decoder. The capacity tables below this box are already loaded, so you can read your code off them now.
Nominal capacity from a model number is a nameplate convention, not a measurement. Actual delivered capacity depends on the matched indoor unit, line set, airflow and conditions. Confirm against the data plate's BTU/h rating and the AHRI certificate for the matched system.
American Standard Capacity Codes and Tonnage
R-454B outdoor units (2026 handbook, 5A)
Capacity sits at positions 7-8, with the refrigerant at position 1, the brand at 2, the system type at 3, the product family at 4, Nominal Rated SEER2 at 5 and the field connection at 6, per American Standard's own 2026 handbook. Example: 5A7A4024A1000AA.
The tonnage is the one the maker's own document prints for this capacity code; a BTU/h figure for it is converted from that tonnage.
The 15 capacity codes 14-1011-43 prints for this generation, each decoded here by the same engine the calculator above runs on.
Swipe the table sideways to see the rest of its columns. →
| Code | Nominal BTU/h | Tons | Code / 12 |
|---|---|---|---|
| 12 | 12,000 | 1 | same answer |
| 18 | 18,000 | 1.5 | same answer |
| 19 | 18,000 | 1.5 | 1.58, so the division is wrong here |
| 24 | 24,000 | 2 | same answer |
| 25 | 24,000 | 2 | 2.08, so the division is wrong here |
| 30 | 30,000 | 2.5 | same answer |
| 31 | 30,000 | 2.5 | 2.58, so the division is wrong here |
| 36 | 36,000 | 3 | same answer |
| 37 | 36,000 | 3 | 3.08, so the division is wrong here |
| 42 | 42,000 | 3.5 | same answer |
| 43 | 42,000 | 3.5 | 3.58, so the division is wrong here |
| 48 | 48,000 | 4 | same answer |
| 49 | 48,000 | 4 | 4.08, so the division is wrong here |
| 60 | 60,000 | 5 | same answer |
| 61 | 60,000 | 5 | 5.08, so the division is wrong here |
Table read from 2026 RESIDENTIAL & LIGHT COMMERCIAL PRODUCT HANDBOOK (14-1011-43, Effective 1/1/26 (page 12, NOM-1)), published by americanstandardair.com (a distributor's copy, on the distributor host of Denver Winair Co., which American Standard lists as a distributor), read 2026-10-12.
The American Standard codes that dividing by 12 gets wrong
The shortcut is that a capacity code is the nominal BTU/h divided by 1,000, so dividing it by 12 gives the tonnage. American Standard prints 7 codes where that arithmetic disagrees with American Standard's own table, and the table is what the equipment is sold against:
Swipe the table sideways to see the rest of its columns. →
| Code | American Standard prints | Code / 12 gives |
|---|---|---|
| 19 | 1.5 tons | 1.58 |
| 25 | 2 tons | 2.08 |
| 31 | 2.5 tons | 2.58 |
| 37 | 3 tons | 3.08 |
| 43 | 3.5 tons | 3.58 |
| 49 | 4 tons | 4.08 |
| 61 | 5 tons | 5.08 |
These cannot be worked out, only read off the table, which is why this decoder carries American Standard's printed table rather than a formula. If you meet one of these codes in the field, arithmetic will land you between two real sizes, and the printed table is the only thing that resolves it.
Worked example: American Standard 5A7A4024A1000AA
Capacity code 24 at characters 7-8 of 5A7A4024A1000AA: 24,000 BTU/h, which is 2 tons at 12,000 BTU/h per ton. Positions 7-8 are the Nominal Tonnage: American Standard's handbook 14-1011-43 prints "24 = 2.0" under that heading, in tons.
- Refrigerant: R-454B. Position 1 reads "5": American Standard's handbook 14-1011-43 prints "5 = R-454B" under Refrigerant Type.
- Brand letter: American Standard. Position 2 reads "A": American Standard's handbook 14-1011-43 prints "A = American Standard" under Brand.
- Product type: Split AC condenser. Position 3 reads "7": American Standard's handbook 14-1011-43 prints "7 = AC" under System Type.
- Efficiency: 14 SEER2. Position 5 reads "4": American Standard's handbook 14-1011-43 prints "4 = 14 SEER2" under Nominal Rated SEER2. That is the nominal rating the model number encodes, not a measured one.
What is specific to American Standard
American Standard equipment in the decoder
The decoder reads or identifies these American Standard lines; each one says what it rests on. Open an example to see the decoder's full answer for it.
| Line | Example model | What the decoder reads | Document |
|---|---|---|---|
| American Standard split outdoor unit | 4A7A4036B1000AA | 3 tons (36,000 BTU/h) | 12-1173-03, 12-1175-03 |
| American Standard R-454B split outdoor unit | 5A7A4024A1000AA | 2 tons (24,000 BTU/h) | 14-1011-43 |
CPSC recall notices naming American Standard
Hazard, in the notice's words: “The fuel gas valve can open unexpectedly, allowing a gas leak and posing a fire hazard.”
