NEC 310.16 Wire Sizing

What Size Wire for a 40 Amp Breaker?

The copper and aluminum conductor, ground wire, and code basis for a 40 amp circuit, per NEC Table 310.16. Common on electric ranges, cooktops, and hardwired EV chargers.

Quick answer: A 40 amp circuit needs #8 copper or #6 aluminum at the 60°C column, the NEC default for terminations 100A and under and the required column for NM-B cable (110.14(C)(1)(a), 334.80), with a #10 copper ground (250.122). Size up for a continuous load (125%) or a long run (voltage drop). Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)).

Wire Size by Breaker Amperage (NEC 310.16, 75°C)

Copper and aluminum conductor and copper ground by breaker rating. Sized to the 75°C column, which on a circuit of 100A or less holds only where the breaker and the equipment are both listed and identified for 75°C conductors (NEC 110.14(C)(1)(a)(3)); unmarked terminations and NM-B cable (NEC 334.80) take the 60°C column; the 240.4(D) small-conductor limits are applied.

Minimum copper and aluminum wire size and copper ground by breaker amperage, NEC 310.16 and 250.122

Swipe the table sideways to see the rest of its columns. →

BreakerCopperAluminumEGC (Cu)
20A#12#10#12
30A#10#8#10
40A#8#8#10
50A#8#6#10
60A#6#4#10
100A#3#1#8
200A3/0250 kcmil#6

Copper THHN/THWN-2 at the 75°C column (75°C-listed terminals). For NM-B cable (Romex), use the 60°C column per NEC 334.80 and 110.14(C)(1)(a). A dwelling service, or a feeder carrying a dwelling's entire load, at single-phase 120/240 V can use NEC 310.12; a feeder carrying only part of the load cannot. Verify terminal temperature rating and voltage drop on long runs.


How a 40 Amp Circuit Is Sized

The breaker protects the conductor, so the conductor ampacity must be at least the breaker rating (NEC 240.4). For a 40 amp breaker, the smallest 75°C copper conductor that meets or exceeds 40 amps is #8, and the aluminum equivalent is #8 (on 75°C-marked terminations; #6 aluminum at 60°C or on NM-B cable). For #14, #12, and #10, the 240.4(D) small-conductor rule caps the breaker at 15, 20, and 30 amps regardless of the table ampacity.

Continuous loads. If the load runs for three hours or more (an EV charger, for example), NEC 210.19(A) and 210.20(A) require sizing at 125% of the load. A load near 40 amps continuous is sized like the next circuit up, so the #8 copper this page leads with may need to increase a size. The chart above is for standard, non-continuous loads.


Size a Specific Circuit

Enter your load, run length, insulation, and conditions for NEC 310.16 sizing with temperature derating, bundling, and terminal temperature limits; the result links to the voltage drop calculator, which checks that wire over your run; this tool does not size for voltage drop. It opens on this page's 40 A breaker rating as the load, at the 60°C column.

Loading calculator...

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

What size wire do I need for a 40 amp breaker?

A 40 amp circuit needs #8 copper or #6 aluminum at the 60°C column of NEC Table 310.16, which is the NEC 110.14(C)(1)(a) default for terminations rated 100A and under and the required column for NM-B cable (Romex) per 334.80. The equipment grounding conductor is #10 copper per NEC Table 250.122. This is for a standard load; a continuous load (three hours or more) must be sized at 125%, which bumps the conductor up a size. Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)).

Can I use aluminum wire for a 40 amp breaker?

Yes. Aluminum is allowed and common on larger circuits and services where it saves on cost. For a 40 amp breaker, use #8 aluminum at the 75°C column (on 75°C-marked terminations; #6 aluminum at 60°C or on NM-B cable) versus #8 copper. Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)). Apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops more voltage, so check the run length on long pulls.

What size ground wire for a 40 amp breaker?

The equipment grounding conductor for a 40 amp circuit is #10 copper, per NEC Table 250.122. The EGC is sized by the breaker rating, not the circuit conductors, and it does not carry current in normal operation. If you upsize the circuit conductors for voltage drop, the EGC must be upsized proportionally per 250.122(B).

Does a continuous load change the wire size for a 40 amp circuit?

Yes. For a continuous load (one that runs for three hours or more, like an EV charger), NEC 210.19(A) and 210.20(A) require the conductor and breaker to be rated at 125% of the load. So a load pulling close to 40 amps continuously is sized like the next circuit up, and the #8 copper this page leads with may need to increase a size. The chart on this page is for standard (non-continuous) loads.

Do I size the wire to the breaker or to the load?

Size the conductor to the load first, then protect it with a breaker at or above the conductor rating (NEC 240.4). The breaker protects the wire, so the wire ampacity must be at least the breaker rating, with the small-conductor limits of 240.4(D) for #14, #12, and #10. On long runs, voltage drop can force a larger conductor than ampacity alone requires.


Wire Size for Other Breakers

Long run or a continuous load? Check it.

Ampacity is only half the job. A 40 amp circuit can pass the table and still fail on voltage drop over distance. Run the numbers before you pull the wire.