R-454B (Puron Advance)

R-454B Superheat & Subcooling Calculator

Check charge on R-454B systems with the calculator preloaded for the A2L refrigerant that replaced R-410A in new ducted equipment. Full PT chart, every grade cited to its source, and the A2L handling notes that actually change how you charge.

Quick answer: The target comes from the equipment maker. Where it publishes no superheat for a TXV, California Title 24 Table RA3.2-1 sets 4–25°F, the same figure as for R-410A; subcooling is checked within ±3°F of the unit’s own target in cooling, at an outdoor air dry bulb of 55°F to 120°F and a return air dry bulb of at least 70°F. R-454B runs slightly lower pressures: 114 psig suction saturates near 43°F at the dew point (used for superheat) and 297 psig liquid saturates near 99°F at the bubble point (used for subcooling). Superheat = suction line temp − saturated suction temp. Subcooling = saturated liquid temp − liquid line temp.

R-454B Pressure-Temperature Chart

R-454B bubble and dew saturation temperatures at gauge pressure. Superheat converts suction pressure to the dew point; subcooling converts liquid pressure to the bubble point.

Swipe the table sideways to see the rest of its columns. →

R-454B
Pressure (psig)Bubble °F (subcooling)Dew °F (superheat)Publisher spread (°F)
9.5-40°F-38.1°F0
16.2-30°F-28.1°F0.71
24.3-20°F-18°F0.67
33.9-10°F-7.9°F0.67
45.30°F2.2°F0.64
58.510°F12.2°F0.69
73.920°F22.2°F0.67
91.730°F32.3°F0.63
11240°F42.4°F0.60
13550°F52.4°F0.65
161.160°F62.4°F0.65
190.570°F72.4°F0.65
223.480°F82.4°F0.64
26090°F92.4°F0.65
300.8100°F102.3°F0.65
345.9110°F112.3°F0.65
395.7120°F122.2°F0.66
450.5130°F132°F0.66
510.7140°F141.9°F0.68
576.8150°F151.6°F0.67

About the spread column. It is the widest gap in saturation temperature between the published tables we hold, at that pressure, on the bubble column. Across this chart the widest is 0.71°F, at 16.2 psig. Our table and 2 other published tables are compared here: 1 is a separate publisher, and 1 resolves to the same equation of state as our base, so that one is a consistency check rather than independent confirmation. A dash in the column: no other published table is compared at this pressure: none we hold reaches it, or this row is that table's own cell. A narrow spread means the charts agree, which is not the same as the charts being right: they are all computed from equations of state fitted to lab data, and no field measurement settles it.

Where this table comes from. Chemours Opteon XL41 (R-454B) thermodynamic properties table, liquid (bubble) and vapor (dew) columns.
  • Checked against Arkema Forane 454B, within 0.1 psig [same model]
  • Checked against Honeywell Solstice 454B, bubble line within 0.29 F and dew line within 0.41 F of ours, at the 66 pressures both print [separate publisher]
  • Checked against Weitron, reprinted as Daikin/Goodman PM-A2LPTC-USA_04-24, bubble line about 0.64 F away [separate publisher]
  • Checked against CoolProp 7.2.0, the same bubble pressure as ours to 0.1 psig at its 16 rows from -20 to 130 F, and a dew curve within 0.2 F of our dew points at our pressures [same model]

CoolProp 7.2.0 covers the rows from -20 to 130 F, Weitron's card runs from -38 to 150 F, and Honeywell's chart stops at 530 psig, below the 150 F row. Arkema's chart covers every row. The table stops at 150 F by our choice, where Arkema's and Weitron's charts stop; Chemours' table prints on to 172 F.

Chemours makes this blend and states its table is based on NIST REFPROP. Arkema, which also makes it, states the same of its chart, and CoolProp is the same kind of equation-of-state model, so their close agreement is not independent confirmation. Weitron is the one table that disagrees: its bubble line sits about 0.64 F from ours across the whole range, a constant offset rather than noise, and no further chart can settle which is right. The calculator says so on any reading close enough to a band edge for that difference to change the call.