Hazard, in the notice's words: “The ground wire in the furnace’s junction box can become loose. If an electrical component then fails and short circuits, the unit poses a shock hazard.”
Hazard, in the notice's words: “The ground screws used in some units do not have the two threads required to provide sufficient grounding, posing a shock hazard to consumers.”
Hazard, in the notice's words: “A gas leak can occur if there is a crack in the gas valve body near the inlet pipe connection. A build-up of gas in the burner compartment of the unit could occur, which could be ignited by an internal spark.”
Hazard, in the notice's words: “Heat exchangers in the furnace can crack.”
Whether a particular unit is inside a recall depends on the models and serials the notice lists. The American Standard serial number lookup checks a unit against the notices.
Trane, same family as American Standard
Trane is in American Standard's family. These are Trane's lines; each one says what it rests on.
| Line | Example model | What the decoder reads | Document |
|---|---|---|---|
| Trane legacy split outdoor unit | 4TWV0036A1000AA | 3 tons (36,000 BTU/h) | 22-1746-04, 22-1725-04, 22-1904-1M-EN |
| Trane R-454B split outdoor unit | 5TTR5024A1000AA | 2 tons (24,000 BTU/h) | 22-8301-39 |
| Trane R-454B Low Profile outdoor unit | 5HPL5036A1000AA | 3 tons (36,000 BTU/h) | 22-8301-39, ODR-PSD038A-EN, DLR-PSD004A-EN |
| RunTru by Trane outdoor unit | A5AC3024B1000 | 2 tons (24,000 BTU/h) | 22-8301-39 |
| Trane ProSpace PTAC (PTEF/PTHF) | PTEF0702GAA | A Trane packaged terminal unit (PTAC or PTHP): its legend prints this code in BTU/h, not a whole, half or quarter ton, so no tonnage is published | PTAC-SVX002A-EN |
| Trane split system (1996 nomenclature, Pub. 22-1633-04) | TWN018C100B | 1.5 tons (18,000 BTU/h), an estimate | Pub. No. 22-1633-04-1296 (EN) |
| Trane RTAC air-cooled Series R chiller | RTAC140 | An air-cooled rotary chiller: large commercial equipment, outside this tool's range, so no tonnage is read | RLC-PRC006M-EN |
| Trane Horizon outdoor air unit (OAD, OAN) | OAND360 | A dedicated outdoor air unit: large commercial equipment, outside this tool's range, so no tonnage is read | OAU-PRC008A-EN |
| Trane air handler (1996 nomenclature, Pub. 22-1633-04) | TWV018B14 | An air handler: identified; its maker's document prints no model number legend, so no size is read | Pub. No. 22-1633-04-1296 (EN) |
| Trane indoor coil (1996 nomenclature, Pub. 22-1633-04) | TXC031E5 | An indoor coil: identified; its maker's document prints no model number legend, so no size is read | Pub. No. 22-1633-04-1296 (EN) |
- Trane Precedent packaged rooftop (3 to 10 tons): packaged or light commercial; its capacity is read from the maker's own printed legend or table, for the codes it prints.
- Trane Precedent packaged rooftop, R-410A J and R-454B K (3 to 25 tons): packaged or light commercial; its capacity is read from the maker's own printed legend or table, for the codes it prints.
- Trane Foundation packaged rooftop (3 to 25 tons): packaged or light commercial; its capacity is read from the maker's own printed legend or table, for the codes it prints.
- Trane Precedent packaged heat pump, R-410A WSC (3 to 10 tons): packaged or light commercial; its capacity is read from the maker's own printed legend or table, for the codes it prints.
- Trane Voyager packaged rooftop (12.5 to 25 tons): packaged or light commercial; its capacity is read from the maker's own printed legend or table, for the codes it prints.
The American Standard documents behind this page
Published by americanstandardair.com. This is a distributor's copy, on the distributor host of Denver Winair Co., which American Standard lists as a distributor. Read 2026-10-12. Covers American Standard's Model Nomenclature Residential - Outdoor on p12 (NOM-1): Refrigerant Type 5 = R-454B; Brand A = American Standard; System Type 5 = Cold Climate HP, 6 = HP, 7 = AC; Product Family A = Silver/Gold AC, C = Light Commercial, H = Silver/Gold HP, V = Platinum VSPD; Nominal Rated SEER2; Field Connection 0 = Brazed, 5 = Mechanical straight fitting; Nominal Tonnage 12 = 1.0 to 61 = 5.0 at positions 7-8.
Published by www.asdealernet.com. Read 2026-10-11. Covers American Standard's Outdoor Units model nomenclature on p6: Refrigerant Type 2 = R-22, 4 = R-410A; position 2 AMERICAN STANDARD; Product Type 6 = Split Heat Pump, 7 = Split Cooling; Family SEER 0 = 10 to 9 = 19; Split System Connections 1-6 Tons 0 = Brazed; Nominal Capacity in 000s of BTUs at positions 7-8.
