EMT Bending Reference
1" EMT Bending Calculator
Take-up, deduct, gain, and stub-up marks for 1 inch EMT, with the interactive bender. Offset and saddle multipliers are the same on every conduit size; the take-up, deduct and gain change with the pipe, and so does whether a bend can be made at all, because the size's bend radius sets the smallest offset, saddle or kick. This page covers what changes with 1 inch pipe.
1" EMT Bender Constants
The four constants that change with conduit size, for all standard EMT hand-bender sizes. Take-up equals deduct on standard benders.
1" EMT Stub-Up Marks
For a 90-degree stub-up, mark the conduit at the stub height minus the 8" take-up, then bend up with the arrow on your mark.
Mark position for a 90-degree stub-up in 1 inch EMT, by desired stub height
Swipe the table sideways to see the rest of its columns. →
| Stub Height | Mark From End |
|---|---|
| 8" (shortest) | 0" |
| 10" | 2" |
| 12" | 4" |
| 18" | 10" |
| 24" | 16" |
Mark = stub height − 8" take-up. Verify with a test bend on your bender.
6" is not in this table: A 6" stub is below this bender's 8" take-up. 1/2" EMT has a 5" take-up, so the same stub is reachable in that size if the run allows it. Otherwise raise the stub to at least 8".
Bend 1" EMT
The calculator is set to 1 inch EMT. Pick a bend type and enter your measurements for exact marks, shrink, and an SVG diagram.
Bend type: 15 families, pick one
Common bends
Klein and Gardner Bender EMT hand bender take-up, with NEC Chapter 9, Table 2 radii by trade size. Greenlee's SITE-RITE hand-bender manual rates the same benders for 1/2" through 1-1/4" EMT and 1/2" through 1" rigid and IMC, and its older IM 1071 manual says 1/2" through 1" rigid: pick the type above (1-1/4" is not carried in IMC or RMC: no held bender document bends it by hand).
Deducts are not standard across makes. Greenlee's own manuals publish no table and tell you to read the deduct off the bender casting.
Show the math
- MATHMark = Stub Height − Take-up = 12 − 8 = 4"
- MATHStub leg after the 90's gain = Stub − Gain = 12 − 3.63 = 8.37" (the stub measured to its outside corner, less the field gain: the pipe beyond the STAR mark; the pipe beyond the ARROW mark is Stub − Take-up = 4", and the two differ by take-up minus gain, 4.37" in 1" EMT)
Where this number comes fromIntry Verified
- Calculated from
- 1" EMT bender, Klein and Gardner Bender take-up 8". Marks and shrink from the bender-chart constants where a manufacturer prints the angle (offset multiplier, 3-point saddle multiplier and shrink per inch) and from bend geometry elsewhere (offset 1/sin, saddle depth/sin(half-angle), kick travel); take-up from the EMT bender profile for your conduit size, or the deduct you entered (the only take-up carried for IMC and RMC), and gain from that conduit's own radius and outside diameter. See the full receipt ↓
- Run with
- Bend90° Stub
- Conduit1" EMT
- Setup12" stub, 90°
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius. This is our own deterministic gate, not a third-party audit.
- Final say
- Field-verify against the actual bend. Bender take-up varies by tool and shoe.
Intry Verified · Build 525536D · 2026-11-13
Next on this job
This run travels with its receipt: 1" EMT, 90° Stub, 1 mark, stub leg after the 90's gain 8.37".
- Conduit fillCarries 1" EMT into the fill calculator; add the conductors you are pulling.
- Wire sizeCarries the receipt only: a bend run knows no load, so enter the amps, voltage and one-way distance there.
- Box fillCarries the receipt only: a bend run knows no box, so enter the box and its conductors there.
One question
Did this help you on the job?
Frequently Asked Questions
What is the take-up for 1 inch EMT?
The take-up for 1 inch EMT is 8 inches, published by Klein and Gardner Bender. Take-up is the distance from the bender's arrow to the back of a finished 90-degree bend, so you subtract it from the desired stub height to find your mark; on this calculator it is also the shortest stub that size can make, with the mark at the very end of the pipe. For a 12-inch stub in 1 inch EMT, the mark goes at 12 − 8 = 4 inches from the end of the conduit.
What is the deduct for a 1 inch EMT 90?
The deduct for a 1 inch EMT 90-degree bend equals the take-up, 8 inches, on a standard hand bender. Deduct and take-up are the same number: measure your stub height, subtract 8, and place the mark there. Some benders stamp this value on the shoe, but verify it with a test bend on your specific tool.
How much gain does a 1 inch EMT 90 have?
A 90-degree bend in 1 inch EMT has a gain of 3.63 inches, measured to the outside corner the way a tape reaches it. Gain is the material the curved bend saves compared to two straight pieces meeting at a square corner. When you figure the developed length of a bent piece, subtract 3.63 inches for each 90 in 1 inch EMT. Larger conduit has a larger radius and diameter, so it has more gain.
Do offset multipliers change for 1 inch EMT?
No. Offset multipliers and shrink per inch depend only on the bend angle, not the conduit size. A 30-degree offset uses a multiplier of 2.0 and 1/4 inch of shrink per inch whether you bend 1 inch EMT or any other size. Take-up, deduct, radius and gain change with conduit size, and so does whether the offset can be bent at all: at the size's NEC Chapter 9, Table 2 bend radius the two arcs need straight conduit between them, so a shallow offset that bends in 1/2 inch EMT can refuse in 1-1/4 inch. See the offset multiplier chart for the angle-based values.
Other Sizes & References
1/2" EMT Bending
Take-up 5", gain 2.42", and stub marks for 1/2 inch pipe.
3/4" EMT Bending
Take-up 6", gain 2.85", and stub marks for 3/4 inch pipe.
1-1/4" EMT Bending
Take-up 11" (unconfirmed), gain 4.62", and stub marks for 1-1/4 inch pipe.
Offset Multiplier Chart
Multipliers and shrink per inch (the same on every size).
Conduit Gain Chart
Gain by size and the developed-length formula.