NEC 310.16 Wire Sizing

What Size Wire for a 200 Amp Breaker?

The copper and aluminum conductor, ground wire, and code basis for a 200 amp circuit, per NEC Table 310.16. Common on a standard modern home service.

Quick answer: A 200 amp single-phase 120/240 V dwelling service needs 2/0 copper or 4/0 aluminum (NEC 310.12, the 83% dwelling rule), with a #4 copper grounding electrode conductor (Table 250.66). A 200 amp feeder that is not a dwelling service uses 3/0 copper at the 75°C column with a #6 copper EGC. Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)).

Wire Size by Breaker Amperage (NEC 310.16, 75°C)

Copper and aluminum conductor and copper ground by breaker rating. Sized to the 75°C column, which on a circuit of 100A or less holds only where the breaker and the equipment are both listed and identified for 75°C conductors (NEC 110.14(C)(1)(a)(3)); unmarked terminations and NM-B cable (NEC 334.80) take the 60°C column; the 240.4(D) small-conductor limits are applied.

Minimum copper and aluminum wire size and copper ground by breaker amperage, NEC 310.16 and 250.122

Swipe the table sideways to see the rest of its columns. →

BreakerCopperAluminumEGC (Cu)
20A#12#10#12
30A#10#8#10
40A#8#8#10
50A#8#6#10
60A#6#4#10
100A#3#1#8
200A3/0250 kcmil#6

Copper THHN/THWN-2 at the 75°C column (75°C-listed terminals). For NM-B cable (Romex), use the 60°C column per NEC 334.80 and 110.14(C)(1)(a). A dwelling service, or a feeder carrying a dwelling's entire load, at single-phase 120/240 V can use NEC 310.12; a feeder carrying only part of the load cannot. Verify terminal temperature rating and voltage drop on long runs.


Size the Service: Conductors and Grounding Electrode Conductor

Pick the service rating (or bring it from the load calculator) and the metal. This sizes the service conductors by NEC 310.12(A) and the grounding electrode conductor by Table 250.66, shows the math, saves to a job, and opens conduit fill with these conductors.

Loading the service sizer...

How a 200 Amp Circuit Is Sized

The breaker protects the conductor, so the conductor ampacity must be at least the breaker rating (NEC 240.4). For a 200 amp breaker, the smallest 75°C copper conductor that meets or exceeds 200 amps is 3/0, and the aluminum equivalent is 250 kcmil. For #14, #12, and #10, the 240.4(D) small-conductor rule caps the breaker at 15, 20, and 30 amps regardless of the table ampacity.

The dwelling exception (NEC 310.12). A single-phase 120/240 V dwelling service, or a feeder carrying the dwelling's entire load, can be sized at 83% of the rating. That is why a 200 amp home service can run 2/0 copper or 4/0 aluminum instead of the 3/0 copper a 200 amp branch circuit would require. Confirm your load with a service calculation before you rely on the exception.


Size a Specific Circuit

Enter your load, run length, insulation, and conditions for NEC 310.16 sizing with temperature derating, bundling, and terminal temperature limits; the result links to the voltage drop calculator, which checks that wire over your run; this tool does not size for voltage drop. It opens on a 200 A load at the 75°C column, the feeder answer above. It does not apply the dwelling service rule, so it will not return the smaller service size.

Loading calculator...

Frequently Asked Questions

What size wire do I need for a 200 amp breaker?

A 200 amp single-phase 120/240 V dwelling service needs 2/0 copper or 4/0 aluminum under the NEC 310.12 dwelling allowance (conductors rated for 83% of the service rating). Its grounding electrode conductor is #4 copper, sized from the service conductors per NEC Table 250.66. A 200 amp feeder that is not a dwelling service is sized at the 75°C column of Table 310.16 (3/0 copper) and grounded by a #6 copper equipment grounding conductor per Table 250.122.

Can I use aluminum wire for a 200 amp breaker?

Yes. Aluminum is allowed and common on larger circuits and services where it saves on cost. For a 200 amp breaker, use 250 kcmil aluminum at the 75°C column versus 3/0 copper. Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)). Apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops more voltage, so check the run length on long pulls.

What size ground wire for a 200 amp breaker?

It depends on whether this is a service or a feeder. For a 200 amp dwelling service, the grounding electrode conductor (GEC) is #4 copper or #2 aluminum, sized from the service-entrance conductors per NEC Table 250.66 (not by the breaker). If this 200 amp panel is instead a subpanel fed by a feeder, the equipment grounding conductor run with the feeder is #6 copper per NEC Table 250.122. A service uses a GEC to the grounding electrodes; a feeder or branch circuit uses a 250.122 EGC.

Why can a 200 amp service use smaller wire than a 200 amp branch circuit?

NEC 310.12 lets a single-phase 120/240 V dwelling service, or a feeder carrying the dwelling's entire load, use conductors rated for 83% of the service rating. That is why a 200 amp home service can use 2/0 copper or 4/0 aluminum instead of the 3/0 copper a 200 amp branch circuit would need. The exception applies only to dwelling services and main feeders, not general branch circuits.

Do I size the wire to the breaker or to the load?

Size the conductor to the load first, then protect it with a breaker at or above the conductor rating (NEC 240.4). The breaker protects the wire, so the wire ampacity must be at least the breaker rating, with the small-conductor limits of 240.4(D) for #14, #12, and #10. On long runs, voltage drop can force a larger conductor than ampacity alone requires.


Wire Size for Other Breakers

Long run or a continuous load? Check it.

Ampacity is only half the job. A 200 amp circuit can pass the table and still fail on voltage drop over distance. Run the numbers before you pull the wire.