Published by www.asdealernet.com. Read 2026-10-11. Covers the same Outdoor Units model nomenclature as 12-1173-03, on p6.
Frequently asked questions
How do I find the tonnage of an American Standard unit from the model number?
Read the capacity code: on American Standard it sits at positions 7-8, with the refrigerant at position 1, the brand at 2, the system type at 3, the product family at 4, Nominal Rated SEER2 at 5 and the field connection at 6, per American Standard's own 2026 handbook. On 5A7A4024A1000AA that code is 24, which is 24,000 BTU/h, or 2 tons, because one ton of cooling is 12,000 BTU/h. Use the OUTDOOR unit's model number for system cooling capacity; the indoor air handler or coil carries its own number. This position comes from American Standard's own 14-1011-43, not from a third-party chart.
Can I just divide the American Standard capacity code by 12?
Not on every code. American Standard prints 7 capacity codes where that division gives the wrong answer: 19 is 1.5 tons where dividing gives 1.58, 25 is 2 tons where dividing gives 2.08, 31 is 2.5 tons where dividing gives 2.58, 37 is 3 tons where dividing gives 3.08, 43 is 3.5 tons where dividing gives 3.58, 49 is 4 tons where dividing gives 4.08, 61 is 5 tons where dividing gives 5.08. Those values come from American Standard's own printed table rather than from arithmetic, which is the whole reason the table exists. On every other code in the table the division does work.
Where is the model number on an American Standard unit?
On the data plate on the outdoor unit's cabinet. It is labeled M/N, MODEL or MODEL NO., and can be printed directly above or beside the serial number. The model number describes what the unit is, including its capacity. The serial number describes when it was built and carries no capacity information at all.
Which American Standard document is this based on?
2026 RESIDENTIAL & LIGHT COMMERCIAL PRODUCT HANDBOOK (14-1011-43, Effective 1/1/26 (page 12, NOM-1)), published by americanstandardair.com (a distributor's copy, on the distributor host of Denver Winair Co., which American Standard lists as a distributor) and read 2026-10-12, which covers American Standard's Model Nomenclature Residential - Outdoor on p12 (NOM-1): Refrigerant Type 5 = R-454B; Brand A = American Standard; System Type 5 = Cold Climate HP, 6 = HP, 7 = AC; Product Family A = Silver/Gold AC, C = Light Commercial, H = Silver/Gold HP, V = Platinum VSPD; Nominal Rated SEER2; Field Connection 0 = Brazed, 5 = Mechanical straight fitting; Nominal Tonnage 12 = 1.0 to 61 = 5.0 at positions 7-8. SPLIT SYSTEM COOLING MODELS 4A7A4018-24C/30-060B (12-1173-03, May 2008), published by www.asdealernet.com and read 2026-10-11, which covers American Standard's Outdoor Units model nomenclature on p6: Refrigerant Type 2 = R-22, 4 = R-410A; position 2 AMERICAN STANDARD; Product Type 6 = Split Heat Pump, 7 = Split Cooling; Family SEER 0 = 10 to 9 = 19; Split System Connections 1-6 Tons 0 = Brazed; Nominal Capacity in 000s of BTUs at positions 7-8. SPLIT SYSTEM HEAT PUMP MODELS 4A6H4018-060B (12-1175-03, June 2008), published by www.asdealernet.com and read 2026-10-11, which covers the same Outdoor Units model nomenclature as 12-1173-03, on p6. Every capacity value in the capacity tables above traces to one of those documents, and each is named with the date it was read so you can pull it yourself. The sizes in the equipment table are read from the document named in its Document column, listed on this page's source receipt.
Is the decoded tonnage the size I should install?
No. Nominal tonnage is what the unit was built to deliver, not what the building needs, and the old unit may have been oversized or sized before insulation and window changes. Treat it as a starting clue and run a load calculation before matching a replacement. Actual delivered capacity also depends on the matched indoor unit, line set, airflow and conditions.
Related tools
Tonnage From Model Number (all brands)
The full decoder: 40+ brands, the universal capacity ladder, and the brands whose own tables override it.
American Standard Serial Number Lookup
The model number gives the size. The serial gives the age and the refrigerant era. Decode American Standard build dates.
BTU / HVAC Load Calculator
Compute the house's load by Manual J at your ZIP code's weather station, then check it against the decoded nominal tonnage.
MCA / MOCP Breaker & Wire Size
Got the size? Size the circuit next: nameplate MCA and MOCP to wire, breaker and ground per NEC Article 440.
Other brands with their own manufacturer nomenclature document: Carrier tonnage by model number, Trane tonnage by model number, Lennox tonnage by model number, Goodman tonnage by model number, Amana tonnage by model number.
Got a central system's tonnage? Check it against the house's load.
The old unit's nominal size is a clue, not a load calculation. Oversized systems short-cycle and dehumidify poorly. For central equipment that conditions the whole house, run the numbers before you match a replacement. A PTAC, a single package vertical unit, a room air conditioner or one unit of a VRF system conditions a room or a zone, which this load calculator does not size.