Bending Calculator
Stick Builder
Many bends on one length of conduit: list them in order from one end and get every mark from that end, the cut length, the mark table and a 3D of the finished stick, with every arc checked against the bend radius for the size.
The Composition Rule, Stated as the Site's Own
The bender manuals this site holds teach single bends and the star-point back-to-back; none prints a chain formula for a stick. So this tool composes the single-bend marks those documents do teach, by these rules, and invents no mark of its own:
- Every bend is a family this calculator already carries, called at its own inputs: its marks, its multiplier basis and its shrink are that family's, unchanged.
- Every bend lies in one plane and turns left or right in it; no bend is rolled out of another's plane.
- The pipe between any two consecutive marks, less the pipe each arc consumes at the size's NEC Chapter 9, Table 2 radius, must be at least zero; the two end pieces are checked the same way. One check, over every segment of the stick. An end 90 consumes the take-up less half an OD, minus the radius of straight, past its arrow and then the quarter arc, and the kick calculator checks the same pipe past its own 90, by the same rule.
- "From" is a distance between pencil marks on the straight pipe, uncorrected. The manuals say to add the shrink to a distance measured to an obstruction before marking it; do that before it goes in.
- A 90° stub or a kick with 90 sits only at an end and is measured from that end by its own frame (the 90 mark at stub height minus the take-up); every other family's marks are measured from the previous bend's last mark, with the family's own first mark at that point plus the "from" distance.
- Cut length is the pipe between consecutive marks, summed end to end; shrink is printed beside it, never folded in.
- Not composed: an obstruction to clear, a roll between bends, a rack of sticks. Each is its own problem with its own calculator or none.
The picture and the mark table come from one skeleton, built in developed stations: every corner is placed so the point where its mark lands on the bent pipe sits at that mark's station, so the finished centerline measures the cut length and every band sits on its own bend. The calculator prints both lengths.
Read as an arrow mark, the pipe beyond a 90's mark is the stub height minus the take-up; read as a star mark, it is the stub height minus the field gain; so the same pencil line laid out the other way moves the cut length by the take-up minus the gain: 2.58 inches in 1/2" EMT, 3.15 inches in 3/4" EMT, 4.37 inches in 1" EMT and 6.38 inches in 1-1/4" EMT. A stick of two stubs lays both out by the arrow from their own ends; a U measured back to back with the tape between the two outsides is the back-to-back calculator, which lays the second 90 out on the star.
The Worked Stick, in Every Size
A 12" stub at end A, a 4" offset at 30° whose first mark is 24" past the 90 mark, a 3" saddle at 45° 30" past the offset's second mark, and a 12" stub at end B whose 90 mark is 30" past the saddle's last mark. Every row is run through the calculator; only the stubs' marks move with the size, by the take-up, so the offset and saddle marks shift with them.
| EMT Size | Take-Up | Marks from End A | Cut Length | Drawn Centerline |
|---|---|---|---|---|
| 1/2" | 5" | 7, 31, 39, 69, 76.5, 84, 114" | 121" | 121" |
| 3/4" | 6" | 6, 30, 38, 68, 75.5, 83, 113" | 119" | 119" |
| 1" | 8" | 4, 28, 36, 66, 73.5, 81, 111" | 115" | 115" |
| 1-1/4" | 11" † | 1, 25, 33, 63, 70.5, 78, 108" | 109" | 109" |
† Both take-up tables we hold, Klein and Gardner Bender's, stop at 1", so the 1-1/4" take-up is a field value no manufacturer document we hold confirms. Check it against your own bender before you cut.
Worked Example: the Default Stick in 1/2" EMT
Given: one stick has to stand up 12" out of a box, run, jog over 4" at 30°, saddle a 3" pipe at 45°, and stand up 12" into a second box.
Step 1: The stub at end A. Its own rule: 12 minus the 5" take-up puts the 90 mark at 7" from end A.
Step 2: The offset. Its first mark 24" past that, at 31"; its second mark its own travel farther, at 39".
Step 3: The saddle. Its first outer mark 30" past the offset's second, at 69"; the center and second outer at its own spacing, 76.5" and 84".
Step 4: The stub at end B. Its 90 mark 30" past the saddle's last mark, at 114" from end A, which is 7" from end B by its own rule.
Result: 7 marks, 121" of conduit to cut, 1.56" of shrink across the offset and the saddle, and a drawn centerline of 121", the same length.
Frequently Asked Questions
How does the stick builder lay out many bends on one conduit?
You list the bends in order from one end of the stick (end A): a 90 stub or a kick with 90 at either end, and offsets, 3-point saddles, 4-point saddles and segmented 90s in between, each with its own inputs. Every mark is that bend family's own result: an offset's two marks its travel apart, a saddle's three at its spacing, a segmented 90's at its shot spacing, a stub's at its stub height minus the take-up. The stick only places them: each bend sits "from" inches past the previous bend's last mark, or past end A when it is the first bend, measured between pencil marks on the straight pipe. A distance you measured to an obstruction or to the back of a bend is not that: the bender manuals say to add the family's shrink to it first, and so does this page. For the worked stick in 1/2 inch EMT (a 12 inch stub, a 4 inch offset at 30 degrees 24 inches on, a 3 inch saddle at 45 degrees 30 inches on, a 12 inch stub 30 inches on) the marks fall at 7, 31, 39, 69, 76.5, 84, 114 inches from end A and the cut length is 121 inches.
