3-Point Saddle Bend

60° Center Saddle Bend

Everything for a 60 degree 3-point saddle: the center-to-outer multiplier, the shrink, a worked example, and the calculator, all from the same math your bender uses.

Quick answer: A 60° saddle bends the center 60° and the two outer marks 30°, spaced depth × 2.0 (the value printed in Klein's Zip Guide for Saddles (2" per inch of depth), and exact 1/sin(30°) is the same 2.00) from center, and shrinks 1/4″ per inch of depth. A 3″ saddle → marks 6″ from center, shrinks 0.75″. In 1-1/4" EMT a 3" saddle at a 60° center cannot be bent (the 30° outer arc and the 60° center arc on its 7.25" bend radius would overlap); the smallest saddle at a 60° center in that size is 3-1/8".

The 60° Saddle Numbers

Swipe the table sideways to see the rest of its columns. →

Center bend / outer bends60° / 30°
Center-to-outer multiplier (applied / exact 1/sin)2.0 / 2.00
Shrink per inch of depth1/4″ (0.2500″)
3″ saddle: center to each outer mark6″ (not bendable in 1-1/4" EMT)
3″ saddle: shrink to shift the center0.75″

Distance from center to each outer mark = saddle depth × 2.0, which is what the calculator applies (the value printed in Klein's Zip Guide for Saddles (2" per inch of depth), and exact 1/sin(30°) is the same 2.00). Shrink = depth × 1/4″. Center bend 60 degrees, both outer bends 30 degrees.

Bender saddle tables print 2.0 per inch of depth for a 60° center, which this calculator uses, and exact 1/sin(30°) is the same 2.00, so the marks at that spacing lay out the peak exactly at the depth you asked for, before the bend radius rounds the top. The calculator and its 3D show the centerline peak those marks reach once the center arc at the NEC Chapter 9, Table 2 radius is counted, which sits below the depth you enter on every saddle: 2.38″ for the 3″ example in 1/2″ EMT, so enter about 3.62″ there for a 3″ peak. The calculator prints the depth to enter for the peak you need.


Calculate Your 60° Saddle

The calculator opens in 3-point saddle mode on the worked example, 3″ entered at a 60° center (the peak that depth reaches is given above). Enter your own saddle depth for the exact mark spacing and shrink.

Bend type: 15 families, pick one

Offsets
Saddles
90s and kicks
Racks of conduit
Large radius and corners
The whole stick

Common bends

Klein and Gardner Bender EMT hand bender take-up, with NEC Chapter 9, Table 2 radii by trade size. Greenlee's SITE-RITE hand-bender manual rates the same benders for 1/2" through 1-1/4" EMT and 1/2" through 1" rigid and IMC, and its older IM 1071 manual says 1/2" through 1" rigid: pick the type above (1-1/4" is not carried in IMC or RMC: no held bender document bends it by hand).

3-point saddle: 2.38" peak at these marks, 60° center2.38" peakCenter (60°)Outer 1Outer 26"
Outer bend 10"
Center bend6"
Outer bend 212"
Center-to-Outer Spacing6″
Multiplier applied2x
Peak at these marks (centerline, at the NEC radius)2.38″
Depth to enter for the peak to reach the depth entered3.62″
Shrink0.75"
Developed Length
12"
Show the math
  1. MATHOuter angle = Center / 2 = 60 / 2 = 30°
  2. MATHCenter-to-outer spacing = Depth × saddle-table multiplier = 3 × 2 = 6"

Bender saddle tables print 2.0 per inch of depth for a 60° center, which this calculator uses, and exact 1/sin(30°) is the same 2.00, so the marks at that spacing lay out the peak exactly at the depth you asked for, before the bend radius rounds the top.

Where this number comes fromIntry Verified
Calculated from
Bender saddle-table multiplier (2.0), Klein's Zip Guide for Saddles (2" per inch of depth). Marks and shrink from the bender-chart constants where a manufacturer prints the angle (offset multiplier, 3-point saddle multiplier and shrink per inch) and from bend geometry elsewhere (offset 1/sin, saddle depth/sin(half-angle), kick travel); take-up from the EMT bender profile for your conduit size, or the deduct you entered (the only take-up carried for IMC and RMC), and gain from that conduit's own radius and outside diameter. See the full receipt ↓
Run with
  • Bend3-Point Saddle
  • Setup3" saddle, 60° center
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius. This is our own deterministic gate, not a third-party audit.
Final say
Field-verify against the actual bend. Bender take-up varies by tool and shoe.
What Intry Verified means

Intry Verified · Build 525536D · 2026-11-13

Next on this job

This run travels with its receipt: 1/2" EMT, 3-Point Saddle, 3 marks, developed length 12".

  • Conduit fillCarries 1/2" EMT into the fill calculator; add the conductors you are pulling.
  • Wire sizeCarries the receipt only: a bend run knows no load, so enter the amps, voltage and one-way distance there.
  • Box fillCarries the receipt only: a bend run knows no box, so enter the box and its conductors there.

One question

Did this help you on the job?

Outer bend 1: 0" (+2 more marks above)12" total

Frequently Asked Questions

What is the multiplier for a 60 degree saddle?

The center-to-outer multiplier for a 60 degree 3-point saddle is 2.0, which is what this calculator applies (the value printed in Klein's Zip Guide for Saddles (2" per inch of depth), and exact 1/sin(30°) is the same 2.00). The center bend is the full 60 degrees and the two outer bends are half that, 30 degrees. Multiply the saddle depth by the multiplier to get the distance from the center mark to each outer mark. For a 3 inch saddle that is 3 x 2.0 = 6 inches. In 1-1/4 inch EMT a 3 inch saddle at a 60 degree center cannot be bent (the 30 degree outer arc and the 60 degree center arc on its 7.25 inch bend radius would overlap); the smallest saddle at a 60 degree center in that size is 3-1/8 inches.

How much does a 60 degree saddle shrink?

A 60 degree saddle shrinks 1/4 inch for every inch of saddle depth. A 3 inch saddle shrinks about 0.75 inches, so shift the center mark toward the free end by that amount before bending so the saddle lands centered over the obstruction.

How do you bend a 60 degree 3-point saddle?

Find the center of the obstruction and mark it on the conduit, then shift that mark 0.75 inches (the shrink for a 3 inch saddle) toward the free end. Bend the center mark to the full 60 degrees. Measure 6 inches (for a 3 inch saddle) to each side of the center and mark the outer bends. Rotate the conduit 180 degrees and bend each outer mark to 30 degrees. The three bends lift the conduit up and back down over the obstruction. In 1-1/4 inch EMT a 3 inch saddle at a 60 degree center cannot be bent (the 30 degree outer arc and the 60 degree center arc on its 7.25 inch bend radius would overlap); the smallest saddle at a 60 degree center in that size is 3-1/8 inches.

When should I use a 60 degree saddle?

A 60 degree saddle is a tight, steep saddle. The outer bends are 30 degrees, so the marks sit close together (multiplier 2.0) and it clears the obstruction in a short length, but it shrinks more (1/4 inch per inch) and pulls harder. Use it for a tall obstruction in a short run.


Other Saddle Angles