Bending Calculator
Compound 90 Calculator
Two bends that add up to 90, placed so the conduit cuts across the corner and clears the beam, duct or pipe sitting in it by the clearance you enter. Every result is measured on the drawn bend at the radius for the size.
The Frame, Stated by Geometry
The conduit runs along one surface, turns 90 and runs along the second. The obstruction sits in the inside corner against both surfaces, so a one-shot 90, whose arc hugs that corner, runs into it. A compound 90 leaves the first surface early, crosses the corner on a diagonal that passes the obstruction's outer corner, and joins the second surface late. The calculator measures the obstruction along the two legs from the surfaces, places the diagonal so the pipe wall clears the nearest point of the obstruction by your clearance, and reports where each bend sits back from the corner where the two legs' centerlines would meet. The marks are the bends.
- The obstruction: a rectangle (width along the first leg, height along the second), a square, or a round obstruction tucked into the corner. The first surface is the one the conduit arrives on and the second the one it leaves on; the obstruction touches both, and the conduit lies against both too, half an OD off each on its centerline.
- The clearance: from the outside of the pipe to the nearest point of the obstruction, along the chord. Enter 0 to put the pipe wall exactly on it.
- The split: 45 then 45 cuts the corner evenly; 30 then 60 hugs the first surface longer and leaves the second sooner; 60 then 30 the reverse. Both bends are checked against the NEC Chapter 9, Table 2 radius for the size.
- What is measured, not assumed: the clearance the finished bend draws with each arc at that radius (never less than the clearance entered), and what a one-shot 90 in the same size would clear the obstruction by.
Square Obstructions, 1/2" Clearance, Two 45s, by Size
Each cell is run through the calculator: how far back from the corner each 45 sits (the same on both legs for a square at 45 and 45), the distance between the two marks, and whether a one-shot 90 in that size would clear the obstruction on its own. A refused cell prints the calculator's own sentence.
| Square | 1/2" EMT | 3/4" EMT | 1" EMT | 1-1/4" EMT |
|---|---|---|---|---|
| 1" × 1" | 2.5" back, 3.54" apart; a one-shot 90 clears by 0.39" | not bendable in 3/4" EMT, 1" EMT, 1-1/4" EMT (smallest clearance that works: 11/16" in 3/4"; 1-1/4" in 1"; 1-15/16" in 1-1/4") | not bendable in 3/4" EMT, 1" EMT, 1-1/4" EMT (smallest clearance that works: 11/16" in 3/4"; 1-1/4" in 1"; 1-15/16" in 1-1/4") | not bendable in 3/4" EMT, 1" EMT, 1-1/4" EMT (smallest clearance that works: 11/16" in 3/4"; 1-1/4" in 1"; 1-15/16" in 1-1/4") |
| 2" × 2" | 4.5" back, 6.36" apart; a one-shot 90 hits it by 0.82" | 4.44" back, 6.27" apart; a one-shot 90 hits it by 0.68" | 4.37" back, 6.18" apart; a one-shot 90 hits it by 0.2" | 4.26" back, 6.03" apart; a one-shot 90 clears by 0.49" |
| 4" × 4" | 8.5" back, 12.02" apart; a one-shot 90 hits it by 1.87" | 8.44" back, 11.93" apart; a one-shot 90 hits it by 2.24" | 8.37" back, 11.83" apart; a one-shot 90 hits it by 2.31" | 8.26" back, 11.69" apart; a one-shot 90 hits it by 1.87" |
| 6" × 6" | 12.5" back, 17.68" apart; a one-shot 90 hits it by 1.87" | 12.44" back, 17.59" apart; a one-shot 90 hits it by 2.24" | 12.37" back, 17.49" apart; a one-shot 90 hits it by 2.84" | 12.26" back, 17.35" apart; a one-shot 90 hits it by 3.63" |
| 12" × 12" | 24.5" back, 34.65" apart; a one-shot 90 hits it by 1.87" | 24.44" back, 34.56" apart; a one-shot 90 hits it by 2.24" | 24.37" back, 34.46" apart; a one-shot 90 hits it by 2.84" | 24.26" back, 34.32" apart; a one-shot 90 hits it by 3.63" |
The Same Beam, Three Splits, 1/2" EMT
A 4" × 4" beam with 1/2" clearance, three ways. Every row is run; the last column is the clearance the drawn bend gives, with each arc at the 4" radius.
| Split | First Bend Back From Corner | Second Bend Along Second Leg | Between Marks | Clearance Drawn |
|---|---|---|---|---|
| 30° then 60° | 11.67" | 6.74" | 13.48" | 0.5" |
| 45° then 45° | 8.5" | 8.5" | 12.02" | 0.5" |
| 60° then 30° | 6.74" | 11.67" | 13.48" | 0.5" |
Worked Example: 4" × 4" Beam, 1/2" Clearance, Two 45s, 3/4" EMT
Given: a 3/4" EMT run along the ceiling has to come down the wall, and a 4" × 4" beam fills the corner. You want 1/2" between the pipe and the beam.