A separate publisher can catch a copying, edition or rounding error. A cross-check marked same model resolves to the same equation of state as the base table, so it is a consistency check rather than independent confirmation. One marked same printing prints numbers identical to another table listed here, so the two are one witness and we do not count them twice. Sources last re-verified 2026-10-25.

For quick sanity checks: Sporlan’s Bulletin 10-9 (Table 7) lists air conditioning and heat pump evaporators at 40–50°F, which puts R-454B suction pressure at 107–129 psig on the dew line. If your condenser saturates at 100–110°F, the bubble line puts liquid pressure at 301–346 psig. If your gauges are far outside those windows with the system running steady, verify the reading before touching the charge.


R-454B Normal Operating Pressures

On a properly charged R-454B air conditioner, the low-side (suction) pressure stays fairly steady because the evaporator temperature is set by the load and metering device, while the high-side (liquid) pressure climbs with outdoor temperature as the condenser has to reject heat into hotter air. The pressures at a few coil saturation temperatures, read from the PT chart above:

R-454B saturation pressures at the stated evaporator and condensing temperatures (AC mode)

Swipe the table sideways to see the rest of its columns. →

Saturation temperaturesSuction (Low)Liquid (High)
Evaporator 40°F, condensing 100°F107 psig301 psig
Evaporator 40–45°F, condensing 105–110°F107–118 psig323–346 psig
Evaporator 40–45°F, condensing 115–120°F107–118 psig371–396 psig

Suction is read on the dew line and liquid on the bubble line. Which condensing temperature a unit runs at on a given day is set by the unit and its maker’s chart, not by this table. Pressures shift with indoor load, airflow, and humidity, so confirm the charge with superheat and subcooling, not pressure alone. R-454B runs lower than R-410A on the high side (R-410A reads higher by about 14 psig at 90°F, 16 psig at 100°F and 26 psig at 130°F condensing). An R-410A manifold reads the pressure fine, but use an R-454B PT scale for saturation temperature.


What R-454B Superheat & Subcooling Are Graded Against

TXV superheat: California Energy Commission, 2025 Reference Appendices (CEC-400-2025-010-AP), Table RA3.2-1, page RA3-19, the installer default "Superheat meets the Manufacturer's specifications or 4°F ≤ Superheat ≤ 25°F", for residential ducted split systems with a TXV or other variable metering device, installer testing: outdoor air dry bulb 55°F to 120°F, return air dry bulb at least 70°F. TXV subcooling: the maker's own target, checked within ±3°F ("Subcooling tolerance ±3°F of the manufacturer-specified target", same table) in cooling, at an outdoor air dry bulb of 55°F to 120°F and a return air dry bulb of at least 70°F. Fixed orifice: superheat against the target Table RA3.2-2 computes from indoor wet bulb and outdoor dry bulb, within ±5°F ("Superheat tolerance ±5°F of the specified target", Table RA3.2-1); subcooling only against the maker's own target with the tolerance the maker prints beside it (Lennox 13ACC Installation Instructions (form 504726), page 14, Table 6: "Liquid Subcooling [± 1°F (.6°C)]"), otherwise not graded. Refrigeration fluids: the superheat is shown and not graded, on a TXV or a fixed orifice, because these figures are residential comfort-cooling figures. Where the equipment maker prints its own figure, it governs.

Swipe the table sideways to see the rest of its columns. →

Metering deviceSuperheat graded againstSubcooling graded againstCharging method
TXV4–25°Fmaker's target ±3°FCharge by subcooling; the TXV holds superheat
Fixed orifice (piston)RA3.2-2 target ±5°Fmaker's target and printed tolerance, else not gradedCharge by superheat against its target; where the maker sets the charge by subcooling, by its target and tolerance

What Is R-454B?

