R-454B / Puron Advance (A2L, near-azeotrope)

R-454B PT Chart

The full R-454B pressure-temperature reference table, from -20 to 130°F, with both the bubble and dew columns its about 2°F glide requires. Use the dew point for superheat and the bubble point for subcooling. Checked cell by cell against 4 other published tables, 2 of them separate publishers: Arkema, Chemours, Honeywell and Weitron. Three of them, Weitron, Arkema and Chemours, have full columns on file here, so this chart prints where those tables and ours disagree at every pressure instead of quietly picking one. The widest gap on the bubble column, which is the one compared here, is 0.69 degrees F, against Weitron, Arkema and Chemours, at 58.5 psig.

Field brief
260 psigbubble point 90°F (subcooling), dew point 92.4°F (superheat). At 112 psig, bubble 40°F and dew 42.1°F.bubble / dew
GlideAbout 2°F, a near-azeotrope. The two columns stay close, but read dew for superheat and bubble for subcooling.~2°F
vs R-410AA few psig lower at the same temperature, so the R-410A line set is usually pressure-adequate. Still A2L, not a drop-in.A2L
Where you left off
Saved in this browser, which can get cleared. The app keeps 10x the readings.Saved in this app.
Intry Pro, coming soon, keeps your saved readings on every device. See Intry Pro ›

Read the R-454B chart at your gauge pressure

The chart below is the reference. This reads it at the pressure you actually have, off the bubble or dew column the line you are measuring calls for, and works out superheat or subcooling once you add the line temperature.

the big insulated line, for superheat

Saturation temperature dew point, the column superheat uses42.1°F
The other column bubble point, which subcooling uses40.0°F

A blend has two saturation temperatures at one pressure. On the suction line the dew point is the one to use. Reading the bubble point instead would put the saturation temperature 2.1°F lower, which makes the superheat come out 2.1°F higher than it is.

112.0 psig is a published row of the R-454B (Puron Advance) chart, not an interpolated value. Glide at this pressure is 2.1°F.

Add the suction line temperature to get superheat from this reading.

Where this number comes fromIntry Verified
Calculated from
R-454B (Puron Advance) PT chart, dew column. Table looked up from a named datasheet. See the full receipt ↓
Run with
  • Pressure112.0 psig, suction line
  • Saturation42.1°F, dew point
  • Chart rowa published row of the chart
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 31163 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from the locked modules each figure is traced to: the manufacturer PT tables behind the saturation temperatures, superheat and subcooling, and the transcribed code and service-literature constants behind the charge, metering, airflow, approach and discharge line figures, each quoted with its own source in the panel it appears in. This is our own deterministic gate, not a third-party audit.
Final say
The unit nameplate and the manufacturer's charging chart have final say.
What Intry Verified means

Intry Verified · Build 2731D30 · 2026-10-15

R-454B Pressure-Temperature Table

R-454B saturation temperatures at gauge pressure (psig): bubble (subcooling) and dew (superheat).
R-454B
Pressure (psig)Bubble °F (subcooling)Dew °F (superheat)Publisher spread (°F)
24.3-20°F-18.3°F0.67
33.9-10°F-7.9°F0.67
45.30°F1.9°F0.64
58.510°F12.2°F0.69
73.920°F22°F0.67
91.730°F32.3°F0.63
11240°F42.1°F0.60
13550°F52.4°F0.65
161.160°F62.1°F0.65
190.570°F72.4°F0.65
223.480°F82.2°F0.64
26090°F92.4°F0.65
300.8100°F102.1°F0.65
345.9110°F112.3°F0.65
395.7120°F122.1°F0.66
450.5130°F132.2°F0.66

About the spread column. It is the widest gap in saturation temperature between the published tables we hold, at that pressure, on the bubble column. Across this chart the widest is 0.69°F, at 58.5 psig. Our table and 3 other published tables are compared here: 1 is a separate publisher, and 2 resolve to the same equation of state as our base, so those are consistency checks rather than independent confirmation. A narrow spread means the charts agree, which is not the same as the charts being right: they are all computed from equations of state fitted to lab data, and no field measurement settles it.

Where this table comes from. CoolProp 7.2.0 reference data, bubble and dew columns.
  • Checked against Arkema Forane 454B, within 0.1 psig [same model]
  • Checked against Chemours Opteon XL41, within 0.05 psig [same model]
  • Checked against Honeywell Solstice 454B, within 2 psig [separate publisher]
  • Checked against Weitron, reprinted as Daikin/Goodman PM-A2LPTC-USA_04-24, bubble line about 0.64 F away [separate publisher]

Arkema and Chemours make this blend, and both state their tables were generated from NIST REFPROP, the same equation-of-state lineage our own base resolves to. Their agreement is close and it is not independent confirmation. Weitron is the one table that disagrees: its bubble line sits about 0.64 F from ours across the whole range, a constant offset rather than noise, and no further chart can settle which is right. The calculator says so on any reading close enough to a band edge for that difference to change the call.

A separate publisher can catch a transcription, edition or rounding error. A cross-check marked same model resolves to the same equation of state as the base table, so it is a consistency check rather than independent confirmation. One marked same printing prints numbers identical to another table listed here, so the two are one witness and we do not count them twice. Sources last re-verified 2026-08-25.

Read the low-side (suction) pressure and its dew temperature for superheat, and the high-side (liquid) pressure and its bubble temperature for subcooling. The chart is in psig (gauge) and °F. To convert: kPa gauge = psig × 6.895; °C = (°F − 32) / 1.8. The table opens in psig and °F; the buttons above it show the same rows in bar or kPa (gauge) and °C.


R-454B PT Chart FAQs

What is the R-454B pressure at a 40F bubble point?

On the R-454B PT chart, a 40F bubble point corresponds to about 112 psig, where the dew point is 42.1F. At 260 psig the bubble point is 90F and the dew point is 92.4F. R-454B (Puron Advance) is a near-azeotropic A2L blend with only about 2F of glide, so its pressures sit close to R-410A but a hair lower.

Why does the R-454B PT chart have two temperature columns?

R-454B is a zeotropic blend, so at any given pressure it boils and condenses across a small range of temperatures rather than at one point. The lower temperature is the bubble point and the higher one is the dew point; the gap is the glide, only about 2 degrees F for R-454B, which is why it is called a near-azeotrope. Because the glide is small, the two columns are close, but the table still lists both so you read the correct one.

Do I use bubble or dew point for R-454B superheat and subcooling?

Use the dew point for superheat and the bubble point for subcooling. Superheat is measured on the suction line where the refrigerant is fully vapor, which is the dew side. Subcooling is measured on the liquid line where it is fully liquid, which is the bubble side. R-454B's glide is only about 2F, so the penalty for reading the wrong column is small, but reading it right keeps the charge diagnosis clean.

Is the R-454B PT chart the same as R-410A?

Very close but not identical. R-454B runs a few psig below R-410A at the same temperature, which is why R-454B is a low-glide near-match on the pressure side and the R-410A line set is usually pressure-adequate. It is still not a drop-in: R-454B is A2L (mildly flammable), so it requires A2L-listed equipment, leak detection, and A2L service practices.


Related R-454B Tools