Bending Calculator

Kick 90 Calculator

Calculate both marks for a kick 90: the 90-degree stub mark and the kick mark, with kick travel, shrink per inch of kick, and an interactive SVG diagram. For 1/2" through 1-1/4" EMT.

Quick answer: For a kick 90, the 90° mark = stub height − take-up, and the kick mark = 90° mark + (kick height × multiplier). Shrink per inch of kick is 1/16" at 10°, 3/16" at 22.5°, and 1/4" at 30°. Always bend the kick first, then the 90.

Bend type: 15 families, pick one

Offsets
Saddles
90s and kicks
Racks of conduit
Large radius and corners
The whole stick

Common bends

Klein and Gardner Bender EMT hand bender take-up, with NEC Chapter 9, Table 2 radii by trade size. Greenlee's SITE-RITE hand-bender manual rates the same benders for 1/2" through 1-1/4" EMT and 1/2" through 1" rigid and IMC, and its older IM 1071 manual says 1/2" through 1" rigid: pick the type above (1-1/4" is not carried in IMC or RMC: no held bender document bends it by hand).

Deducts are not standard across makes. Greenlee's own manuals publish no table and tell you to read the deduct off the bender casting.

Kick 90: 12" stub, kick mark 20.91" past the 90 mark along the run, 22.5° kick lifting the run 8"12" stub90° mark: 7" from stub end20.91" of pipe to kick mark8" kick22.5° kick
90° bend mark7"
Kick bend mark27.91"
Kick Height8″
Kick Travel20.91″
Shrink1.5"
Stub plus kick travel after the 90's gain (the stub measured to its outside corner, less the gain; not a pipe length)
30.49"
Show the math
  1. MATH90° mark = Stub − Take-up = 12 − 5 = 7" from the stub end
  2. MATHKick travel = Kick Height / sin(22.5°) = 8 / sin(22.5°) = 20.91"
  3. MATHKick mark = 90° mark + Kick travel = 7 + 20.91 = 27.91"
Where this number comes fromIntry Verified
Calculated from
1/2" EMT bender, Klein and Gardner Bender take-up 5". Marks and shrink from the bender-chart constants where a manufacturer prints the angle (offset multiplier, 3-point saddle multiplier and shrink per inch) and from bend geometry elsewhere (offset 1/sin, saddle depth/sin(half-angle), kick travel); take-up from the EMT bender profile for your conduit size, or the deduct you entered (the only take-up carried for IMC and RMC), and gain from that conduit's own radius and outside diameter. See the full receipt ↓
Run with
  • BendKick 90
  • Conduit1/2" EMT
  • Setup12" stub, 8" kick @ 22.5°
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius. This is our own deterministic gate, not a third-party audit.
Final say
Field-verify against the actual bend. Bender take-up varies by tool and shoe.
What Intry Verified means

Intry Verified · Build 525536D · 2026-11-13

Next on this job

This run travels with its receipt: 1/2" EMT, Kick 90, 2 marks, stub plus kick travel after the 90's gain 30.49".

  • Conduit fillCarries 1/2" EMT into the fill calculator; add the conductors you are pulling.
  • Wire sizeCarries the receipt only: a bend run knows no load, so enter the amps, voltage and one-way distance there.
  • Box fillCarries the receipt only: a bend run knows no box, so enter the box and its conductors there.

One question

Did this help you on the job?

90° bend mark: 7"30.49" total

Kick Multiplier and Shrink by Angle

A kick uses the same trigonometry as an offset, applied to a single bend. Kick travel (distance from the 90° mark to the kick mark) = kick height × multiplier, where the multiplier is the exact 1 / sin(kick angle): no bender manufacturer we hold prints a kick table, so the kick is worked from geometry, while the offset charts round the same factor to 6.0, 2.6 and 2.0 for offsets. Shrink = kick height × shrink per inch.

The kick is in the run, not in the stub. Both marks are measured from the stub end: the 90° mark at stub height minus take-up, and the kick mark one kick travel farther along. That puts the kick past the 90, so the stub stands its full height and the run is what kicks over. Both pictures draw the kick in the plane of the 90, lifting the run. Both are built in developed stations: the 90's corner sits the take-up less half an OD past its arrow (the stub is measured to the back of the 90) and the kick's corner at the kick mark, so the drawn pipe is the pipe the marks lay out, and a kick mark the finished 90 would consume is refused rather than drawn. That floor is this site's own model at the Table 2 radius, the two arcs just touching; a bender with a tighter shoe may lay a kick closer. The marks fix neither the plane nor the direction, so roll the pipe in the bender to put the kick toward the box.

Kick multiplier and shrink per inch of kick height, by kick angle

Swipe the table sideways to see the rest of its columns. →

Kick AngleMultiplierShrink per Inch of Kick
10°5.761/16"
15°3.86not published
22.5°2.613/16"
30°2.001/4"

Kick Travel by Kick Height and Angle

Pre-computed kick travel (kick height / sin(angle)) for common kick heights. Add this distance to your 90° mark to find the kick mark. Past its arrow the finished 90 consumes the take-up less half an OD, minus the radius of straight, and then the quarter arc at the size's NEC Chapter 9, Table 2 bend radius (6.93" in 1/2" EMT), so a short kick at a steeper angle puts the kick mark where the 90's curve is still finishing. Rows the engine refuses say so and name the smallest kick height that works.

