NEC Voltage Drop Reference

Voltage Drop Chart

Maximum one-way run distance at the NEC-recommended 3% voltage drop, for copper and aluminum, by wire size and circuit. Plus the K-factor formula, the allowable-drop table for every common system voltage, and conductor circular mils.

Quick answer: Single-phase voltage drop = (2 × K × I × L) / CM, where K is 12.9 for copper and 21.2 for aluminum. Keep it under 3% on a branch circuit (3.6V on 120V, 7.2V on 240V) and 5% total with the feeder. Example: 20A on 120V copper #12 reaches about 45 feet before it hits 3%.

Intry Verified. The circular mils, K-factors, and NEC 240.4 overcurrent limits behind this chart are the locked, re-checked engine constants; the maximum run distances are derived from them by the published K-factor formula (VD = 2·K·I·L / CM) on every build. Those figures are computed by a locked engine straight from the source it cites, not hand-typed, and that computation re-runs inside a deterministic test on every deploy. Source-checked. Locked. This is our own deterministic gate, not a third-party audit. What Intry Verified means

Run this in your AI. Ask Claude or ChatGPT to check the voltage drop for a 20 amp 120 volt copper circuit at 100 feet and it runs the Intry voltage_drop tool live, handing back the verdict with its cited source instead of a guess. Then keep the reading as one job in the Intry app.

The Voltage Drop Formula (K-Factor Method)

The K-factor (or circular-mil) method is the standard field formula for estimating voltage drop on a conductor run:

Single-phase: VD = (2 × K × I × L) / CM
Three-phase: VD = (1.732 × K × I × L) / CM
  • K = resistivity constant: 12.9 for copper, 21.2 for aluminum (ohms-cmil/ft at 75°C).
  • I = load current in amps.
  • L = one-way length of the run in feet.
  • CM = conductor cross-sectional area in circular mils (see the table below).

To reverse-solve for the minimum wire size, rearrange to CM = (2 × K × I × L) / VD_allowed, then pick the next standard conductor with at least that many circular mils.


Allowable Voltage Drop by System Voltage

The NEC recommends 3% maximum on a branch circuit and 5% total for feeder plus branch (NEC 210.19(A) and 215.2 informational notes). These are the voltages those percentages work out to, and the minimum voltage still present at the load at the 3% limit.

Allowable voltage drop in volts at the 3% and 5% NEC recommendations, by nominal system voltage
System Voltage3% Drop5% DropVoltage at Load (3%)
120V3.6 V6.0 V116.4 V
208V6.2 V10.4 V201.8 V
240V7.2 V12.0 V232.8 V
277V8.3 V13.9 V268.7 V
480V14.4 V24.0 V465.6 V

Maximum Copper Wire Run at 3% Drop

The farthest one-way distance each copper wire size can run before exceeding 3% voltage drop, by circuit. Single-phase, computed as (CM × V × 0.03) / (2 × 12.9 × I) and floored to whole feet. Double these for the 5% limit. Cells marked “n/a” are code-impossible pairings under NEC 240.4: the circuit breaker exceeds the largest overcurrent device that conductor may sit on, so the wire is not permitted on that circuit at any run length. The small conductors are capped by 240.4(D) (#14 copper at 15A, #12 at 20A, #10 at 30A); the larger ones are capped by their 75°C ampacity and 240.4(B), so #8 copper (50A) and #6 (65A, one size up to 70A) cannot ride a 100A circuit.

Maximum one-way copper wire run distance (feet) at 3% voltage drop, by wire size and circuit
Wire Size20A / 120V20A / 240V30A / 240V50A / 240V100A / 240V
#14n/an/an/an/an/a
#1245 ft91 ftn/an/an/a
#1072 ft144 ft96 ftn/an/a
#8115 ft230 ft153 ft92 ftn/a
#6183 ft366 ft244 ft146 ftn/a
#4291 ft582 ft388 ft232 ftn/a
#2462 ft925 ft617 ft370 ft185 ft
1/0736 ft1473 ft982 ft589 ft294 ft
2/0928 ft1857 ft1238 ft742 ft371 ft
4/01476 ft2952 ft1968 ft1181 ft590 ft

Maximum Aluminum Wire Run at 3% Drop

The same chart for aluminum conductors (K = 21.2). Aluminum drops more voltage than copper for a given size, so the distances are shorter. Aluminum is common on feeders and services where the cost per amp wins out. As on the copper chart, “n/a” cells are code- impossible under NEC 240.4: aluminum ampacity runs about one size behind copper, so #8 aluminum (40A) cannot ride a 50A or 100A circuit and #6 (50A) cannot ride 100A.

Maximum one-way aluminum wire run distance (feet) at 3% voltage drop, by wire size and circuit
Wire Size20A / 120V20A / 240V30A / 240V50A / 240V100A / 240V
#870 ft140 ft93 ftn/an/a
#6111 ft222 ft148 ft89 ftn/a
#4177 ft354 ft236 ft141 ftn/a
#2281 ft563 ft375 ft225 ftn/a
1/0448 ft896 ft597 ft358 ft179 ft
2/0565 ft1130 ft753 ft452 ft226 ft
4/0898 ft1796 ft1197 ft718 ft359 ft
250 kcmil1061 ft2122 ft1415 ft849 ft424 ft
350 kcmil1485 ft2971 ft1981 ft1188 ft594 ft

Calculate Your Exact Run

The charts assume single-phase at 3%. Enter your material, wire size, load, length, and voltage for an exact percent drop, or reverse-solve for the minimum wire size that meets 3%.