Step 1: The chord. The diagonal between the two bends is placed so the pipe wall passes the beam's outer corner by 1/2": on the centerline that is 1/2" plus half the 0.922" OD.
Step 2: The bends. First bend 8.44" back from the corner along the ceiling; second bend 8.44" down the wall from that same corner; the marks are 11.93" apart.
Step 3: Check the drawn bend. With each 45 an arc at the 4.5" radius, the pipe wall clears the beam by 0.5". A one-shot 90 in 3/4" EMT would hit it, by up to 2.24" at the deepest point.
Result: mark the first 45 at 8.44" from where the ceiling and wall centerlines would meet, the second 45 11.93" past it, and bend both.
Frequently Asked Questions
What is a compound 90?
A 90 degree turn made in two bends instead of one, so the conduit cuts across the corner on a diagonal and misses something sitting in it: a beam where the ceiling meets the wall, a duct in the corner, a pipe along the floor-wall junction. The two bends add up to 90, most often 45 and 45; 30 then 60 or 60 then 30 skew the diagonal when the obstruction is much wider than it is tall or the other way around.
Where do the two bends go?
The calculator measures both from the corner where the two legs' centerlines would meet. It places the chord between the bends so the pipe wall clears the nearest point of the obstruction by the clearance you enter, then reports how far back along the first leg the first bend sits and how far along the second leg the second one does. For a 4 inch by 4 inch beam with 1/2 inch clearance in 3/4 inch EMT at 45 and 45, the first bend is 8.44 inches back from that corner, the second 8.44 inches along the wall, and the marks are 11.93 inches apart.
How is the obstruction measured?
It sits in the inside corner against both surfaces the conduit runs on: the first surface is the one the conduit arrives on, the second the one it leaves on. A rectangle is its size along the first leg (how far it sticks out from the second surface) by its size along the second leg (how far it sticks out from the first surface); a square has one side; a round obstruction is tucked into the corner touching both surfaces. The conduit lies against both surfaces too, half an OD off each on its centerline, which is what puts the obstruction in a one-shot 90's path.
Is the clearance measured to the centerline or the pipe wall?
To the pipe wall, from the nearest point of the obstruction along the chord. The calculator lays the bends out so the chord's centerline clears by the clearance plus half the OD, then measures the finished bend, with each bend an arc at the NEC Chapter 9, Table 2 radius for the size, and prints the clearance it actually draws. That figure is never less than the clearance entered; where the arcs pull the pipe farther from the obstruction it is more.
Why does it refuse a small obstruction, and what does the one-shot figure mean?
The chord between the two bends must keep straight conduit between their arcs, and each arc takes up conduit on both sides of its mark at the shoe's radius (4 inches for 1/2 inch EMT). A small obstruction with little clearance puts the two bends so close that the arcs overlap, and the calculator refuses, naming the smallest clearance that works at that split and any other split that answers. It also prints what a one-shot 90 in that size would clear the obstruction by: when that figure is positive, the plain 90 already misses it and no compound bend is needed for clearance.
Where does this method come from?
From geometry, stated on this page. None of the bender manuals this site holds (Greenlee, Gardner Bender, Klein) describes a compound 90, so there is no table to cite and no rounding to inherit: the chord is placed by the clearance, the bends are placed by the chord, and the finished bend is measured with each arc at the NEC Chapter 9 Table 2 radius.
More Bending References
Conduit Bending Calculator
Every bend type as an interactive 3D rendering or flat diagram, with verified bender profiles.
Segmented 90 Calculator
A 90 bent as equal shallow shots to a large radius: developed length, mark spacing and shot angle.
Saddle Bend Calculator
Over an obstruction in the run rather than around one in the corner: 3-point and 4-point saddle marks.
Kick 90 Calculator
Kick marks, travel, and shrink per inch of kick by angle.
90° Deduction Chart
Take-up, deduct, radius, and gain for 1/2" through 1-1/4" EMT.
Conduit Fill Calculator
Check NEC Chapter 9 fill compliance for any conduit and conductor combination.
New: run this inside your AI assistant
Prefer to just ask? Add this to Claude, free.
Connect Intry to Claude once, then just say “use Intry to…” to run the compound 90 calculator from a plain-English question, on your phone, on the job. You get the number (computed live, not guessed), what it means, and the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius. Works on every Claude plan.