NEC 310.16 Wire Sizing
What Size Wire for a 200 Amp Breaker?
The copper and aluminum conductor, ground wire, and code basis for a 200 amp circuit, per NEC Table 310.16. Common on a standard modern home service.
Wire Size by Breaker Amperage (NEC 310.16, 75°C)
Copper and aluminum conductor and copper ground by breaker rating. Sized to the 75°C column with the 240.4(D) small-conductor limits applied.
| Breaker | Copper | Aluminum | Ground (Cu) |
|---|---|---|---|
| 20A | #12 | #10 | #12 |
| 30A | #10 | #8 | #10 |
| 40A | #8 | #8 | #10 |
| 50A | #8 | #6 | #10 |
| 60A | #6 | #4 | #10 |
| 100A | #3 | #1 | #8 |
| 200A | #3/0 | 250 kcmil | #6 |
Copper THHN/THWN-2 at the 75°C column (110.14(C)). Service and feeder ratings can use the NEC 310.12 dwelling exception. Verify terminal temperature rating and voltage drop on long runs.
How a 200 Amp Circuit Is Sized
The breaker protects the conductor, so the conductor ampacity must be at least the breaker rating (NEC 240.4). For a 200 amp breaker, the smallest 75°C copper conductor that meets or exceeds 200 amps is #3/0, and the aluminum equivalent is 250 kcmil. For #14, #12, and #10, the 240.4(D) small-conductor rule caps the breaker at 15, 20, and 30 amps regardless of the table ampacity.
The dwelling exception (NEC 310.12). A single-phase dwelling service or main power feeder can be sized at 83% of the rating, because a home rarely draws its full service continuously. That is why a 200 amp home service commonly runs #2/0 copper or #4/0 aluminum instead of the #3/0 copper a 200 amp branch circuit would require. Confirm your load with a service calculation before you rely on the exception.
Size a Specific Circuit
Enter your load, run length, insulation, and conditions for exact NEC 310.16 sizing with temperature derating, bundling, terminal temperature limits, and voltage drop.
Frequently Asked Questions
What size wire do I need for a 200 amp breaker?
A 200 amp breaker needs #3/0 copper or 250 kcmil aluminum conductors, sized at the 75°C column of NEC Table 310.16 (the standard termination rating under 110.14(C)). The equipment grounding conductor is #6 copper per NEC Table 250.122. For a single-phase dwelling service or main power feeder, NEC 310.12 allows a smaller conductor: #2/0 copper or #4/0 aluminum.
Can I use aluminum wire for a 200 amp breaker?
Yes. Aluminum is allowed and common on larger circuits and services where it saves on cost. For a 200 amp breaker, use 250 kcmil aluminum at the 75°C column versus #3/0 copper. Apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops more voltage, so check the run length on long pulls.
What size ground wire for a 200 amp breaker?
The equipment grounding conductor for a 200 amp circuit is #6 copper, per NEC Table 250.122. The EGC is sized by the breaker rating, not the circuit conductors, and it does not carry current in normal operation. If you upsize the circuit conductors for voltage drop, the EGC must be upsized proportionally per 250.122(B).
Why can a 200 amp service use smaller wire than a 200 amp branch circuit?
NEC 310.12 lets a single-phase dwelling service or main power feeder use conductors rated for 83% of the service rating, because a whole house rarely draws its full rating continuously. That is why a 200 amp home service commonly uses #2/0 copper or #4/0 aluminum instead of the #3/0 copper a 200 amp branch circuit would need. The exception applies only to dwelling services and main feeders, not general branch circuits.
Do I size the wire to the breaker or to the load?
Size the conductor to the load first, then protect it with a breaker at or above the conductor rating (NEC 240.4). The breaker protects the wire, so the wire ampacity must be at least the breaker rating, with the small-conductor limits of 240.4(D) for #14, #12, and #10. On long runs, voltage drop can force a larger conductor than ampacity alone requires.
Wire Size for Other Breakers
20 Amp Wire Size
#12 copper or #10 aluminum, #12 ground.
30 Amp Wire Size
#10 copper or #8 aluminum, #10 ground.
40 Amp Wire Size
#8 copper or #8 aluminum, #10 ground.
50 Amp Wire Size
#8 copper or #6 aluminum, #10 ground.
60 Amp Wire Size
#6 copper or #4 aluminum, #10 ground.
100 Amp Wire Size
#3 copper or #1 aluminum, #8 ground.
Wire Size Calculator
Full NEC 310.16 sizing with derating, bundling, and terminal temperature limits.
Voltage Drop Chart
Max copper and aluminum run distances at 3% drop, for long runs.
Long run or a continuous load? Check it.
Ampacity is only half the job. A 200 amp circuit can pass the table and still fail on voltage drop over distance. Run the numbers before you pull the wire.