3-Point Saddle Bend
45° Center Saddle Bend
Everything for a 45 degree 3-point saddle: the center-to-outer multiplier, the shrink, a worked example, and the calculator, all from the same math your bender uses.
The 45° Saddle Numbers
Swipe the table sideways to see the rest of its columns. →
| Center bend / outer bends | 45° / 22.5° |
| Center-to-outer multiplier (applied / exact 1/sin) | 2.5 / 2.61 |
| Shrink per inch of depth | 3/16″ (0.1875″) |
| 3″ saddle: center to each outer mark | 7.5″ |
| 3″ saddle: shrink to shift the center | 0.56″ |
Distance from center to each outer mark = saddle depth × 2.5, which is what the calculator applies (the value printed in the Greenlee IM 1071, Greenlee SITE-RITE, Gardner Bender 960-Series and Klein Zip Guide saddle tables (2-1/2" per inch of depth); exact 1/sin(22.5°) is 2.61). Shrink = depth × 3/16″. Center bend 45 degrees, both outer bends 22.5 degrees.
Bender saddle tables print 2.5 per inch of depth for a 45° center, which this calculator uses. Exact 1/sin(22.5°) is 2.61, 4.5% above it; the table is that value rounded for a tape measure, so the marks at that spacing lay out a peak 4.3% lower than the depth you asked for, before the bend radius rounds the top, which is the rounding the trade accepts. The calculator and its 3D show the centerline peak those marks reach once the center arc at the NEC Chapter 9, Table 2 radius is counted, which sits below the depth you enter on every saddle: 2.54″ for the 3″ example in 1/2″ EMT, so enter about 3.48″ there for a 3″ peak. The calculator prints the depth to enter for the peak you need.
Calculate Your 45° Saddle
The calculator opens in 3-point saddle mode on the worked example, 3″ entered at a 45° center (the peak that depth reaches is given above). Enter your own saddle depth for the exact mark spacing and shrink.
Bend type: 15 families, pick one
Common bends
Klein and Gardner Bender EMT hand bender take-up, with NEC Chapter 9, Table 2 radii by trade size. Greenlee's SITE-RITE hand-bender manual rates the same benders for 1/2" through 1-1/4" EMT and 1/2" through 1" rigid and IMC, and its older IM 1071 manual says 1/2" through 1" rigid: pick the type above (1-1/4" is not carried in IMC or RMC: no held bender document bends it by hand).
Show the math
- MATHOuter angle = Center / 2 = 45 / 2 = 22.5°
- MATHCenter-to-outer spacing = Depth × saddle-table multiplier = 3 × 2.5 = 7.5"
Bender saddle tables print 2.5 per inch of depth for a 45° center, which this calculator uses. Exact 1/sin(22.5°) is 2.61, 4.5% above it; the table is that value rounded for a tape measure, so the marks at that spacing lay out a peak 4.3% lower than the depth you asked for, before the bend radius rounds the top, which is the rounding the trade accepts.
Where this number comes fromIntry Verified
- Calculated from
- Bender saddle-table multiplier (2.5), the Greenlee IM 1071, Greenlee SITE-RITE, Gardner Bender 960-Series and Klein Zip Guide saddle tables (2-1/2" per inch of depth). Marks and shrink from the bender-chart constants where a manufacturer prints the angle (offset multiplier, 3-point saddle multiplier and shrink per inch) and from bend geometry elsewhere (offset 1/sin, saddle depth/sin(half-angle), kick travel); take-up from the EMT bender profile for your conduit size, or the deduct you entered (the only take-up carried for IMC and RMC), and gain from that conduit's own radius and outside diameter. See the full receipt ↓
- Run with
- Bend3-Point Saddle
- Setup3" saddle, 45° center
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius. This is our own deterministic gate, not a third-party audit.
- Final say
- Field-verify against the actual bend. Bender take-up varies by tool and shoe.
Intry Verified · Build 525536D · 2026-11-13
Next on this job
This run travels with its receipt: 1/2" EMT, 3-Point Saddle, 3 marks, developed length 15".
- Conduit fillCarries 1/2" EMT into the fill calculator; add the conductors you are pulling.
- Wire sizeCarries the receipt only: a bend run knows no load, so enter the amps, voltage and one-way distance there.
- Box fillCarries the receipt only: a bend run knows no box, so enter the box and its conductors there.
One question
Did this help you on the job?
Frequently Asked Questions
What is the multiplier for a 45 degree saddle?
The center-to-outer multiplier for a 45 degree 3-point saddle is 2.5, which is what this calculator applies (the value printed in the Greenlee IM 1071, Greenlee SITE-RITE, Gardner Bender 960-Series and Klein Zip Guide saddle tables (2-1/2" per inch of depth); exact 1/sin(22.5°) is 2.61). The center bend is the full 45 degrees and the two outer bends are half that, 22.5 degrees. Multiply the saddle depth by the multiplier to get the distance from the center mark to each outer mark. For a 3 inch saddle that is 3 x 2.5 = 7.5 inches.
How much does a 45 degree saddle shrink?
A 45 degree saddle shrinks 3/16 inch for every inch of saddle depth. A 3 inch saddle shrinks about 0.56 inches, so shift the center mark toward the free end by that amount before bending so the saddle lands centered over the obstruction.
How do you bend a 45 degree 3-point saddle?
Find the center of the obstruction and mark it on the conduit, then shift that mark 0.56 inches (the shrink for a 3 inch saddle) toward the free end. Bend the center mark to the full 45 degrees. Measure 7.5 inches (for a 3 inch saddle) to each side of the center and mark the outer bends. Rotate the conduit 180 degrees and bend each outer mark to 22.5 degrees. The three bends lift the conduit up and back down over the obstruction.
When should I use a 45 degree saddle?
The 45 degree saddle is the everyday choice and the one most electricians memorize (saddle-table multiplier 2.5). The center bends 45 degrees with 22.5 degree outer bends, balancing a close mark spacing against an easy wire pull. Use it for most pipes and small obstructions.
Other Saddle Angles
30° Center Saddle
Multiplier 3.8637, shrink 0.1317″ per inch, 15° outer bends.
60° Center Saddle
Multiplier 2.0, shrink 1/4″ per inch, 30° outer bends.
22.5° Center Saddle
Multiplier 5.1258, shrink 0.0985″ per inch, 11.25° outer bends.
Saddle Calculator + All Angles
3-point and 4-point saddle marks, multipliers, and shrink with the calculator.