Electrical / runnable MCP tool

Run the MCA & MOCP Breaker Calculator in your AI assistant

Through the free Intry MCP server, Claude, ChatGPT, or Cursor runs this exact calculator and hands back a verdict and the cited source, not a guess. Tool name: mca_mocp.

What it runs: Wire, breaker, ground and voltage drop for an HVAC unit, read straight off its nameplate MCA and MOCP.

How it computes the answer

From an HVAC nameplate MCA and MOCP, or from compressor RLA and fan FLA in RLA mode: the minimum wire size from NEC 310.16 at the ambient Table 310.16 itself assumes, with 3 or fewer current-carrying conductors, the breaker as the largest standard 240.6(A) rating not exceeding MOCP per 440.22, the ground from 250.122, and voltage drop.

What it cites

Your assistant calls the same engine the interactive calculator calls, with the inputs listed under Inputs. It sizes the conductor at 86 F, the ambient Table 310.16 itself assumes, with 3 or fewer current-carrying conductors and insulation rated at the termination temperature you give, so no ambient correction (Equation 310.15(B)(1)), bundling adjustment (Table 310.15(C)(1)) or rooftop adder (310.15(B)(2)) is applied here. This tool takes no ambient, conductor count or insulation input; the web calculator takes them (with a rooftop run) and resizes the conductor. These are the interactive calculator's sources, including the ones for inputs only it takes.

