HVAC · Load calculation
Manual J Load Calculator
The heating and cooling load for a house from the ACCA Manual J worksheets, run against the real design temperatures for the weather station nearest your ZIP. Each component arrives on its own line with the printed table behind it.
What this computes, and what it does not
Worksheet A fixes the design conditions and the temperature differences from the station. Worksheet D prices opaque panels, Worksheet E prices infiltration, the Table 3 procedure prices windows and glass doors, and Manual J Figure 3-1 supplies the internal gain from occupants and appliances. Each arrives as its own line with its own citation.
Duct loads are computed when the duct system is described: the abridged edition's four printed scenarios are copied and the adjustment multiplies the rest of the heating load rather than adding to it. What is not copied is the FULL Table 7 library, 38 printed pages (pages 365 to 402) of grids, so a system outside those four printed arrangements is refused by name rather than fitted to the nearest one. Skylights, external sun screens, glass that is not clear, NFRC-rated products and several construction numbers are named absences too. On a run where no duct term was priced and runs do pass through an unconditioned attic, crawlspace or garage, the true load is higher than every figure reported on that run.
Where the numbers come from
The design conditions are the ASHRAE Handbook of Fundamentals 2021, Chapter 14, climatic design conditions. ACCA Manual J 8th Edition supplies the load procedure these numbers are used in, not the numbers themselves. The ASHRAE Handbook of Fundamentals prints 541 weather stations across 50 states, and this build carries all 541 of them, across all 50 states.
The ZIP is resolved through the US Census Bureau 2020 Gazetteer Files, ZIP Code Tabulation Areas (ZCTA5), accessed 2026-08-08, which publishes an internal point per ZIP Code Tabulation Area. The Census INTPTLAT / INTPTLONG internal point: a point guaranteed to lie inside the ZIP Code Tabulation Area. A ZCTA is a tabulation area built from census blocks to approximate a ZIP code, so this is neither the ZIP's geometric centre nor a postal address. Some ZIP codes have no ZCTA at all, including point codes and PO-box-only codes. A ZIP with no ZCTA is refused by name rather than mapped to a neighbouring area.
What this is not
This is not an ACCA-approved Manual J and it does not replace a permit-grade load calculation. Permits and rebate programmes can require an approved or permit-grade calculation, and what they accept differs by jurisdiction and programme. This page follows the abridged MJ8AE method and is not intended to satisfy them. What it is for is the work before that: sizing a replacement on the truck, checking a load before you quote it, and seeing which inputs actually move the number so you know where to spend your measuring time.
Manual J Load Calculator FAQs
Is there a whole-house total?
A whole-house HEATING total, yes, once you describe the envelope and answer four questions about the site, and a whole-house COOLING load as a sensible and latent PAIR once you answer two more and give the Table 1A daily-range class for your site. Manual J section 4-11 makes the total heating load the sum of seven terms, and four of them go to zero under conditions the book prints: no duct system or all ducts inside the heated space, no mechanical ventilation, no winter humidifier, no piping outside the heated space. Section 5-11 prints a different list for cooling, with seven sensible terms and four latent ones, and it does not contain humidification or piping at all. Each blocker is a question about your house or your equipment rather than a calculation, so this page asks them, shows your answers beside the total, and withholds a total if any is unanswered or if your answer is one Manual J does not zero. It reports a whole-house COOLING load as the PAIR Manual J section 5-12 sizes equipment from: the total sensible load (Form J1ae line 20) and the total latent load (line 21). Either is withheld when a printed term of it is unanswered or has no printed route in the abridged edition, and the specific term is named on the result rather than folded in. The AED excursion adjustment is NOT one of the blockers: Manual J Appendix 3 section A3-2 (printed page 421) prints that for MJ8AE the excursion adjustment is always zero, so it is not one of the reasons. Manual J section 5-12 (printed page 40): "The total sensible and total latent load shall be used for equipment sizing (exactly as they appear on Form J1AE or Form J1) with no 'safety-factor' adjustment." Both halves are needed to select equipment, and a sensible figure on its own is not the cooling load.
