HVAC · Evacuation
Vacuum Decay Test & Evacuation Criteria
Whether your timestamped micron readings pass the acceptance criterion your equipment's own installation instructions print, quoted. 7 criteria covering Amana, Carrier, Daikin, Goodman, Rheem, Ruud, Trane and York; for equipment it has not read, it says so.
Time from the moment you valved the pump off, and the micron reading at that moment. We need at least 3, and the reason is geometry rather than fussiness: two points make a straight line, so telling a curve that is flattening from one that is climbing takes a third.
More readings over a longer hold is the cheapest way to make this answer stronger, and it costs nothing but the time you were going to spend watching the gauge anyway.
Not the room. Water collects at the cold spot and its vapor pressure is set there, so a line set in a cold crawl space governs this even when the condenser is in the sun. Your pass or fail is measured against your manufacturer's criterion; this temperature sets the separate water line, which is what tells you moisture alone cannot explain a reading.
7 acceptance criteria read out of the manufacturers' own documents. They do not agree, which is why this tool asks instead of publishing a number of its own. Your manual governs your equipment.
Filled in for you if you picked your equipment above, and you can override it. It changes exactly one thing: without it we can still tell you a reading is past what water can do at your temperature, and we cannot tell you it passed. We publish no pass mark, because the manufacturer documents behind this tool do not agree on one. Watch out for the evacuation TARGET printed a few lines away from the HOLD criterion. They are different numbers.
These are things only you can see, and each one changes what your gauge was measuring. We will not judge a test until they are confirmed, because there is no verdict hiding underneath a bad measurement waiting to be released.
- Only 0 reading(s) supplied; 3 is the minimum for a shape.
stopped
Refusal Do not use this tool's answer for this job. With 0 readings there is no curve to read. This is a limit of the measurement, not of the tool. (The declared measurement method of this tool)
1. Two points define a straight line, so telling a curve that is flattening from one that is climbing without bound needs a third point. That is why the minimum here is 3 and not 2. (The declared measurement method of this tool)
2. Isolate the pump, then note the gauge and the clock at least three times while you watch it. Readings spread over a longer hold separate the two answers faster than readings crowded together. (The declared measurement method of this tool)
Show the method
Water line = saturation vapor pressure of water at the system temperature
log10(P bar) = 5.40221 − 1838.675 / (T K − 31.737), NIST Antoine, water
past the water line: moisture alone does not account for it. at or under the water line: your manual decides
no decay rate, no leak size and no plateau projection is published, on purpose
Where this number comes fromIntry Verified
- Calculated from
- The saturation vapor pressure of water, derived from the NIST Antoine coefficients, plus the hold criterion in your own installation instructions. Readings judged against the evacuation acceptance criterion quoted from your equipment's own manufacturer document, with the water line derived on every build from the NIST Antoine coefficients for water. No pass mark of our own, and no cause named. See the full receipt ↓
- Run with
- Readingsnot supplied
- Coldest pointnot supplied
- Hold criterionnot supplied
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,006 automated checks, one suite for the whole site rather than a per-tool count, re-derive those figures and re-check the manufacturer method this tool applies before each deploy. The standard it judges your reading against is the hold criterion in the installation instructions for your equipment, which you supply, judged alongside the vapor pressure of water derived from the NIST Antoine coefficients, so no check of ours can confirm that what you entered is what is printed on your equipment. This is our own deterministic gate, not a third-party audit.
- Final say
- The installation instructions for your equipment have final say on the hold criterion, and a nitrogen pressure test is what locates a leak. A system that holds a vacuum has not been pressure tested.
Intry Verified · Build AF0D4B6 · 2026-11-11
The most repeated number in this trade is a different number for a different job
Search for a vacuum decay standard and the answer comes back immediately: 500 microns. Open the manufacturers' own documents and it falls apart, in both directions at once. Trane asks you to pull to 350 microns first, then passes the system only if it does not rise above 500 in one minute, so a tech who starts the hold at 500 has left himself no headroom at all. Goodman asks for a ten minute hold and calls the system leak-free under 1000 microns, with the band from 1000 to 2000 explicitly not a pass and 2000 the line where a leak is present. In Carrier's 26SCA5 instructions, 500 is what the pump must be capable of reaching and the hold criterion is stated separately as 1000 microns after approximately seven minutes. The same document uses a third figure, 1500, for opening a circuit charged with a flammable refrigerant. One document, three numbers, three scopes.
