NEC 310.16 Wire Sizing

What Size Wire for a 200 Amp Breaker?

The copper and aluminum conductor, ground wire, and code basis for a 200 amp circuit, per NEC Table 310.16. Common on a standard modern home service.

Quick answer: A 200 amp single-phase dwelling service needs 2/0 copper or 4/0 aluminum (NEC 310.12, the 83% dwelling rule), with a #4 copper grounding electrode conductor (Table 250.66). A 200 amp feeder that is not a dwelling service uses 3/0 copper at the 75°C column with a #6 copper EGC.

Wire Size by Breaker Amperage (NEC 310.16, 75°C)

Copper and aluminum conductor and copper ground by breaker rating. Sized to the 75°C column with the 240.4(D) small-conductor limits applied.

Minimum copper and aluminum wire size and copper ground by breaker amperage, NEC 310.16 and 250.122
BreakerCopperAluminumEGC (Cu)
20A#12#10#12
30A#10#8#10
40A#8#8#10
50A#8#6#10
60A#6#4#10
100A#3#1#8
200A3/0250 kcmil#6

Copper THHN/THWN-2 at the 75°C column (75°C-listed terminals). For NM-B cable (Romex), use the 60°C column per NEC 334.80 and 110.14(C)(1)(a). Service and feeder ratings can use the NEC 310.12 dwelling exception. Verify terminal temperature rating and voltage drop on long runs.


How a 200 Amp Circuit Is Sized

The breaker protects the conductor, so the conductor ampacity must be at least the breaker rating (NEC 240.4). For a 200 amp breaker, the smallest 75°C copper conductor that meets or exceeds 200 amps is 3/0, and the aluminum equivalent is 250 kcmil. For #14, #12, and #10, the 240.4(D) small-conductor rule caps the breaker at 15, 20, and 30 amps regardless of the table ampacity.

The dwelling exception (NEC 310.12). A single-phase dwelling service or main power feeder can be sized at 83% of the rating, because a home rarely draws its full service continuously. That is why a 200 amp home service commonly runs 2/0 copper or 4/0 aluminum instead of the 3/0 copper a 200 amp branch circuit would require. Confirm your load with a service calculation before you rely on the exception.


Size a Specific Circuit

Enter your load, run length, insulation, and conditions for NEC 310.16 sizing with temperature derating, bundling, and terminal temperature limits; the result links to the voltage drop calculator, which checks that wire over your run; this tool does not size for voltage drop. It opens on a 200 A load at the 75°C column, the feeder answer above. It does not apply the dwelling service rule, so it will not return the smaller service size.

Loading calculator...

Frequently Asked Questions

What size wire do I need for a 200 amp breaker?

A 200 amp single-phase dwelling service needs 2/0 copper or 4/0 aluminum under the NEC 310.12 dwelling allowance (conductors rated for 83% of the service rating). Its grounding electrode conductor is #4 copper, sized from the service conductors per NEC Table 250.66. A 200 amp feeder that is not a dwelling service is sized at the 75°C column of Table 310.16 (3/0 copper) and grounded by a #6 copper equipment grounding conductor per Table 250.122.

Can I use aluminum wire for a 200 amp breaker?

Yes. Aluminum is allowed and common on larger circuits and services where it saves on cost. For a 200 amp breaker, use 250 kcmil aluminum at the 75°C column versus 3/0 copper. Apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops more voltage, so check the run length on long pulls.

What size ground wire for a 200 amp breaker?

It depends on whether this is a service or a feeder. For a 200 amp dwelling service, the grounding electrode conductor (GEC) is #4 copper or #2 aluminum, sized from the service-entrance conductors per NEC Table 250.66 (not by the breaker). If this 200 amp panel is instead a subpanel fed by a feeder, the equipment grounding conductor run with the feeder is #6 copper per NEC Table 250.122. A service uses a GEC to the grounding electrodes; a feeder or branch circuit uses a 250.122 EGC.

Why can a 200 amp service use smaller wire than a 200 amp branch circuit?

NEC 310.12 lets a single-phase dwelling service or main power feeder use conductors rated for 83% of the service rating, because a whole house rarely draws its full rating continuously. That is why a 200 amp home service commonly uses 2/0 copper or 4/0 aluminum instead of the 3/0 copper a 200 amp branch circuit would need. The exception applies only to dwelling services and main feeders, not general branch circuits.

Do I size the wire to the breaker or to the load?

Size the conductor to the load first, then protect it with a breaker at or above the conductor rating (NEC 240.4). The breaker protects the wire, so the wire ampacity must be at least the breaker rating, with the small-conductor limits of 240.4(D) for #14, #12, and #10. On long runs, voltage drop can force a larger conductor than ampacity alone requires.


Wire Size for Other Breakers

Long run or a continuous load? Check it.

Ampacity is only half the job. A 200 amp circuit can pass the table and still fail on voltage drop over distance. Run the numbers before you pull the wire.