NEC Chapter 9 Conduit Fill

What Size Conduit for Your Wire?

You know the wire; find the pipe. The minimum conduit size for common pulls in EMT, PVC, RMC, and IMC, computed from the NEC Chapter 9 fill limits, with the area math for each.

Quick answer: Add every conductor's area (NEC Chapter 9 Table 5, include the ground), divide by 0.40 for three or more conductors, and pick the smallest conduit whose internal area meets it (Table 4). The common pulls are worked out below.

Minimum Conduit for Common Wire (THHN, 40% Fill)

Smallest EMT, PVC, RMC, and IMC for common wire pulls as individual THHN (NEC Chapter 9)

Swipe the table sideways to see the rest of its columns. →

WireEMTPVCRMCIMC
6/33/4"3/4"3/4"3/4"
6/23/4"3/4"1/2"1/2"
8/33/4"3/4"3/4"1/2"
8/21/2"1/2"1/2"1/2"
10/31/2"1/2"1/2"1/2"
10/21/2"1/2"1/2"1/2"
12/31/2"1/2"1/2"1/2"
12/21/2"1/2"1/2"1/2"

Each pull is figured as individual THHN conductors including the equipment ground. Click a wire for the conductor breakdown, the area math, and the calculator.


Pick Your Wire


Frequently Asked Questions

How do I find what size conduit I need for my wire?

Add the cross-sectional area of every conductor from NEC Chapter 9 Table 5 (including the ground), then divide by the fill limit: 40% for three or more conductors, 31% for two, 53% for one. The result is the minimum internal area, and you pick the smallest conduit trade size at or above it from NEC Chapter 9 Table 4. For example, 10/3 as individual THHN is four #10 conductors (0.0844 sq in total), which fits 1/2 inch EMT (0.304 sq in x 40% = 0.122 sq in allowable).

Does the ground count when sizing conduit?

Yes. Every conductor in the raceway counts for fill per NEC Chapter 9 Table 1, including the equipment grounding conductor. Forgetting the ground can make a pull come out one conduit size too small.