A calculator that hard-codes one of those has to be wrong about the others, and it is wrong in both directions. Fed a system holding 900 microns at seven minutes, which is the case Carrier's own manual describes as tight and dry, a threshold set at 500 returns a failure and sends a technician to hunt a leak that is not there. Fed a Goodman system sitting at 1800 microns, a tool that has heard "2000 means a leak" hands back a pass on a system Goodman's own manual sends back to re-evacuate. So this tool holds the criteria instead of a threshold, quotes the one that governs your equipment, and refuses for equipment it has not read.
The rule everyone teaches has a boundary, and we measured where it is
The web tool we measured, forum answers we read, and York's own installation manual teach the same thing: a steady continuous rise means a leak, and a rise that levels off after a few minutes means moisture. It is not folklore, it is printed in a manufacturer document, and inside its scope it works. We simulated it against a mixture model over 400 simulated tests at each of three sampling efforts. Against a pure leak of 100 microns per minute with nothing else going on, it finds the leak 7.2 percent of the time on 5 readings over 15 minutes, 27.5 percent on 8 readings over 30 minutes, and 92.2 percent on 12 readings over a full hour. Against a leak happening at the same time as ordinary outgassing, it found the leak in none of the 400 trials, at every one of those settings.
The reason is arithmetic rather than a shortcoming of your gauge. Over a finite window a leak's straight ramp and the early part of a curve that is flattening out are mathematically confounded: the same readings fit both, so no amount of care with the instrument separates them. Two more things break the rule in the other direction. Refrigerant coming back out of the POE oil, and nitrogen trapped in a dead leg after a pressure test, both carry a system with nothing wrong with it past the water line. And a genuinely wet system can plateau well below that line, because water boiling into a vacuum cools itself toward ice and water held in the drier never saturates.
So this tool names no cause, and that is a consequence of the measurement rather than a gap in it. What your readings genuinely support is whether they met the criterion your manufacturer published, and that is what you get. If the leak question is the one you need answered, a nitrogen pressure test answers it, because it pushes outward instead of asking a decay curve to do something it cannot.
The ways a decay test lies, and why none of them show up in the numbers
A micron gauge left near the pump reads the deepest, cleanest part of the setup through a restriction, and it can sit reassuringly low while the system it is supposed to be watching sits far higher. That is the false pass, and it is invisible from the readings themselves. Readings taken before the pump was valved off describe what the pump can hold, not what the system does when left alone. Valve cores left in the circuit restrict the path, so the pump pulls the hose down while the system stays high, and the equalisation afterwards produces a rise that is neither moisture nor a leak but looks exactly like a decay curve.
The fourth is temperature. The water line moves with it, and it is set by the coldest wet spot rather than by the room. Below freezing this stops being a matter of precision and becomes a trap: water in the system is ice, ice holds a far lower vapor pressure than liquid water, and a wet system can sit at a deep flat reading that looks like a pass. This tool refuses below freezing rather than reading it, and it asks you to confirm the other three rather than assuming them, because nothing in a list of micron readings can reveal any of the four.
Vacuum Decay Test FAQs
Is 500 microns the standard for a vacuum decay test?
