Bending Reference

Conduit Gain Chart

The material a 90-degree bend saves versus two straight legs measured to the outside corner, by EMT size, with the pure centerline arc savings alongside and the developed-length formula for cutting conduit to the right overall length.

Quick answer: Gain is the length a 90 saves versus a square corner. Measured to the outside corner the way you run a tape, it is 2.42" for 1/2" EMT, 2.85" for 3/4", 3.63" for 1", and 4.62" for 1-1/4". To size a piece, add the legs to the outside corner and subtract the gain for each 90: developed length = legs − (gain × 90s).

Gain by EMT Size

Standard EMT hand-bender values. The gain column is the field value you subtract when legs are measured to the outside corner. The pure arc savings column is the centerline-only figure, exactly one conduit OD less. Take-up positions a single 90 mark; gain sizes the overall piece.

90-degree bend gain (outside corner), pure arc savings, take-up, and radius by EMT trade size

Swipe the table sideways to see the rest of its columns. →

Conduit SizeGainPure Arc SavingsTake-UpRadius
1/2" EMT2.42"1.72"5"4"
3/4" EMT2.85"1.93"6"4.5"
1" EMT3.63"2.47"8"5.75"
1-1/4" EMT4.62"3.11"11" †7.25"

† Both take-up tables we hold, Klein and Gardner Bender's, stop at 1", so the 1-1/4" take-up is a field value no manufacturer document we hold confirms. Check it against your own bender before you cut.

Intry Verified. The gain, pure arc savings, and developed-length figures on this page are computed by the locked conduit-bending geometry engine from each EMT size's centerline radius and outside diameter, never hand-typed. Those figures are computed by a locked engine straight from the source it cites, not hand-typed, and that computation re-runs inside a deterministic test on every deploy. Source-checked. Locked. This is our own deterministic gate, not a third-party audit. What Intry Verified means


The Two Gain Numbers, and Why They Differ by One OD

A 90-degree bend has two corners you could measure to, and that is where gain confusion comes from:

  • Pure arc savings (centerline). Geometrically, the curved centerline is shorter than routing along the two centerline legs to their corner by radius × (2 − π/2). On 1/2" EMT that is 1.72". This is the true arc savings, but it is measured to a corner that only exists on the pipe's centerline.
  • Field gain (outside corner). Your tape does not reach the centerline corner. It reaches the outside corner, where the two outer surfaces meet, and that point sits one full conduit outside diameter (0.706" on 1/2" EMT) farther out. So the gain you actually subtract from a tape layout is one diameter larger than the arc savings: 2.42", versus 1.72" at the centerline.

Published field charts and manufacturer tables list the outside-corner value, so that is the gain in the chart above and the one the calculator subtracts. The centerline figure is the geometry underneath it. If your own layout references the centerline instead, use the pure arc savings column; the two always differ by exactly one OD.


Developed Length Formula

Developed length is the total conduit a bent piece actually needs. Measure each leg to the outside corner, add them, then subtract the gain for every 90 in the piece:

Developed length = (sum of legs to the outside corners) − (gain × number of 90s)

Skipping the gain deduction makes a bent piece come out too long. On a piece with several 90s the error stacks up fast: three 90s in 1" EMT would leave you almost 11 inches long if you forgot the gain.


Worked Example: An Offset-Free L in 1/2" EMT

Given: An L-shaped run with a 12-inch vertical leg and an 18-inch horizontal leg measured to the outside corner, one 90-degree bend, in 1/2" EMT (gain = 2.42").

Step 1: Sum the legs. 12 + 18 = 30 inches to the outside corner.

Step 2: Subtract the gain. 30 − 2.42 = 27.58 inches of conduit to cut.

Result: Cut the piece at 27.58", not 30". The 2.42" gain is the material the curved bend saves versus a square corner.


Frequently Asked Questions

What is gain in conduit bending?

Gain is the amount of conduit a 90-degree bend saves compared to two straight pieces meeting at a square corner. Because the bend follows a curved radius instead of a sharp right angle, the finished path is shorter than the two leg measurements added together. In the field you measure legs to the outside corner, so the gain you subtract is 2.42 inches for 1/2-inch EMT. You subtract the gain from the summed leg lengths to find how much conduit to actually cut.

What do you call the length a 90-degree bend's curve saves against a square corner?

It is called gain. The arc of a 90-degree bend is shorter than the two straight legs measured to the corner, and that difference is the gain. Measured to the outside corner the way a tape reaches it, the standard EMT hand-bender gain is 2.42 inches for 1/2 inch, 2.85 inches for 3/4 inch, 3.63 inches for 1 inch, and 4.62 inches for 1-1/4 inch. Subtracting gain is what makes a multi-bend piece come out to the correct overall length.

Why are there two different gain numbers for the same conduit?

Because a 90 has two corners you could measure to. The pure arc savings is centerline only: the curved centerline is 1.72 inches shorter than routing to the centerline corner on 1/2-inch EMT. But a tape measures to the outside corner, which sits one full conduit outside diameter (0.706 inch on 1/2-inch EMT) farther out. So the gain you actually subtract from a tape layout is one diameter larger than the arc savings: 2.42 inches, versus 1.72 inches at the centerline. Field charts and manufacturer tables list the 2.42-inch outside value; the 1.72-inch centerline value is the geometry underneath it.

How do you calculate developed length?

Developed length is the total conduit needed for a piece with bends. Add the leg dimensions measured to the outside corner, then subtract the gain for each 90-degree bend: developed length = sum of legs minus (gain x number of 90s). For an L-shape with a 12-inch and an 18-inch leg in 1/2-inch EMT, developed length = 12 + 18 - 2.42 = 27.58 inches. Cutting to the summed 30 inches would leave the piece too long.

Is gain the same as take-up?

No. Take-up (also called deduct) is used to place the bend mark for a single 90: it is the distance from the bender arrow to the back of the finished bend, subtracted from the stub height. Gain is used when figuring the total length of conduit for a run with bends. Take-up positions the mark; gain sizes the overall piece. Both come from the bend radius but they solve different problems.

Does gain change with conduit size?

Yes. Larger conduit has a larger bend radius and a larger diameter, so its 90-degree bends save more material and the gain is larger: 2.42 inches for 1/2 inch up to 4.62 inches for 1-1/4 inch EMT. This is the opposite of offset shrink, which depends only on the bend angle and is the same on every conduit size. Always use the gain that matches the conduit you are bending.


More Bending References