NEC 440.33, 440.34, 440.35 and 430.24
Minimum circuit ampacity, when computed from RLA/FLA: 125% of the largest motor-compressor or motor full-load current plus 100% of the others in the group (440.32 governs a lone compressor, the same 125% result). NEC 440.34 governs instead once a non-motor load such as strip heat shares the circuit, and NEC 440.35 is the ampacity the conductor must reach. In nameplate mode you enter the marked MCA directly. NFPA 70-2023, p. 70-369 / p.70-345.
NEC 440.22, 440.22(A), 440.22(B)(1) and 440.22(B)(2)
Maximum overcurrent protection: the branch-circuit short-circuit and ground-fault device, the largest standard rating that does not exceed the calculated maximum. 440.22(A) is the ceiling for an INDIVIDUAL motor-compressor, 175% of its rated-load current or branch-circuit selection current and 225% where the motor will not start on 175%. Where other loads share the circuit and the motor-compressor is the largest load connected, 440.22(B)(1) permits that value PLUS the sum of those other loads; where it is not the largest load, 440.22(B)(2) applies instead. The tool takes the largest motor entered as the motor-compressor, so it falls back to its general bound rather than the (B)(1) sum only where a non-motor load is larger than every motor; where a fan's current is larger than the compressor's, check 440.22(B)(2) yourself. The tool applies Exception No. 1's round-up to the next standard rating and Exception No. 3's 15 A floor. Read from the primary (p.70-368).
NEC 240.6(A)
Standard overcurrent-device ratings. The recommended breaker is the largest standard rating at or below the MOCP ceiling (and, where minimum-sizing applies, the smallest standard rating at or above the MCA). Read from the primary.
NEC 240.4(G) (Article 440)
Air-conditioning and refrigeration branch-circuit conductors are protected under Article 440, so they are exempt from the 240.4(D) small-conductor overcurrent cap. This exemption applies inside Article 440 only, never on a general branch circuit. Read from the primary (p.70-124).
NEC 440.1, 440.21, 424.4(B) and 424.19 (a circuit with no compressor)
Article 440's special provisions, including the Part III overcurrent relief Table 240.4(G) points to, are for circuits supplying a hermetic refrigerant motor-compressor (440.1, 440.21). When you say no compressor is on the circuit (or, in the calculator's RLA mode, leave the compressor RLA at 0; over MCP, answer that no compressor is on the circuit), this tool does not size it: an air handler's heat strips and blower on their own circuit are Article 424, where 424.4(B) sizes the conductors at 125% of the heater and blower and Table 240.4(G) has no row, so it sends you to the heat strip calculator, and its disconnect is 424.19's (rated at least 125 percent of the motor and heater load, lockable, within sight of the unit's supplementary devices), never 440.14's. NFPA 70, 2023 edition, pages 70-365, 70-368 and 70-323.
NEC 310.15(B)(1) and 310.15(C)(1)
Ambient-temperature correction factors (310.15(B)(1)) and the more-than-three-conductor bundling adjustment (310.15(C)(1)), applied to the base ampacity before the terminal cap.
NEC 310.15(B)(2)
The rooftop option. For raceways or cables in direct sunlight where the distance above the roof to the bottom of the raceway is less than 19 mm (3/4 in), a temperature adder of 33 C (60 F) is added to the outdoor temperature. Type XHHW-2 conductors are excepted. NFPA 70-2023, p. 70-184.
NEC 110.14(C)
Terminal temperature limitation. Ampacity is held to the lowest temperature rating of any connected termination, even when a 90°C conductor is installed. On a circuit rated 100 amperes or less, 110.14(C)(1)(a) makes the 60°C column the rule and allows the 75°C column under (3), "Conductors with higher temperature ratings if the equipment is listed and identified for use with such conductors" (NFPA 70-2023, p. 70-65); over 100 amperes, or marked for conductors larger than 1 AWG, 110.14(C)(1)(b) makes 75°C the baseline. NEC 334.80 holds NM-B cable to the 60°C column. The tool sizes on the column you choose, and where the answer holds only on 75°C terminations it says so beside it. This is the cap most calculators skip.
NEC 440.14, 440.12 and 110.26(A)
The disconnecting means: within sight from and readily accessible to the equipment (NEC 440.14), rated by NEC 440.12, with the working space of 110.26(A) preserved. This tool prints the requirement and does NOT check it: nothing here has been anywhere near the equipment, so the row says so in the row itself. The horsepower tables NEC 440.12 sends you to (NEC Table 430.248, Table 430.249 or Table 430.250 for the rated-load current, and Table 430.251(A) or Table 430.251(B) for the locked-rotor current) are named for the same reason, cited and not read.
NEC 440.52
Compressor overload protection. On an Article 440 circuit the branch-circuit device covers short circuits and ground faults while the equipment's own overload protection, required by 440.52 and verified by the listing, is what protects the conductor. This is why 240.4(G) can relieve the 240.4 conductor rule inside Article 440 and nowhere else.
NEC Table 310.16
Conductor ampacity for the minimum circuit ampacity, the general ampacity table for conductors in raceway or cable, held to the termination column per 110.14(C). Read from the primary (p.70-187).
NEC Table 250.122
Equipment grounding conductor, sized from the circuit's overcurrent device. NFPA 70-2023, p. 70-158.
NEC 250.122(A) and 250.122(B)
Where the run's voltage drop is over 3 percent and the calculator names a larger conductor, it says the ground wire goes up too. 250.122(B) says that where ungrounded conductors are "increased in size for any reason other than as required in 310.15(B) or 310.15(C), wire-type equipment grounding conductors, if installed, shall be increased in size proportionately to the increase in circular mil area of the ungrounded conductors" (NFPA 70, 2023 edition, page 70-157). The calculator names the rule and does not size that larger ground; the ground it shows is Table 250.122's size at the breaker, before the upsize. Where that ground is already at least the size of the larger conductor, the calculator says so in one clause and cites 250.122(A), under which the equipment grounding conductor "shall not be required to be larger than the circuit conductors" (page 70-157).
NEC 440.4(B) and 110.3(B)
The nameplate minimum circuit ampacity and maximum overcurrent rating marked on the equipment govern; the manufacturer's marking is the field ceiling under 110.3(B). Read from the primary.
NEC Chapter 9, Table 8 and NEC 210.19, its Informational Note (voltage drop)
The voltage-drop reading reuses the voltage-drop engine: conductor circular mils from NEC Chapter 9 Table 8 against the advisory 3% recommendation (210.19 Informational Note, guidance, not an enforceable limit).

The code sections those sources name, each with the edition and the page the book prints it on:

Swipe the table sideways to see the rest of its columns. →

Code and editionSectionPrinted page
NEC 2023430.2470-345
NEC 2023440.3370-369
NEC 2023440.3470-369
NEC 2023440.3570-369
NEC 2023440.2270-368
NEC 2023440.22(A)70-368
NEC 2023440.22(B)(1)70-368
NEC 2023440.22(B)(2)70-368
NEC 2023240.6(A)70-124
NEC 2023240.4(G)70-123
NEC 2023424.1970-323
NEC 2023424.4(B)70-323
NEC 2023440.170-365
NEC 2023440.2170-368
NEC 2023310.15(B)(1)70-184
NEC 2023310.15(C)(1)70-184
NEC 2023310.15(B)(2)70-184
NEC 2023110.14(C)70-65
NEC 2023110.26(A)70-67
NEC 2023440.1270-367
NEC 2023440.1470-367
NEC 2023440.5270-369
NEC 2023Table 310.1670-187
NEC 2023Table 250.12270-158
NEC 2023250.122(A)70-157
NEC 2023250.122(B)70-157
NEC 2023110.3(B)70-63
NEC 2023440.4(B)70-365
NEC 2023210.1970-83
NEC 2023Chapter 9 Table 870-725

