NEC Chapter 9 Conduit Fill

What Size Conduit for 6/2 Wire?

The smallest conduit for 6/2 (two #6 plus one #10 ground) in EMT, PVC, RMC, and IMC at the NEC fill limit, with the area math and the calculator for any other mix.

Quick answer: 6/2 wire (two #6 plus one #10 ground, 3 conductors = 0.1225 sq in) needs 3/4″ EMT or 3/4″ PVC at the NEC 40% fill limit. Used for a 50-60A 240V load such as a water heater or A/C.

Minimum Conduit for 6/2 by Type

Smallest conduit that holds 6/2 (two #6 plus one #10 ground) at the NEC 40% fill limit

Swipe the table sideways to see the rest of its columns. →

Conduit TypeMinimum Size
EMT3/4"
Schedule 40 PVC3/4"
RMC1/2"
IMC1/2"

3 THHN conductors totaling 0.1225 sq in (NEC Chapter 9 Table 5). With three or more conductors the fill limit is 40% (Table 1), so the required internal area is 0.1225 ÷ 0.40 = 0.306 sq in, and each type's smallest trade size at or above that is shown.


Different Conductors? Calculate It

For a different wire mix, insulation type, or added conductors, enter your exact pull for the precise fill percentage and the smallest compliant conduit. The calculator opens on this page's 6/2 THHN set in 3/4″ EMT.

23.0%
conduit fill
NEC PASSThreshold: 40% (3+ conductors)

Within fill: 23.0% of 40%, room for 1 more #6

#6 AWG THHN × 20.1014 sq in
#10 AWG THHN × 10.0211 sq in
Total conductor area0.1225 sq in
Conduit area (3/4" EMT)0.5330 sq in
Remaining space0.0907 sq in
Show the math
  1. GIVENConduit: 3/4" EMT; 3 conductors
  2. TABLE#6 AWG THHN: 0.0507 sq in each × 2 = 0.1014 sq inNEC Chapter 9 Table 5
  3. TABLE#10 AWG THHN: 0.0211 sq in each × 1 = 0.0211 sq inNEC Chapter 9 Table 5
  4. MATHTotal conductor area: 0.1225 sq inNEC Chapter 9 Table 5
  5. TABLE3/4" EMT total area: 0.5330 sq inNEC Chapter 9 Table 4
  6. TABLEFill limit for 3+ conductors: 40%, an allowable area of 0.2132 sq inNEC Chapter 9 Table 1
  7. MATHFill = 0.1225 / 0.5330 × 100 = 23.0%NEC Chapter 9 Table 1
  8. RESULTFill: 23.0% of a 40% limitNEC Ch. 9 Tables 1, 4, 5
  9. RESULTStatus: NEC PASSNEC Ch. 9 Tables 1, 4, 5
Where this number comes fromIntry Verified
Calculated from
NEC Ch. 9 Tables 1, 4, 5. Computed from NEC Chapter 9 Table 1 (fill percent), Table 4 (conduit area) and Table 5 (conductor area), with Note 7's round-up at a decimal of 0.8 or more for conductors all of one size. See the full receipt ↓
Run with
  • Conduit3/4" EMT
  • Conductors2 #6 AWG THHN, 1 #10 AWG THHN
  • Fill limit40%
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit.
Final say
Your AHJ and local amendments have final say. Confirm before rough-in.
What Intry Verified means

Intry Verified · NEC 2023 · Build 525536D · 2026-11-13

Bend this EMT →
23.0% fillNEC PASS

Frequently Asked Questions

What size conduit do I need for 6/2 wire?

6/2 wire pulled as individual THHN conductors (two #6 plus one #10 ground) needs 3/4 inch EMT, or 3/4 inch Schedule 40 PVC, at the NEC 40% fill limit. The 3 conductors total 0.1225 square inches (NEC Chapter 9 Table 5); with three or more conductors the raceway may be filled to 40%, so the smallest conduit whose 40% area covers 0.1225 sq in is 3/4 inch EMT.

What is the minimum EMT size for 6/2?

3/4 inch EMT. Its internal area at 40% fill exceeds the 0.1225 sq in that 6/2 (two #6 plus one #10 ground) occupies. Going one trade size down would exceed 40% and violate NEC Chapter 9 Table 1. If you are running RMC use 1/2 inch; IMC and PVC each have their own internal area, shown in the table above.

Does the ground wire count for conduit fill on 6/2?

Yes. Every conductor in the raceway counts for fill, including the equipment grounding conductor (NEC Chapter 9 Table 1). That is why 6/2 is figured here as two #6 plus one #10 ground: the 3 conductors together, not just the current-carrying ones. Leaving the ground out of the count is a conduit-fill mistake.

Can I use 6/2 as NM cable (Romex) in conduit instead?

If you sleeve an intact 6/2 NM cable (Romex) rather than pulling individual THHN, the fill is figured differently: a single cable is treated at the 53% one-conductor limit using the cable's actual cross-sectional area (NEC Chapter 9, Note 9), which can need a larger conduit than individual THHN. The 3/4 inch answer above assumes individual THHN conductors.


Conduit Size for Other Wire

Conduit sized. Will the wire reach?

Getting 6/2 in the pipe is one thing. Confirm the gauge holds up over the run length with the voltage drop calculator before you pull.