Where do the design temperatures come from?
They are the ASHRAE Handbook of Fundamentals 2021 Chapter 14 climatic design conditions, read from the printed pages of that book. ACCA Manual J supplies the load procedure this calculator follows; it is not where these temperatures come from. Your ZIP is resolved to its Census ZIP Code Tabulation Area internal point, and the nearest station held here to that point is used, with the distance shown. The book prints 541 stations across 50 states; 541 are held here and 0 are not. If the nearest station is further from you than any station in the table is from its own nearest neighbour, the calculator stops and says so rather than substituting a station from somewhere else.
Is this an ACCA-approved Manual J?
No. This is not an ACCA-approved Manual J and it does not replace a permit-grade load calculation. It follows the Form J1 worksheet procedure and cites the printed clause behind each figure, and it names the terms it does not compute, but several of those terms are ones a permit-grade calculation must include. Use it to understand and sanity-check a load, not to satisfy a building department.
Why does it refuse instead of estimating?
Because a substituted number is indistinguishable from a correct one once it reaches a result. Every figure downstream of the design conditions is a function of them, so a nearby-instead-of-real station produces a whole load calculation that is confidently wrong and fully traceable to the wrong place. The same rule applies inside the calculation: a window assembly the printed tables do not describe, a skylight, an external sun screen, glass that is not clear, an overhang at a latitude beyond the shade-line table's reach. Each of those is named and left out rather than approximated.
Why does the window section not have a double pane low-e option?
Because Manual J Table 3A-1 prints ONE column headed "Triple Pane or Double Pane Low-e", covering two different assemblies, and this interface selects a column by pane count. There is no honest way to say "double pane, low-e" through that interface, and it is a modern residential window. It is absent and named rather than routed to the nearest-looking column.
Can I submit this for a permit or a rebate?
No. This is not an ACCA-approved Manual J and it does not replace a permit-grade load calculation. Permits and rebate programmes can require an approved or permit-grade calculation, and requirements differ by jurisdiction and programme, so check what yours accepts. This page follows the abridged MJ8AE method and is not intended to satisfy them. What this is for is the work before that: sizing a replacement on the truck, checking a load before you quote it, settling an argument about whether the existing equipment is oversized, and seeing exactly which inputs the answer turns on so you know where to spend your measuring time.
How accurate is the latitude adjustment?
There is none on the windows' basic cooling figure. This calculator follows the abridged method (MJ8AE), and Manual J Figure 3-5 (printed page 18) marks the latitude, foreground and shade-colour adjustment of generic glass "Not supported" in MJ8AE. So each window reads Manual J Table 3A-1 as printed, at the 40 degrees North the table is built for, whatever the site's latitude. Section 19-5 (printed page 153) says of these values: "For hand calculations, these values are used for all cities listed in Table 1 without correction for month or latitude. This practice is acceptable", and the book's own MJ8AE example does the same for a Houston house at latitude 29 (Worksheet B, printed page 56). The full edition's optional latitude correction (Table 3E-2) is not applied, so far from 40 degrees North the window figure can differ from what that correction would give; each window's line on the result names the values it read. Latitude enters in one place: an overhang's shade line, from Table 3E-1, which prints rows for 25 to 50 degrees North (Worksheet B reprints them, printed page 56). The calculator reads the nearest printed row, as that worksheet reads latitude 29 on its 30 row, up to 2.5 degrees beyond that span, and past that it refuses the overhang rather than extrapolating.
Next in the sizing job
Run this inside your AI assistant
Prefer to just ask? Add this to Claude.
Connect Intry to Claude once, then just say “use Intry to…” to run the manual j load calculator from a plain-English question, on your phone, on the job. You get the number (computed live, not guessed), what it means, and the ACCA Manual J 8th Edition Form J1 worksheet procedure and the ASHRAE Chapter 14 design conditions it was computed from. Works on every Claude plan.