Bending Reference

EMT Offset Multiplier Chart

Multipliers and shrink constants for every standard offset angle: 10, 15, 22.5, 30, 45, and 60 degrees. Travel tables for common offset heights, worked examples, and the formula for any angle in between.

Quick answer: Offset multipliers are 6.0 at 10°, 2.6 at 22.5°, 2.0 at 30°, 1.4 at 45°, and 1.2 at 60°, the constants bender-manufacturer charts print and the ones this calculator applies. Each is the exact 1/sin(angle) rounded for a tape measure (5.76, 2.61, 2.00, 1.41 and 1.15 unrounded); 15° has no chart row, so it uses the exact 3.86. Multiply the offset height by the multiplier to get the distance between bend marks. Shrink runs 1/16" per inch at 10° up to 1/2" per inch at 60°.

Intry Verified. The per-angle offset multipliers and shrink-per-inch values in this chart are read from the locked conduit-bending engine on every build: the bender-chart constants where a manufacturer prints the angle, and the bend trigonometry (1/sin θ) beside them and for every other angle. Those figures are computed by a locked engine straight from the source it cites, not hand-typed, and that computation re-runs inside a deterministic test on every deploy. Source-checked. Locked. This is our own deterministic gate, not a third-party audit. What Intry Verified means

Run this in your AI. Ask Claude or ChatGPT to find the offset multiplier and shrink for a 30 degree bend and it runs the Intry Conduit Offset Bend Calculator live, handing back the verdict with its cited source instead of a guess. Then keep the reading as one job in the Intry app.

Offset Multiplier and Shrink Chart

Travel (distance between marks) = offset height × multiplier. Shrink = offset height × shrink per inch. Both columns are the bender-chart constants wherever a manufacturer prints the angle, which is what the calculator applies; the multiplier is 1 / sin(angle) rounded, and the exact cosecant is shown beside it.

Offset multiplier and shrink per inch of offset height, by bend angle

Swipe the table sideways to see the rest of its columns. →

Bend AngleMultiplier (applied)BasisExact 1/sinShrink per InchShrink (decimal)
10°6.0bender chart5.761/16"0.063
15°3.861/sin (no chart row)3.86not published0.132
22.5°2.6bender chart2.613/16"0.188
30°2.0bender chart2.001/4"0.250
45°1.4bender chart1.413/8"0.375
60°1.2bender chart1.151/2"0.500

For any angle not listed, the calculator applies 1 / sin(angle) as the multiplier and tan(angle / 2) as shrink per inch, and says so in its receipt. At a charted angle it applies the chart, so its marks match the table cast on your bender.

Travel and Shrink for Common Offset Heights

Mark spacing (travel) and total shrink for two field angles, run through the calculator's own engine: travel = height × the applied multiplier (2.0 and 1.4) and shrink = height × the chart constant. The marks are the same on every EMT size, but whether the bend can be made is not: at the NEC Chapter 9, Table 2 bend radius the two arcs need straight conduit between them, so a row the engine refuses says so instead of printing a spacing, and names the smallest height that works.

Mark spacing and shrink at 30 and 45 degrees, by offset height

Swipe the table sideways to see the rest of its columns. →

Offset HeightTravel @ 30°Shrink @ 30°Travel @ 45°Shrink @ 45°
2"4"1/2"not bendable in any EMT size this calculator carries (smallest offset depth that works: 2-3/8" in 1/2", 4-5/16" in 1-1/4")-
3"6"3/4"4-3/16"1-1/8"
4"8"1"5-5/8"1-1/2"
5"10"1-1/4"7"1-7/8"
6"12"1-1/2"8-3/8"2-1/4"
8"16"2"11-3/16"3"

Calculate Any Offset

Enter your offset height and angle to get exact marks, travel, and shrink with an SVG diagram. The calculator also handles rolling offsets, saddles, 90s, and kicks.

