R-22 (Legacy HCFC)

R-22 PT Chart

The full R-22 pressure-temperature reference table, from -40 to 120°F. R-22 is a pure single-component refrigerant, so the chart is one saturation column with zero glide. Checked cell by cell against one other published table, a separate publisher: iGas/Arkema, printing NIST REFPROP 9.0. It has a full column on file here, so this chart prints where that table and ours disagree at every pressure instead of quietly picking one. The widest gap anywhere on it is 1.00 degrees F, at 1 psig. This table is stored in whole psig, the resolution its two sources agree to. Near -40°F the curve is flat enough that one psig is worth about 2.5°F of saturation temperature, so read the cold end as a guide and take the reading itself off your gauge.

Field brief
40°F / 100°FR-22 saturates at about 69 psig at 40°F and 196 psig at 100°F (84 psig at 50°F, 260 psig at 120°F).69/196 psig
GlideZero. One saturation column serves both superheat and subcooling; there is no separate bubble and dew point.single column
SupplyRecycled, reclaimed or previously produced R-22 only, since U.S. production and import ended on January 1, 2020 (EPA).servicing only
Where you left off
Saved in this browser, which can get cleared. The app keeps 10x the readings.Saved in this app.
Intry Pro, coming soon, keeps your saved readings on every device. See Intry Pro ›

Read the R-22 chart at your gauge pressure

The chart below is the reference. This reads it at the pressure you actually have, including between the published rows, and works out superheat or subcooling once you add the line temperature.

the big insulated line, for superheat

Saturation temperature one saturation column40.0°F

69.0 psig is a published row of the R-22 (Legacy) chart, not an interpolated value.

Add the suction line temperature to get superheat from this reading.

Where this number comes fromIntry Verified
Calculated from
R-22 (Legacy) PT chart. Table looked up from a named datasheet; rack statements quoted from publisher documents, cited beside the sentence. See the full receipt ↓
Run with
  • Pressure69.0 psig, suction line
  • Saturation40.0°F
  • Chart rowa published row of the chart
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 31163 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from the locked modules each figure is traced to: the manufacturer PT tables behind the saturation temperatures, superheat and subcooling, and the transcribed code and service-literature constants behind the charge, metering, airflow, approach and discharge line figures, each quoted with its own source in the panel it appears in. This is our own deterministic gate, not a third-party audit.
Final say
The unit nameplate and the manufacturer's charging chart have final say.
What Intry Verified means

Intry Verified · Build 2731D30 · 2026-10-15

R-22 Pressure-Temperature Table

R-22 saturation temperature at gauge pressure (psig). Single column, zero glide.
R-22
Pressure (psig)Sat. Temp (°F)Publisher spread (°F)
1-40°F1.00
3-35°F0.87
5-30°F0.20
7-25°F0.80
10-20°F0.36
13-15°F0.33
17-10°F0.69
20-5°F0.14
240°F0
285°F0.35
3310°F0.20
3815°F0.19
4320°F0.09
4925°F0.16
5530°F0
6235°F0.35
6940°F0.27
7645°F0.07
8450°F0.06
9355°F0.22
10260°F0.21
11165°F0.15
12170°F0.20
13275°F0.09
14480°F0.17
15685°F0.12
16890°F0.16
18295°F0.07
196100°F0.03
211105°F0.06
226110°F0.13
243115°F0.06
260120°F0

About the spread column. It is the widest gap in saturation temperature between the published tables we hold, at that pressure, on the saturation column. Across this chart the widest is 1.00°F, at 1 psig. Our table and 1 other published table are compared here: 1 is a separate publisher. A narrow spread means the charts agree, which is not the same as the charts being right: they are all computed from equations of state fitted to lab data, and no field measurement settles it.

Where this table comes from. Hudson Technologies R-22 PT chart.
  • Checked against NIST REFPROP 9.0, as printed by iGas and Arkema, agrees to the whole psig at all 33 shipped points, raw spread at most 0.4 psig [separate publisher]

A separate publisher can catch a transcription, edition or rounding error. A cross-check marked same model resolves to the same equation of state as the base table, so it is a consistency check rather than independent confirmation. One marked same printing prints numbers identical to another table listed here, so the two are one witness and we do not count them twice. Sources last re-verified 2026-08-25.

Read the low-side (suction) pressure and find its saturation temperature for superheat, and read the high-side (liquid) pressure and its saturation temperature for subcooling. The chart is in psig (gauge) and °F. To convert: kPa gauge = psig × 6.895; °C = (°F − 32) / 1.8. The table opens in psig and °F; the buttons above it show the same rows in bar or kPa (gauge) and °C.


R-22 PT Chart FAQs

What is the R-22 pressure at 40F and 100F?

On the R-22 PT chart, 40F saturation is about 69 psig and 100F is about 196 psig; 50F is about 84 psig and 120F is about 260 psig. R-22 is a single-component refrigerant with zero glide, so the same saturation temperature serves both superheat (suction) and subcooling (liquid); there is no bubble and dew split.

Is R-22 still available, and can I still buy it?

EPA ended U.S. production and import of R-22 on January 1, 2020, and says an existing R-22 system can still be serviced: "After 2020, only recycled, reclaimed, or previously produced HCFC-22 can be used to service existing equipment."

What refrigerant replaces R-22?

For new equipment, R-454B (ducted) and R-32 (mini splits) are the A2L successors. For servicing an existing R-22 system without replacing it, common retrofit blends include R-407C, R-421A, and R-422B, but a retrofit changes the oil and the target pressures, so always follow the blend manufacturer's retrofit guide rather than reading the system on the R-22 column afterward.

What units is this R-22 PT chart in, and how do I convert to kPa or Celsius?

The table is in psig (gauge pressure) and degrees Fahrenheit, the field-standard units in North America. To convert pressure to kPa (gauge), multiply psig by 6.895. To convert temperature to Celsius, use C = (F - 32) / 1.8. The table opens in psig and degrees Fahrenheit; the buttons above it show the same rows in bar or kPa (gauge) and degrees Celsius.