3-Point Saddle Bend

22.5° Center Saddle Bend

Everything for a 22.5 degree 3-point saddle: the center-to-outer multiplier, the shrink, a worked example, and the calculator, all from the same math your bender uses.

Quick answer: A 22.5° saddle bends the center 22.5° and the two outer marks 11.25°, spaced depth × 5.1258 (the exact 1/sin of the 11.25° outer angle; no bender saddle table we hold prints a 22.5° center row) from center, and shrinks 0.0985″ per inch of depth. A 3″ saddle → marks 15.38″ from center, shrinks 0.3″.

The 22.5° Saddle Numbers

Swipe the table sideways to see the rest of its columns. →

Center bend / outer bends22.5° / 11.25°
Center-to-outer multiplier (applied / exact 1/sin)5.1258 / 5.13
Shrink per inch of depth0.0985″
3″ saddle: center to each outer mark15.38″
3″ saddle: shrink to shift the center0.3″

Distance from center to each outer mark = saddle depth × 5.1258, which is what the calculator applies (the exact 1/sin of the 11.25° outer angle; no bender saddle table we hold prints a 22.5° center row). Shrink = depth × 0.0985″. Center bend 22.5 degrees, both outer bends 11.25 degrees.

The calculator and its 3D show the centerline peak those marks reach once the center arc at the NEC Chapter 9, Table 2 radius is counted, which sits below the depth you enter on every saddle: 2.92″ for the 3″ example in 1/2″ EMT, so enter about 3.08″ there for a 3″ peak. The calculator prints the depth to enter for the peak you need.

The standard shrink chart lists constants at 10°, 22.5°, 30°, 45° and 60°, and publishes none for the 11.25° outer bends this saddle uses. Rather than round to a nearby fraction, the 0.0985″ above is computed from the bend geometry (tan of half the outer angle), which is exactly what the calculator below uses. On a saddle this shallow the shrink is small enough that most techs ignore it.


Calculate Your 22.5° Saddle

The calculator opens in 3-point saddle mode on the worked example, 3″ entered at a 22.5° center (the peak that depth reaches is given above). Enter your own saddle depth for the exact mark spacing and shrink.

Bend type: 15 families, pick one

Offsets
Saddles
90s and kicks
Racks of conduit
Large radius and corners
The whole stick

Common bends

Klein and Gardner Bender EMT hand bender take-up, with NEC Chapter 9, Table 2 radii by trade size. Greenlee's SITE-RITE hand-bender manual rates the same benders for 1/2" through 1-1/4" EMT and 1/2" through 1" rigid and IMC, and its older IM 1071 manual says 1/2" through 1" rigid: pick the type above (1-1/4" is not carried in IMC or RMC: no held bender document bends it by hand).

3-point saddle: 2.92" peak at these marks, 22.5° center2.92" peakCenter (22.5°)Outer 1Outer 215.38"
Outer bend 10"
Center bend15.38"
Outer bend 230.75"
Center-to-Outer Spacing15.38″
Multiplier applied5.13x
Peak at these marks (centerline, at the NEC radius)2.92″
Depth to enter for the peak to reach the depth entered3.08″
Shrink0.3"
Developed Length
30.75"
Show the math
  1. MATHOuter angle = Center / 2 = 22.5 / 2 = 11.25°
  2. MATHCenter-to-outer spacing = Depth / sin(Outer) = 3 / sin(11.25°) = 15.38"
Where this number comes fromIntry Verified
Calculated from
Saddle multiplier geometry (1/sin of the outer angle). Marks and shrink from the bender-chart constants where a manufacturer prints the angle (offset multiplier, 3-point saddle multiplier and shrink per inch) and from bend geometry elsewhere (offset 1/sin, saddle depth/sin(half-angle), kick travel); take-up from the EMT bender profile for your conduit size, or the deduct you entered (the only take-up carried for IMC and RMC), and gain from that conduit's own radius and outside diameter. See the full receipt ↓
Run with
  • Bend3-Point Saddle
  • Setup3" saddle, 22.5° center
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius. This is our own deterministic gate, not a third-party audit.
Final say
Field-verify against the actual bend. Bender take-up varies by tool and shoe.
What Intry Verified means

Intry Verified · Build 525536D · 2026-11-13

Next on this job

This run travels with its receipt: 1/2" EMT, 3-Point Saddle, 3 marks, developed length 30.75".

  • Conduit fillCarries 1/2" EMT into the fill calculator; add the conductors you are pulling.
  • Wire sizeCarries the receipt only: a bend run knows no load, so enter the amps, voltage and one-way distance there.
  • Box fillCarries the receipt only: a bend run knows no box, so enter the box and its conductors there.

One question

Did this help you on the job?

Outer bend 1: 0" (+2 more marks above)30.75" total

Frequently Asked Questions

What is the multiplier for a 22.5 degree saddle?

The center-to-outer multiplier for a 22.5 degree 3-point saddle is 5.1258, which is what this calculator applies (the exact 1/sin of the 11.25° outer angle; no bender saddle table we hold prints a 22.5° center row). The center bend is the full 22.5 degrees and the two outer bends are half that, 11.25 degrees. Multiply the saddle depth by the multiplier to get the distance from the center mark to each outer mark. For a 3 inch saddle that is 3 x 5.1258 = 15.38 inches.

How much does a 22.5 degree saddle shrink?

A 22.5 degree saddle shrinks 0.0985 inch for every inch of saddle depth. A 3 inch saddle shrinks about 0.3 inches, so shift the center mark toward the free end by that amount before bending so the saddle lands centered over the obstruction.

How do you bend a 22.5 degree 3-point saddle?

Find the center of the obstruction and mark it on the conduit, then shift that mark 0.3 inches (the shrink for a 3 inch saddle) toward the free end. Bend the center mark to the full 22.5 degrees. Measure 15.38 inches (for a 3 inch saddle) to each side of the center and mark the outer bends. Rotate the conduit 180 degrees and bend each outer mark to 11.25 degrees. The three bends lift the conduit up and back down over the obstruction.

When should I use a 22.5 degree saddle?

A 22.5 degree saddle is a long, gentle saddle. It shrinks very little (0.0985 inch per inch) and pulls wire easily, but the outer marks sit far apart (multiplier 5.1258), so it needs room. Use it for a shallow obstruction where you have length to work with.


Other Saddle Angles