R-454B is the A2L refrigerant that replaced R-410A in new ducted residential and light commercial equipment. Under EPA's Technology Transitions rule, a new split air conditioner or heat pump system (other than variable refrigerant flow) using a refrigerant at 700 GWP or above may be installed from January 1, 2025 only if all of its specified components (condensing unit, condenser, compressor, evaporator unit and evaporator, as 40 CFR 84.52 defines them) were made or imported before January 1, 2025, and self-contained units (packaged, window and through-the-wall) using such a refrigerant may not be manufactured or imported from January 1, 2025. Carrier markets it as Puron Advance: its CVAMA evaporator coil product data reads “for Puron Advance™ (R-454B) Refrigerant”. It is a blend of R-32 and R-1234yf with a GWP of 465, versus 2,088 for R-410A.

The good news for charging: R-454B behaves very much like R-410A on the gauges. It runs slightly lower pressures at the same saturation temperature (42°F is about 111 psig on R-454B's dew line and 117 psig on its bubble line, versus roughly 123 psig on R-410A), and the charge checks are the same ones: Title 24’s 4–25°F TXV superheat default where the maker publishes none, and subcooling against the unit’s own target. The diagnostic logic you know from R-410A carries over directly: high superheat with low subcooling still means low charge, low superheat with high subcooling still means overcharge.

A2L Charging Notes for R-454B

What changes is handling, not thermodynamics. R-454B is mildly flammable (A2L), which drives four practical rules. First, charge liquid only: R-454B is a zeotropic blend, and vapor charging fractionates it, pulling off a different composition than what stays in the cylinder. Second, use A2L-rated recovery machines, hoses, and leak detectors; standard R-410A recovery equipment is not listed for flammable refrigerants. Third, no brazing or open flame on a circuit holding charge; recover first, then purge with nitrogen while brazing. Fourth, respect the equipment leak-detection system: where an R-454B air handler carries a refrigerant sensor that drives the blower on a detected leak (UL 60335-2-40), that circuit must stay functional after service.

R-454B has about 2°F of temperature glide. That is small, but this calculator still handles it correctly: it reads the dew point off the suction pressure for superheat and the bubble point off the liquid pressure for subcooling, the same bubble/dew treatment used for R-407C. On a critically charged system where you are splitting hairs at the edge of a target range, remember the glide adds roughly a degree of uncertainty; charge to the middle of the manufacturer target rather than the edge.

One thing R-454B is not: a retrofit refrigerant. R-410A equipment is not listed for A2Ls and cannot legally or safely take R-454B. Service existing R-410A systems with R-410A, and install R-454B only in equipment designed for it.


Worked Example: New R-454B Heat Pump with TXV

A 2026-installed R-454B heat pump in cooling mode, TXV metering. Field readings: suction pressure 110 psig, suction line temperature 50°F, liquid pressure 300 psig, liquid line temperature 91°F. The outdoor and return air are inside Title 24’s conditions (in cooling, at an outdoor air dry bulb of 55°F to 120°F and a return air dry bulb of at least 70°F).

Saturated suction temp at 110 psig (dew point) = 41.1°F

Superheat = 50°F − 41.1°F = 8.9°F

Saturated liquid temp at 300 psig (bubble point) = 99.8°F

Subcooling = 99.8°F − 91°F = 8.8°F

Diagnosis: Superheat 8.9°F sits inside Title 24’s 4–25°F TXV default. Subcooling 8.8°F is graded only against the unit’s nameplate target, within ±3°F; until that target is read off the unit, the charge is not assessed from it. Log both numbers on the startup sheet: baseline readings on a new A2L install are worth their weight when the same unit gets a warranty call two summers later.

Run this in your AI. Ask Claude or ChatGPT to check the superheat and whether an R-454B charge is right from your gauge readings and it runs the Intry Superheat & Subcooling Calculator live, handing back the verdict with its cited source instead of a guess. Then keep the reading as one job in the Intry app.

R-454B Charging FAQs

What are normal operating pressures for R-454B?

