Intry Verified receipt

Is the Intry MCA & MOCP Breaker Calculator accurate and NEC compliant?

The provenance receipt for the Intry MCA & MOCP Breaker Calculator: the exact authority its values derive from, the edition they are keyed to, who has final say, and what our automated checks hold them against, rebuilt from their cited source.

Short answer: It computes from the NEC sections named below (NEC 2023), and our automated checks hold its answers against values written from those sources for the cases the checks cover, not for every input you can enter. Whether an installation is NEC compliant is decided by the inspector, not by a calculator. The unit nameplate has final say. NEC Article 440 governs the sizing. Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 30639 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from the cited NEC Article 440 section. This is our own deterministic gate, not a third-party audit. The per-tool receipt is public at https://www.intrysys.com/verified.

The receipt

Calculated from
NEC 440.33, 440.34, 440.35 and 430.24 · NEC 440.22, 440.22(A) and 440.22(B)(1) · NEC 240.6(A) · NEC 240.4(G) (Article 440) · NEC 440.1, 440.21, 424.4(B) and 424.19 (a circuit with no compressor) · NEC 310.15(B)(1) and 310.15(C)(1) · NEC 310.15(B)(2) · NEC 110.14(C) · NEC 440.14, 440.12 and 110.26(A) · NEC 440.52 · NEC Table 310.16 · NEC Table 250.122 · NEC 440.4(B) and 110.3(B) · NEC Chapter 9 (voltage drop) and 210.19(A) (NEC 2023). Reused verbatim from the locked engine, never re-written for this page. The documents it rests on are listed in the source receipt on the tool page.
Edition
NEC 2023
Checked
Before any release, an automated check runs the locked engine that produces these figures and holds its answers against values written from the source it cites, so a checked number answers to its source and not merely to itself. The check covers the cases someone wrote a check for, not every input the tool accepts: it tells you where a number comes from, and it is not a proof of every value. As of the current build that suite holds 30639 checks, and this page has to clear them too. This is our own deterministic gate, not a third-party audit.
Runnable
Exposed at the Intry MCP endpoint. An AI assistant can run this calculator, and before each release an automated check confirms the answer it returns is identical to the one the website's own engine produces.
Final say
The unit nameplate has final say. NEC Article 440 governs the sizing.

Frequently Asked Questions

Is the Intry MCA & MOCP Breaker Calculator accurate and NEC compliant?

It computes from the NEC sections named below (NEC 2023), and our automated checks hold its answers against values written from those sources for the cases the checks cover, not for every input you can enter. Whether an installation is NEC compliant is decided by the inspector, not by a calculator. The unit nameplate has final say. NEC Article 440 governs the sizing. Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 30639 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from the cited NEC Article 440 section. This is our own deterministic gate, not a third-party audit. The per-tool receipt is public at https://www.intrysys.com/verified.


Use it