Which end are the marks measured from?
Every station in the table is from end A, the end you listed the bends from, and the table also prints each mark from end B and from the previous mark. A 90 stub or a kick at end A is laid out from end A by its own family's rule (the 90 mark at stub height minus the 5 inch take-up in 1/2 inch EMT); a stub or kick at end B is laid out from END B the same way, so on the pipe you hook the tape on end B for those marks. The "measured by its family from" column says which. That is why a stub or kick can only be the first or the last bend: its marks are measured from a pipe end, and there is no pipe end in the middle of a stick.
How is the cut length figured?
It is the pipe between consecutive marks, summed from end A to end B: a stub's piece is its stub height minus the take-up (the family's own rule), each later bend adds the distance to its first mark and its own mark spacings, and the tail past the last mark (or the last stub's piece) closes it. For the worked stick in 1/2 inch EMT that is 7 + 24 + 8 + 30 + 7.5 + 7.5 + 30 + 7 = 121 inches. Shrink is not folded in: the offsets' and saddles' shrink is printed beside the cut length, the way each family prints its own. A stick of two stubs is not the back-to-back calculator: that tool lays the second 90 out by the star point from the first stub's end and its cut length carries the field gain, so the same two marks give a cut length take-up minus gain apart per 90 across the two tools (2.58 inches in 1/2 inch EMT). Both are the manuals' own methods; use the back-to-back page for a U you measure back to back.
Is the drawn centerline the pipe I cut?
Yes. The picture is built in developed stations: every corner is placed so that the point where its mark lands on the bent pipe sits at that mark's station, and an end 90 is drawn at its full stub height with its arrow the take-up from the tip, the family's own rule. So the finished centerline measures the cut length (121 against 121 inches for the worked stick in 1/2 inch EMT, within the arc sampling), every yellow band sits on its own bend, and the drawn legs are the pipe's legs. The calculator prints both lengths, and every build checks them equal over a grid of sticks in every size.
What happens when two bends are too close?
One check over the whole stick: the pipe between any two consecutive marks, less the pipe each arc consumes at the size's NEC Chapter 9, Table 2 radius, must be at least zero, and the two end pieces are checked too. Past its arrow an end 90 consumes the take-up less half an OD, minus the radius of straight, and then the quarter arc, and the kick calculator checks the same pipe past its own 90 (both read one rule since item 13, so a kick the kick calculator answers answers in a stick at the same inputs). A refusal names the bend and the segment and the smallest change that works, re-run through every segment of the stick, or the pair where two segments are short. A 4 inch offset at 30 degrees whose first mark is 2 inches past a 12 inch stub's 90 mark in 1/2 inch EMT is refused: the 90 consumes 6.93 inches of pipe past its arrow and the 30 degree arc 1.07 more, and the smallest distance that works is 8-1/16". The stick also measures how close any two legs that share no bend come on the finished pipe, wall to wall, and refuses a stick that would pass through itself.
Where does this method come from?
The single-bend marks come from the bender manuals this site holds: the stub mark by the deduct each of them tells you to apply (the take-up values are Klein and Gardner Bender's; Greenlee publishes no table and tells you to read the deduct off your bender casting), and the offset and saddle multipliers from their charts. The developed length of a segmented 90 is geometry, stated on its own page, because none of these documents prints a segmented-bend table. None of them prints a chain formula across different families: Greenlee's Example 3 lays one 3-bend saddle out cumulatively from the conduit end with the shrink added, and the star-point back-to-back has its own calculator here. So the way this page puts single-bend marks together is stated as the site's own rule, in the words above, and the tool never invents a mark: it places each family's own.
What does the stick builder not do?
It does not go around an obstruction (the compound 90 calculator does that for one corner, and clearing an obstruction with a whole stick is a different problem), it does not roll one bend out of another's plane (every bend here lies in one plane and turns left or right; the marks and the cut length of a rolled stick are the same, but this tool's self-clearance check is in one plane, so it may refuse a rolled stick that clears in the field), and it does not lay out a rack of parallel sticks (the parallel offset calculator does that). It composes up to 12 bends.
More Bending References
Conduit Bending Calculator
Every bend type as an interactive 3D rendering or flat diagram, with verified bender profiles.
Back-to-Back 90s
Two 90s on one stick by the manufacturer star-point method, which is the one chain the manuals print.
Segmented 90 Calculator
A large-radius 90 bent in shots: developed length, mark spacing and the radius the sweep actually draws.
Compound 90 Calculator
Two bends around an obstruction in the corner, with the clearance the drawn bend actually gives.
90° Deduction Chart
Take-up, deduct, radius, and gain for 1/2" through 1-1/4" EMT.
Conduit Fill Calculator
Check NEC Chapter 9 fill compliance for any conduit and conductor combination.
New: run this inside your AI assistant
Prefer to just ask? Add this to Claude, free.
Connect Intry to Claude once, then just say “use Intry to…” to run the stick builder from a plain-English question, on your phone, on the job. You get the number (computed live, not guessed), what it means, and the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius. Works on every Claude plan.