Distance from the 90-degree mark to the kick mark, by kick height and kick angle, in the four EMT sizes (for IMC or RMC, run the calculator above with the deduct cast on your bender)

Swipe the table sideways to see the rest of its columns. →

Kick Height@ 10°@ 15°@ 22.5°@ 30°
1"not bendable in any EMT size this calculator carries (smallest kick height that works: 1-5/16" in 1/2", 2-5/8" in 1-1/4")not bendable in any EMT size this calculator carries (smallest kick height that works: 1-15/16" in 1/2", 4" in 1-1/4")not bendable in any EMT size this calculator carries (smallest kick height that works: 3" in 1/2", 6-1/16" in 1-1/4")not bendable in any EMT size this calculator carries (smallest kick height that works: 4-1/16" in 1/2", 8-3/16" in 1-1/4")
2"11.52"7.73"not bendable in any EMT size this calculator carries (smallest kick height that works: 3" in 1/2", 6-1/16" in 1-1/4")not bendable in any EMT size this calculator carries (smallest kick height that works: 4-1/16" in 1/2", 8-3/16" in 1-1/4")
3"17.28"11.59"7.84"not bendable in any EMT size this calculator carries (smallest kick height that works: 4-1/16" in 1/2", 8-3/16" in 1-1/4")
4"23.04"15.45"10.45"not bendable in any EMT size this calculator carries (smallest kick height that works: 4-1/16" in 1/2", 8-3/16" in 1-1/4")
6"34.55"23.18"15.68"12"
8"46.07"30.91"20.91"16"
12"69.11"46.36"31.36"24"

Worked Example: 12-Inch Stub with a 4-Inch Kick at 15 Degrees

Given: A 3/4" EMT run stubs up 12 inches out of a deck and needs a 4-inch kick to line up with a panel. You choose a 15-degree kick. The 3/4" bender take-up is 6 inches.

Step 1: The 90° mark. Mark = 12 − 6 = 6 inches from the end of the conduit.

Step 2: Kick travel. Travel = 4 / sin(15°) = 4 × 3.8637 = 15.45 inches.

Step 3: The kick mark. Kick mark = 6 + 15.45 = 21.45 inches from the same end of the conduit.

Step 4: Shrink. No bender manufacturer publishes a 15° shrink constant, so this one is derived from the bend geometry: shrink = 4 × 0.132 = about 0.53 inch. The kicked leg ends up about 0.53 inch short of where the unbent conduit would reach, so allow for it on the leg past the kick if the final position is critical.

Step 5: Bend in order. Bend the 15-degree kick first at the 21.45" mark, sight the plane, then flip the conduit and pull the 90 at the 6" mark.

Result: A 12-inch stub whose run, past the 90, sits 4 inches off its original line, dead on the panel knockout.

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

What is a kick in conduit bending?

A kick is a single small-angle bend that pushes the conduit off its original line. A kick 90 combines a standard 90 degree stub with a second, small-angle bend laid out kick travel past the 90 mark, so the run past the 90 angles over to line up with a box, panel, or rack that is not directly in line with the run.

How much shrink per inch of kick?

Shrink per inch of kick height depends on the kick angle: 1/16 inch at 10 degrees, 3/16 inch at 22.5 degrees, and 1/4 inch at 30 degrees. Multiply the kick height by the constant for your angle. An 8-inch kick at 22.5 degrees shrinks the run 8 x 3/16 = 1.5 inches. At the shallow angles of a kick, shrink per inch is small but still worth accounting for on precise layouts.

How do I calculate the marks for a kick 90?

Treat the two bends independently. The 90 degree mark = stub height minus the bender take-up (5 inches for 1/2 inch EMT, 6 inches for 3/4 inch). The kick mark = 90 degree mark + kick travel, where kick travel = kick height / sin(kick angle), both measured from the same end of the conduit. Example in 1/2 inch EMT: a 12-inch stub with an 8-inch kick at 22.5 degrees gives a 90 mark at 12 - 5 = 7 inches and a kick mark at 7 + 20.91 = 27.91 inches from the end. Past its arrow the finished 90 consumes 6.93 inches of pipe (the take-up less half an OD, minus the radius of straight, then the quarter arc), so the kick mark must sit at least that plus the kick arc's own lead-in past the 90 mark, and a shorter kick is refused naming the smallest kick height that works.

Do I bend the kick or the 90 first?

Bend the kick first, then flip the conduit and make the 90. The kick is a small bend that still fits through the bender shoe easily; once the 90 is made, orienting the conduit to put a kick in the correct plane is awkward and error-prone. Make the kick, sight down the conduit to confirm the plane, then bend the 90 at the mark nearer the stub end.

What angle should I use for a kick?

Use the smallest angle that clears the obstruction in the space you have. 10 and 15 degrees give the gentlest wire pull and the least shrink but need the most room: an 8-inch kick takes about 46 inches of travel at 10 degrees versus 16 inches at 30 degrees. 22.5 degrees is easy to lay out on a bender head with a dedicated 22.5 degree mark. Whatever you choose, the kick angle adds to the run's total degrees between pull points.

Does a kick count toward the NEC 360 degree limit?

Yes. NEC 358.24(B) counts every bend between pull points, in any direction. A kick 90 with a 22.5 degree kick uses 112.5 degrees of the 360 degree budget (90 + 22.5). A run with three kick 90s at 22.5 degrees would be at 337.5 degrees, leaving no room for even a small offset before a pull box is required.


More Bending References