Bending Reference

EMT 90-Degree Deduction Chart

Take-up, deduct, radius, and gain for 1/2", 3/4", 1", and 1-1/4" EMT hand benders, plus a pre-computed stub-up mark table for common stub heights.

Quick answer: The 90-degree deduct (take-up) is 5" for 1/2" EMT, 6" for 3/4" EMT, 8" for 1" EMT, and 11" for 1-1/4" EMT (unconfirmed). Subtract the deduct from your stub height to find the bend mark: a 12" stub in 1/2" EMT gets its mark at 12 − 5 = 7" from the end.

Take-Up, Deduct, Radius, and Gain by EMT Size

The 1/2", 3/4" and 1" take-ups are Klein and Gardner Bender's, published in the Klein Tools Conduit Bender and Angle Setter Guide (MKT200815 Rev. 09/20 A). The radii are NEC Chapter 9, Table 2 one-shot values, which is a different source, so the two columns are cited separately rather than to one make. Deduct equals take-up on standard shoes: subtract it from the stub height to find the mark. Gain is the material saved per 90 and is used for developed length and back-to-back 90 layouts.

Standard EMT hand bender constants by conduit size

Swipe the table sideways to see the rest of its columns. →

EMT SizeTake-Up / DeductBend RadiusGain per 90°
1/2" EMT5"4"2.42"
3/4" EMT6"4.5"2.85"
1" EMT8"5.75"3.63"
1-1/4" EMT11" †7.25"4.62"

† Both take-up tables we hold, Klein and Gardner Bender's, stop at 1", so the 1-1/4" take-up is a field value no manufacturer document we hold confirms. Check it against your own bender before you cut.

Compact benders and worn shoes can differ slightly. Gain in particular varies by bender design and published charts do not all agree, so verify gain against your own bender's chart or a test bend before cutting. Verify with a test bend on scrap before committing a full stick.

Stub-Up Mark Positions by Stub Height

Mark position = stub height − deduct, measured from the end of the conduit. The table below applies the deducts from the chart above to common stub heights.

Bend mark distance from conduit end, by stub height and EMT size

Swipe the table sideways to see the rest of its columns. →

Stub Height1/2" EMT3/4" EMT1" EMT1-1/4" EMT
12"7"6"4"1"
16"11"10"8"5"
18"13"12"10"7"
24"19"18"16"13"
30"25"24"22"19"
36"31"30"28"25"

Calculate Any Stub-Up

Enter your stub height and conduit size for the exact mark, deduct, gain, and developed length with an SVG diagram. Switch tabs for back-to-back 90s, offsets, saddles, and kicks.

Bend type: 15 families, pick one

Offsets
Saddles
90s and kicks
Racks of conduit
Large radius and corners
The whole stick

Common bends

Klein and Gardner Bender EMT hand bender take-up, with NEC Chapter 9, Table 2 radii by trade size. Greenlee's SITE-RITE hand-bender manual rates the same benders for 1/2" through 1-1/4" EMT and 1/2" through 1" rigid and IMC, and its older IM 1071 manual says 1/2" through 1" rigid: pick the type above (1-1/4" is not carried in IMC or RMC: no held bender document bends it by hand).

Deducts are not standard across makes. Greenlee's own manuals publish no table and tell you to read the deduct off the bender casting.

90° stub: 12" stub height12"7" mark from the endTake-up: 5"
Bend mark (arrow)7"
Take-Up5″
Deduct Amount5″
Gain2.42″
Stub leg after the 90's gain (the stub measured to its outside corner, less the gain; not a pipe length)
9.58"
Show the math
  1. MATHMark = Stub Height − Take-up = 12 − 5 = 7"
  2. MATHStub leg after the 90's gain = Stub − Gain = 12 − 2.42 = 9.58" (the stub measured to its outside corner, less the field gain: the pipe beyond the STAR mark; the pipe beyond the ARROW mark is Stub − Take-up = 7", and the two differ by take-up minus gain, 2.58" in 1/2" EMT)
Where this number comes fromIntry Verified
Calculated from
1/2" EMT bender, Klein and Gardner Bender take-up 5". Marks and shrink from the bender-chart constants where a manufacturer prints the angle (offset multiplier, 3-point saddle multiplier and shrink per inch) and from bend geometry elsewhere (offset 1/sin, saddle depth/sin(half-angle), kick travel); take-up from the EMT bender profile for your conduit size, or the deduct you entered (the only take-up carried for IMC and RMC), and gain from that conduit's own radius and outside diameter. See the full receipt ↓
Run with
  • Bend90° Stub
  • Conduit1/2" EMT
  • Setup12" stub, 90°
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius. This is our own deterministic gate, not a third-party audit.
Final say
Field-verify against the actual bend. Bender take-up varies by tool and shoe.
What Intry Verified means

Intry Verified · Build 525536D · 2026-11-13

Next on this job

This run travels with its receipt: 1/2" EMT, 90° Stub, 1 mark, stub leg after the 90's gain 9.58".

  • Conduit fillCarries 1/2" EMT into the fill calculator; add the conductors you are pulling.
  • Wire sizeCarries the receipt only: a bend run knows no load, so enter the amps, voltage and one-way distance there.
  • Box fillCarries the receipt only: a bend run knows no box, so enter the box and its conductors there.

One question

Did this help you on the job?