These are NEC Article 440 rules and referenced tables, applied by the engine to the nameplate values you enter and to the conditions you state, not measurements. The conditions have defaults and the tool says which it used; state yours and the conductor can change. When the nameplate marks MCA and MOP, those markings govern the install; the engine's code-minimum output is a check, and the AHJ has final say.

The full receipt, with every source and how each is cross-checked, is on the interactive MCA & MOCP Breaker Calculator.

Ask your assistant

The one rule that makes it reliable: name Intry in your question. That is what tells Claude to run the mca_mocp tool and answer with the real number, the verdict, and the citation. Leave Intry out and Claude may just guess from memory, which is exactly what you are trying to avoid. Type something like:

“Use Intry to size the wire and breaker for a condenser with MCA 24.5, MOCP 40.”
“Ask Intry for the MCA and breaker from compressor RLA 18 and fan FLA 1.5.”

What it refuses or sets aside

When the nameplate's maximum breaker is larger than NEC 440.22(A) could allow beside its minimum circuit ampacity, it refuses and asks for the nameplate to be read again, because a pair that far apart is more likely a misread plate than a real unit.

Inputs

Swipe the table sideways to see the rest of its columns. →

FieldRequiredAcceptsRangeWhat it is
modeoptionalnameplate, rlanameplate (enter MCA/MOCP) or rla (enter loads). Default nameplate.
mcaoptionalnumbermore than 0Minimum circuit ampacity from the nameplate. Required in nameplate mode (the default): an empty request is refused rather than sized from a default circuit. To size from compressor RLA and fan FLA instead, pass mode: 'rla' with loads.
mocpoptionalnumbermore than 0Maximum overcurrent protection from the nameplate.
loadsoptionalarrayMOTOR loads only in rla mode, the compressor RLA FIRST, then fan FLA; the largest gets the 125% factor per NEC 440.33. For a circuit with no compressor (an air handler's strips and blower), pass compressorOnCircuit: false instead: this tool cannot tell a blower from a compressor.
compressorOnCircuitoptionalbooleanIs a hermetic compressor on this circuit? Default true. false is refused with a pointer to the heat strip calculator: Article 440's relief (Table 240.4(G)) is for circuits supplying a compressor (440.1, 440.21), and an air handler's strips and blower are Article 424, where 240.4(D) holds #10 copper to 30 A.
otherNonMotorAmpsoptionalnumber0 or moreAny NON-motor load on the COMPRESSOR's circuit (strip heat in a packaged unit, crankcase heater). NEC 440.34 governs once this is present, so it must not be passed inside loads[].
voltageoptionalnumbermore than 0Circuit voltage (default 240).
phaseoptionalsingle, threeDefault single.
distanceoptionalnumber0 or moreOne-way run feet for a VD check; 0 skips it (default 0).
materialoptionalcu, alDefault cu.
tempRatingoptional60, 75Termination temperature rating (default 75).

Add Intry to Claude

One paste and Claude can run this tool and the other calculators on Intry's MCP server, right from your phone.

Add Intry to ClaudeOpens Claude with Intry already filled in.
  1. Claude opens with the Intry connector already filled in. Review it and click Add.
  2. (If a field is blank, paste the link below into the URL field.)
  3. In any chat, tap + then Connectors and switch Intry on. Then name Intry in your question (“use Intry to…”) so Claude runs the tool instead of guessing.
https://www.intrysys.com/api/mcp

No login, no API key, and it works on every Claude plan, right from your phone.

Using ChatGPT, Cursor, or a dev tool? See the developer setup on the main page. The endpoint is https://www.intrysys.com/api/mcp.

Every answer comes with the cited NEC Article 440 section, so you can check it or show an inspector. The numbers come from the same calculator we run on intrysys.com, and our automated checks hold its answers against their sources before anything goes live, for the cases the checks cover, not for every input you can enter.

Also on Intry