Intry VerifiedA worked default reading, traceable end to end: what it was calculated from, what it was run with, how it was checked, and who has final say.

Over the 3% guideline3.29% drop, over 3%
Where this number comes fromIntry Verified
Calculated from
NEC 210.19 Note, 3% guideline
Run with
  • Wire#12 AWG
  • Load20 A
  • One-way length100 ft
  • System240 V, 1-phase
  • MaterialCopper
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 21026 automated checks re-derive and source-check the numbers against the cited NEC section before each deploy. This is our own deterministic gate, not a third-party audit.
Final say
Your AHJ and local amendments have final say. Confirm before rough-in.
What Intry Verified means

Intry Verified · NEC 2023 · Build AE2FC52 · 2026-08-21



Worked Example: 20A Circuit, 120V, 100 ft Copper

Given: A 20A branch circuit on 120V single-phase, #12 copper THHN, running 100 feet one-way to the farthest outlet.

Step 1: Apply the formula. VD = (2 × 12.9 × 20 × 100) / 6,530 = 7.90 V.

Step 2: Convert to percent. 7.90 / 120 × 100 = 6.58%. That is well over the 3% recommendation, and the load only sees 112.1V.

Fix: Upsize to #10 copper (10,380 CM): VD = (2 × 12.9 × 20 × 100) / 10,380 = 4.97V or 4.14%, within 5% but still over 3%. The copper chart above confirms #12 tops out near 45 ft at 20A/120V, so a 100 ft run needs #8 for full 3% compliance.


Frequently Asked Questions

How far can you run wire before voltage drop is a problem?

A #12 copper branch circuit at 20A/120V can run about 45 feet before it hits the 3% voltage-drop limit, and roughly 91 feet at 240V since the allowable drop doubles with the voltage. NEC does not mandate a limit, but the Informational Notes at 210.19(A) (branch circuits) and 215.2(A) (feeders) recommend keeping branch-circuit drop under 3% and combined feeder-plus-branch drop under 5% for reasonable efficiency. To size any run yourself, use the K-factor method: VD = (2 × K × I × L) / CM, where K is 12.9 for copper, I is amps, L is one-way length in feet, and CM is the conductor's circular mils (6,530 for #12), then solve for the length that keeps VD at or below 3% of your system voltage. See the chart on this page for max lengths at 3% by AWG, load, and voltage so you can pick the run without doing the math.

What is the NEC voltage drop formula?

For a single-phase circuit, voltage drop = (2 x K x I x L) / CM, where K is the conductor resistivity constant (12.9 for copper, 21.2 for aluminum), I is the load current in amps, L is the one-way run length in feet, and CM is the conductor area in circular mils. For three-phase, replace the 2 with 1.732 (the square root of 3). Percent drop = voltage drop divided by system voltage, times 100.

What is an acceptable voltage drop?

The NEC recommends a maximum of 3% voltage drop on a branch circuit and 5% total for feeder plus branch circuits combined (NEC 210.19(A) and 215.2 informational notes). On a 120V circuit, 3% is 3.6V and 5% is 6.0V. These are recommendations, not enforceable requirements, but most inspectors and engineers treat 3% as the practical target. For sensitive electronics, aim for 2% or less.

How far can I run 12 gauge wire?

On a 20A 120V copper circuit at the 3% limit, #12 AWG copper reaches about 45 feet one-way. At 240V the same wire and load reaches about 91 feet, because doubling the voltage halves the percent drop. Aluminum #12 reaches roughly 27 feet at 120V. See the copper and aluminum charts on this page for every common wire size and circuit.

How much farther can I run wire at 240V versus 120V?

Twice as far. Percent voltage drop is inversely proportional to system voltage, so at the same wire size and current, a 240V circuit has half the percent drop of a 120V circuit. That means you can run the wire about twice the distance before hitting the 3% limit. This is why long runs to detached garages, well pumps, and EV chargers are almost always wired at 240V.

Does aluminum wire have more voltage drop than copper?

Yes. Aluminum has a K-factor of 21.2 versus 12.9 for copper, so an aluminum conductor of the same size drops about 64% more voltage than copper. To match copper's run distance you generally go up about two wire sizes in aluminum. Aluminum is still common for feeders and services because it is cheaper per amp of capacity, but you must account for the higher drop on long runs.

Is the maximum run distance based on ampacity or voltage drop?

The charts on this page are limited by voltage drop only, at the 3% recommendation. Ampacity (NEC 310.16) is a separate, independent check: a wire can pass ampacity and still fail voltage drop on a long run, or vice versa. Always size the conductor to satisfy both. Use the wire size calculator for the ampacity side with derating and terminal temperature limits.


Related Calculators

Distance checks out? Confirm the ampacity side.

Voltage drop and ampacity are independent checks. A wire that clears the run distance can still fail NEC 310.16. Run the wire size calculator with derating and terminal temperature limits so the whole circuit holds up.