Read them off the PT chart at the coil temperatures: a 40 to 45F evaporator is 107 to 118 psig on the suction (low) side, on the dew line, and 100 to 120F condensing is 301 to 396 psig on the liquid (high) side, on the bubble line. The suction stays near the evaporator's pressure while the high side climbs with the condensing temperature, which the outdoor air, the condenser and the load set; the maker's chart for the unit says what it should be. R-454B runs lower than R-410A on the high side (R-410A reads higher by about 14 psig at 90°F, 16 psig at 100°F and 26 psig at 130°F condensing), so an R-410A manifold reads the pressure fine, but you must use an R-454B pressure-temperature scale to read saturation temperature correctly.

What are R-454B running pressures on a 90 degree day?

The outdoor temperature alone does not set them: the high side follows the condensing temperature, and how far that sits above a 90F day depends on the unit, its condenser airflow and the indoor load, so the maker's charging chart for the unit is the figure to read. For a sense of scale, at 105 to 110F condensing the liquid (bubble-line) pressure is 323 to 346 psig, and a 40 to 45F evaporator reads 107 to 118 psig suction. Verify the charge with superheat and subcooling rather than pressure alone.

What should R-454B suction and head pressure be?

Suction (low side) should sit near the dew-line pressure for your evaporator temperature, about 107 to 118 psig for a 40 to 45F coil. Head (liquid, high side) should sit near the bubble-line pressure for the condensing temperature, which rises with the outdoor air; it reads around 301 psig at 100F condensing up to about 396 psig at 120F condensing. If the head is much higher, check condenser airflow and for overcharge; if it is much lower, check for low charge or a low outdoor temperature.

What should superheat be for R-454B?

On a TXV system the target is the equipment maker's. Where the maker publishes no superheat, California Title 24 Table RA3.2-1 sets 4 to 25F for residential ducted split systems with a TXV or other variable metering device, installer testing: outdoor air dry bulb 55°F to 120°F, return air dry bulb at least 70°F, and it checks subcooling at the liquid line within ±3F of the manufacturer's target in cooling, at an outdoor air dry bulb of 55°F to 120°F and a return air dry bulb of at least 70°F. Always charge R-454B as a liquid from an inverted cylinder, since it is a zeotropic blend and vapor charging shifts its composition. Its temperature glide is low (about 2F), so the bubble-point/dew-point split is small, though this calculator still applies it (dew point for superheat, bubble point for subcooling). On a fixed-orifice or piston system, set the charge by the manufacturer's charging chart against indoor wet-bulb and outdoor dry-bulb instead of a fixed superheat number.

What should my subcooling be on 454B?

The target is the one the manufacturer prints on the unit nameplate, measured at the liquid line near the condenser outlet; no refrigerant-wide band is published, and California Title 24 Table RA3.2-1 checks the reading within ±3°F of that target in cooling, at an outdoor air dry bulb of 55°F to 120°F and a return air dry bulb of at least 70°F. Subcooling is the primary charging indicator on TXV systems.

What is normal superheat for R-454B?

With a TXV the target is the equipment maker's; where the maker publishes none, California Title 24 Table RA3.2-1 sets 4-25°F at the suction service valve of a residential split system. With a fixed orifice, target superheat depends on outdoor ambient and indoor wet bulb (Title 24 Table RA3.2-2 computes it, checked within ±5°F), so use the manufacturer charging chart or enter both readings here. Superheat below 5°F risks liquid floodback to the compressor.

Can I use my R-410A gauges on R-454B?

Your manifold body handles the pressures fine because R-454B runs slightly lower than R-410A, but the R-410A temperature scale on an analog gauge will give wrong saturation temperatures. Use an R-454B PT scale, digital probes with R-454B selected, or this calculator. Hoses, recovery machines, and vacuum pumps used on R-454B should be A2L rated per the manufacturer.

Do I charge R-454B as liquid or vapor?