Bend mark (arrow): 7"9.58" total

Intry Verified. The take-up, deduct, and radius on this page are the locked per-size EMT bender constants, re-checked on every build; the gain and stub-up marks are computed by the locked bending engine from those constants (gain from the radius and outside diameter, stub-up from the take-up). Those figures are computed by a locked engine straight from the source it cites, not hand-typed, and that computation re-runs inside a deterministic test on every deploy. Source-checked. Locked. This is our own deterministic gate, not a third-party audit. What Intry Verified means


Worked Example: 18-Inch Stub in 3/4" EMT

Given: A panel knockout sits 18 inches above the deck and you are running 3/4" EMT (deduct = 6", gain = 2.85").

Step 1: Mark position. Mark = 18 − 6 = 12 inches from the end of the conduit.

Step 2: Bend. Align the mark with the bender arrow, apply steady foot pressure, and pull to 90 degrees. Check plumb with the level vial or a torpedo level.

Step 3: Account for gain. The bend cuts the corner, so the conduit path is shorter than the two legs measured to the outside corner. An 18" stub plus a 60" horizontal run measured to the outside corner needs 18 + 60 − 2.85 = 75.15" of conduit.

Result: One mark at 12", one pull to 90, and the stub lands at 18" on the nose.


Worked Exam Problem: First Mark From a Given Deduct

Problem. A 24" stub-up goes on a bender whose deduct is 8". Where does the first mark go?

Step 1: the rule. The first mark for any stub-up is the stub height minus the deduct, measured from the end of the conduit.

Step 2: put in the numbers. 24 − 8 = 16 inches from the end.

Answer: mark the conduit at 16", line it up with the arrow, and bend to 90 degrees. The end lands 24" above the bend.

Notice the answer used the deduct the problem handed you, not a value we looked up. That is deliberate: the first-mark rule is the same for every conduit and every bender, so the method works whether the shoe's deduct is 5", 6", or 8". Use your own bender's stamped deduct and the arithmetic never changes.

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

What is the 90 degree deduction for 1/2" EMT?

The deduct for 1/2 inch EMT on a standard hand bender is 5 inches. Measure your stub height, subtract 5 inches, and place your mark at that distance from the end of the conduit. For a 12-inch stub, the mark goes at 12 - 5 = 7 inches. Align the mark with the arrow on the bender shoe and bend to 90 degrees.

What is the take-up for 3/4" EMT?

The take-up for 3/4" EMT is 6 inches. Take-up is the distance from the bend mark (at the bender arrow) to the back of the finished 90 degree bend. The Klein Tools Conduit Bender and Angle Setter Guide (MKT200815 Rev. 09/20 A) publishes 5 inches for 1/2" EMT, 6 inches for 3/4" EMT, 8 inches for 1" EMT, and that is where those come from. That table stops at 1 inch, so the take-up for 1-1/4" EMT is a field value no manufacturer document we hold confirms. Read the deduct stamped on your own bender: Greenlee's own manuals tell you to do exactly that, and publish no table at all.

Are deduct and take-up the same thing?

On standard EMT hand benders, yes: the deduct you subtract from the stub height equals the take-up of the shoe. The two terms describe the same constant from different directions. Take-up describes what the shoe consumes to form the bend; deduct describes what you subtract from your measurement to find the mark. Some manufacturers print one term, some the other.

What is gain on a 90 degree bend?

Gain is the conduit you save by bending a 90 instead of joining two straight pieces at a right angle. Because the bend cuts the corner, the conduit path is shorter than the two legs measured to the outside corner. Measured to the outside corner the way a tape reaches it, gain for standard EMT benders is 2.42 inches for 1/2 inch, 2.85 inches for 3/4 inch, 3.63 inches for 1 inch, and 4.62 inches for 1-1/4 inch. Use gain when figuring the total cut length of a run with 90s, including back-to-back 90s.

How do I bend a 12-inch stub-up in 1/2" EMT?

Subtract the 5-inch deduct from the 12-inch stub height and mark the conduit 7 inches from the end. Slide the conduit into the bender with the mark at the arrow, keep foot pressure on the heel, and pull to 90 degrees using the level vial or a torpedo level on the vertical leg. The end of the conduit will sit 12 inches above the floor of the bend.

Where does the first mark go for a 24 inch stub-up on a bender whose deduct is 8 inches?

Mark the conduit 16 inches from the end. The first mark for any stub-up is the stub height minus the deduct: 24 - 8 = 16 inches. Notice this uses the deduct the problem gives you, so it holds for any conduit and any bender, EMT or RMC, whatever the shoe's deduct happens to be. Line the mark up with the arrow and bend to 90 degrees, and the end sits 24 inches above the bend.

Why is my bender's deduct different from this chart?

The 1/2", 3/4", 1" values here are Klein and Gardner Bender's, from the Klein Tools Conduit Bender and Angle Setter Guide (MKT200815 Rev. 09/20 A); the 1-1/4" value is an unconfirmed field value. Deducts are not standardised across makes: Greenlee publishes none at all in either manual we hold and instructs you to read the deduct off the bender casting instead. Compact shoes, aluminum vs. iron heads, and worn shoes can vary by a fraction of an inch, and site-made jigs vary more. Always verify with a test bend: bend a scrap piece to 90, measure from your mark to the back of the bend, and use that measured take-up for the rest of the job.

How many 90 degree bends are allowed between pull points?

Four. NEC 358.24(B) limits EMT to 360 degrees of total bends between pull points, and four 90 degree bends equal exactly 360 degrees. Every bend counts toward the total, including offsets and saddles, so a run with a single 30 degree offset (60 degrees) can only fit three 90s (270 degrees) before it needs a pull box or conduit body.


More Bending References