Bend type: 15 families, pick one

Offsets
Saddles
90s and kicks
Racks of conduit
Large radius and corners
The whole stick

Common bends

Klein and Gardner Bender EMT hand bender take-up, with NEC Chapter 9, Table 2 radii by trade size. Greenlee's SITE-RITE hand-bender manual rates the same benders for 1/2" through 1-1/4" EMT and 1/2" through 1" rigid and IMC, and its older IM 1071 manual says 1/2" through 1" rigid: pick the type above (1-1/4" is not carried in IMC or RMC: no held bender document bends it by hand).

Shrink per inch of offset:

10°: 1/16"15°: 0.13222.5°: 3/16"30°: 1/4"45°: 3/8"60°: 1/2"
Offset bend: 4" rise at these marks, 30°4" rise at marks8" travelMark 1Mark 230°
First bend mark0"
Second bend mark8"
Travel8″
Mark Spacing8″
Shrink (total)1″
Multiplier applied2x
Actual rise at these marks4″
Shrink1"
Developed Length
8"
Show the math
  1. MATHTravel = Height × chart multiplier = 4 × 2 = 8"
  2. MATHShrink = Height × Shrink/inch = 4 × 0.2500 = 1"
  3. MATHMark spacing = 8"

Bender charts print a 2.0 multiplier at 30°, which this calculator uses, and exact 1/sin(30°) is the same 2.00, so two bends at that spacing rise exactly the depth you asked for.

Where this number comes fromIntry Verified
Calculated from
Bender-chart offset multiplier (2.0), Greenlee and Gardner Bender. Marks and shrink from the bender-chart constants where a manufacturer prints the angle (offset multiplier, 3-point saddle multiplier and shrink per inch) and from bend geometry elsewhere (offset 1/sin, saddle depth/sin(half-angle), kick travel); take-up from the EMT bender profile for your conduit size, or the deduct you entered (the only take-up carried for IMC and RMC), and gain from that conduit's own radius and outside diameter. See the full receipt ↓
Run with
  • BendOffset
  • Setup4" offset @ 30°
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius. This is our own deterministic gate, not a third-party audit.
Final say
Field-verify against the actual bend. Bender take-up varies by tool and shoe.
What Intry Verified means

Intry Verified · Build 525536D · 2026-11-13

Next on this job

This run travels with its receipt: 1/2" EMT, Offset, 2 marks, developed length 8".

  • Conduit fillCarries 1/2" EMT into the fill calculator; add the conductors you are pulling.
  • Wire sizeCarries the receipt only: a bend run knows no load, so enter the amps, voltage and one-way distance there.
  • Box fillCarries the receipt only: a bend run knows no box, so enter the box and its conductors there.

One question

Did this help you on the job?

First bend mark: 0"8" total

Worked Example: 5-Inch Offset at 22.5 Degrees

Given: A duct forces your run up 5 inches, and the obstruction starts 36 inches from the end of the conduit. You choose 22.5 degrees because your bender head has a dedicated 22.5 degree mark.

Step 1: Travel. Travel = 5 × 2.6 = 13 inches between marks, using the chart multiplier. Exact 5 / sin(22.5°) is 13.07", a sixteenth more; the chart rounds it away, and so does this calculator.

Step 2: Shrink. Shrink = 5 × 3/16" = 15/16 inch. The run gets almost an inch shorter, so measure to the obstruction and subtract: 36 − 15/16 = 35-1/16 inches to the first mark.

Step 3: Mark and bend. First mark at 35-1/16", second mark 13" farther along. Bend 22.5 degrees at the first mark, flip the conduit, sight the bends in the same plane, and bend 22.5 degrees at the second mark.

Result: A 5-inch rise over about 13 inches of run, with the far side of the offset landing exactly where the straight run resumes.

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

What is the multiplier for a 10 degree bend?

The multiplier for a 10 degree offset is 6.0, the constant bender-manufacturer charts print, and it is what this calculator applies. It is the rounded cosecant: 1 divided by sin(10 degrees) is 5.76. Shrink is 1/16 inch per inch of offset height. A 10 degree offset needs a lot of room: a 4-inch offset puts the marks 4 x 6.0 = 24 inches apart, so use it only where you have long straight runs and want the gentlest possible wire pull.