Charge R-454B as liquid from the cylinder. It is a blend of R-32 and R-1234yf, so vapor charging can fractionate the blend and shift its composition. Invert the cylinder (or use a liquid port) and throttle liquid into the suction side slowly through a charging valve or metering device so slugs never reach the compressor.

Is R-454B dangerous to work with?

R-454B is classified A2L: low toxicity and mildly flammable. It is much harder to ignite than propane (A3) and needs a strong ignition source plus a concentrated leak, but it changes work practices: no open flames or brazing on a charged circuit, A2L-rated recovery equipment, ventilation in enclosed spaces, and leak detection per UL 60335-2-40 on the equipment side.

Can I retrofit my R-410A system to R-454B?

No. R-454B is not a drop-in replacement for R-410A. Existing R-410A equipment is not listed for A2L refrigerants and lacks the required leak detection, airflow mitigation, and electrical design. Existing R-410A systems keep getting serviced with R-410A; R-454B goes only into equipment designed and listed for it.

Does R-454B have temperature glide?

Yes, but it is small, roughly 2°F. R-454B is a zeotropic blend, so bubble point and dew point differ slightly at the same pressure. This calculator handles that split the honest way: it converts suction pressure to the dew point for superheat and liquid pressure to the bubble point for subcooling, so the glide is already built in. In field practice that glide is close to gauge accuracy. R-407C, by comparison, glides several times as much, where using the wrong point misdiagnoses the system outright.


Other Refrigerants & Related Tools

R-32 Superheat & Subcooling Calculator

Pure A2L refrigerant used in ductless mini splits. Zero glide, higher pressures, hotter discharge.

R-410A Superheat & Subcooling Calculator

The dominant installed base from 2010 to 2025. PT chart and cited charge checks.

R-22 Superheat & Subcooling Calculator

Legacy HCFC: serviced with recycled, reclaimed or previously produced R-22 since 2020. PT chart and cited charge checks for servicing older systems.

R-134a Superheat & Subcooling Calculator

Medium-temp refrigeration, chillers, and automotive AC. PT chart and cited reference figures.

All-Refrigerant Calculator

The full calculator with 10+ refrigerants including R-407C with glide handling, plus the four-quadrant diagnostic guide.

Target Superheat Calculator

Charging a fixed-orifice (piston) system? Set the charge by target superheat from indoor wet-bulb and outdoor dry-bulb, compared to your measured superheat.

Normal Superheat & Subcooling Values

What each reading is graded against, by metering device, each figure cited, with what a high or low reading means. R-410A, R-454B, R-32, R-22, R-134a, and R-407C in one reference.

How to Calculate Superheat & Subcooling

The formulas, the step-by-step field method, and worked examples for R-410A and R-22. The math behind the calculator.

Printable Superheat & Subcooling Chart

What each reading is graded against, with its source, plus PT charts for R-410A, R-454B, and R-22, formatted to print or save as a PDF for the truck.

Subcooling on a Heat Pump

Where to measure on a heat pump in each mode, each maker's own heating-mode charging rule, and when the cooling-mode subcooling number still applies.

A2L Charge Limit Calculator

Maximum A2L charge for a room, or minimum room area for a charge, per UL 60335-2-40 and ASHRAE 15.2. Covers R-454B, R-32, and 6 more refrigerants.

EPA Refrigerant Leak Rate Calculator

Topping off a covered 15+ lb appliance triggers a leak rate calculation under 40 CFR 84.106 as of January 1, 2026. Residential and light commercial air conditioning and heat pumps are excluded by 84.106(a)(3)(ii), so on most split systems the rate is informational. Run the EPA math and check the thresholds.

BTU / HVAC Load Calculator

A house's heating and cooling loads by ACCA Manual J at your ZIP code's weather station, with the size Manual S points to.

Charging a brand-new A2L install? Check the sizing too.

New R-454B equipment means a fresh chance to catch an oversized replacement. Run the load by Manual J at your ZIP code's weather station before you trust the old tonnage.