What is the 22.5 degree offset multiplier?

The multiplier for a 22.5 degree offset is 2.6 on the bender chart (exact 1/sin is 2.61), and the shrink is 3/16 inch per inch of offset height. For a 4-inch offset at 22.5 degrees, the marks are 4 x 2.6 = 10.4 inches apart and the run shrinks 4 x 3/16 = 3/4 inch. A bender head with a dedicated 22.5 degree mark makes this angle easy to lay out.

What is the multiplier for a 30 degree offset?

The multiplier for a 30 degree offset is 2.0, and it is the one angle where the bender chart and the exact 1/sin agree to the digit, because sin(30 degrees) = 0.5. Multiply the offset height by 2 to get the distance between your two bend marks, and use 1/4 inch of shrink per inch of offset height. This easy math is why 30 degrees is the standard angle taught in apprenticeship programs.

How do you find the offset multiplier for any angle?

Multiplier = 1 / sin(bend angle), the cosecant, rounded the way the bender charts round it. For example, 1 / sin(45 degrees) = 1 / 0.7071 = 1.41, which the charts print as 1.4 and this calculator applies as 1.4; for an angle no chart lists, the calculator applies the unrounded 1 / sin. Shrink works differently. The per-angle shrink constants come from the published field chart rather than from a formula, and the 10 degree row sits about 29 percent below tan(angle / 2), so they are not a rounding of the geometry. The chart on this page covers the standard hand bender angles. For an angle it does not list, the calculator computes shrink as tan(angle / 2).

How do I use shrink when laying out an offset?

Shrink is how much shorter the conduit run becomes after you bend the offset. Multiply the offset height by the shrink-per-inch constant for your angle, then subtract that amount when measuring to your first mark from a fixed reference point. Example: your obstruction is 30 inches away and you are bending a 4-inch offset at 30 degrees. Shrink = 4 x 1/4 inch = 1 inch, so your first mark goes at 30 - 1 = 29 inches.

What is the shrink for a 10 degree bend?

1/16 inch (about 0.063 inch) per inch of offset height for a 10 degree bend. Multiply the offset height by 1/16 to get the total shrink: a 4-inch offset at 10 degrees shrinks the run 4 x 1/16 = 1/4 inch. For comparison, shrink is 3/16 inch per inch at 22.5 degrees, 1/4 inch at 30 degrees, 3/8 inch at 45 degrees, and 1/2 inch at 60 degrees.

How much does a 30 degree offset shrink the run for each inch of offset height?

1/4 inch. When using 30 degree bends, the conduit shrinks 1/4 inch (0.25 inch) for every inch of offset height. So a 6-inch offset at 30 degrees shrinks the overall run 6 x 1/4 = 1-1/2 inches, which you subtract when locating the first bend mark.

Does conduit size change the offset multiplier?

No. The multiplier and shrink constants depend only on the bend angle, not the conduit size. A 30 degree offset uses a multiplier of 2.0 whether you are bending 1/2 inch or 1-1/4 inch EMT. Conduit size changes take-up, gain and deduct on 90 degree bends, and it changes whether an offset can be bent at all: at the size's NEC Chapter 9, Table 2 bend radius the two arcs need straight conduit between them, so a shallow offset at a steep angle is refused, and refused sooner in larger pipe. The marks themselves do not change. See the 90 degree deduction chart for the take-up values.

How many degrees does an offset add toward the NEC 360 degree limit?

An offset counts as twice its bend angle, because it is two equal bends. A 30 degree offset adds 60 degrees; a 45 degree offset adds 90 degrees. NEC 358.24(B) limits EMT runs to 360 degrees of total bends between pull points, so a run with two 90s (180 degrees) and two 30 degree offsets (120 degrees) is at 300 degrees and has room for only one more small offset before it needs a pull box.


More Bending References