No, and this is the single most important thing to know about this test. It is the most repeated number in the trade, and the manufacturers' own documents do not support it as one criterion. Trane's Installer's Guide asks you to pull to 350 microns first and then passes the system only if it does not rise above 500 microns in one minute. Goodman asks you to hold for ten minutes and calls the system leak-free under 1000, with 2000 as the line where a leak is present. Carrier states that a tight dry system will hold 1000 microns after approximately 7 minutes. Rheem asks for 500 or less held fifteen minutes. Daikin's VRV commissioning guide asks for a full hour. York gives no time at all. Daikin's residential multi-zone manual does not use microns for the hold at all: it asks you to watch a compound gauge needle for 4 to 5 minutes and confirm it does not swing back. That is 7 criteria covering Amana, Carrier, Daikin, Goodman, Rheem, Ruud, Trane, York. A calculator that hard-codes 500 as the pass mark fails a system Carrier's own manual calls tight and dry. A calculator that has heard "2000 means a leak" does the opposite, and passes a Goodman system at 1800 microns that Goodman sends back to re-evacuate. Pick your equipment above and read your own.
Can a vacuum decay test tell moisture from a leak?
Not reliably, and this tool will not pretend otherwise. The rule the whole trade teaches is that a steady continuous rise means a leak and a rise that levels off means moisture. York's installation manual publishes it in those words, so it is not folklore. But it has a boundary nobody states. Simulated against a mixture model, 400 trials per setting: against a PURE leak with nothing else going on it finds the leak 27.5 percent of the time at 8 readings over 30 minutes, dropping to 7.2 percent at 5 readings over 15, and only reaching 92.2 percent at 12 readings over a full hour. Against a leak COEXISTING with ordinary outgassing it found the leak in ZERO of 400 trials at every setting. The reason is arithmetic rather than instrument quality: over a finite window a leak's linear ramp and the early part of a saturating exponential are mathematically confounded, so no estimator separates them from one decay series. Two other things break the same rule in the other direction. Refrigerant coming out of the POE oil and nitrogen trapped in a dead leg both push a sound system past the water line, and a genuinely wet system can plateau far BELOW it, because water boiling into a vacuum cools itself toward ice. So this tool judges your readings against your manufacturer's criterion and names no cause. If you need the leak question answered, a nitrogen pressure test answers it and a decay curve does not.
Why does this calculator need three readings when others need two?
Because two points define a straight line. Separating a curve that is decelerating toward a plateau from one that is climbing without bound is a question about curvature, curvature is a second difference, and a second difference needs a third point. A tool that takes two readings and names a cause is not measuring the shape at all: it is comparing your level against a threshold and attaching a story to it. That is why 3 is the minimum here. More readings over a longer hold make the answer stronger, and they cost nothing but the time you were already going to spend watching the gauge.
Why does it ask for the coldest part of the system rather than the room temperature?
Because water collects at the cold spot and its vapor pressure is set there. The water line on this page is the saturation vapor pressure of water at the system's own temperature, and if a line set runs through a cold crawl space while the condenser sits in the sun, the crawl space governs. Entering a temperature warmer than the true cold spot raises that line and can hide free water underneath it. It is worth a minute to get right.
What if my equipment is not on your list?
Then this tool has not read your manual and it will not guess at your number, which is the whole design. It covers Amana, Carrier, Daikin, Goodman, Rheem, Ruud, Trane, York, and coverage is per DOCUMENT rather than per brand: Trane's ducted split criterion and Trane's mini-split criterion are genuinely different procedures, so one does not stand in for the other. For anything unread, open the installation instructions for the unit in front of you, find the evacuation acceptance step, and type its two figures in yourself. The tool then judges your readings against that. What it will never do is fill in a house number and let you assume a manufacturer stands behind it.
Why will it not tell me my system passed?
It will, once it has the hold criterion for your equipment, either because you picked your unit from the list or because you typed the figures in from your own manual. Without that number it can still tell you a reading is past what water can do at your temperature, which is a comparison against the vapor pressure of water and needs no threshold. What it will not do is invent a pass mark, because a pass is the claim that your system stayed under the figure your manufacturer specifies, and those figures genuinely disagree across manufacturers.
Why does it not give me a leak rate or tell me how big the leak is?
Because both of those numbers rest on assumptions the readings themselves leave open. Turning a rate of rise into a leak size needs the volume of the system, which the tool does not know, and it assumes the isolation is sound, which is one of the things a rise puts in doubt. A figure computed from an assumption its own answer disputes is worse than no figure, because it looks like a measurement. What the tool reports instead is what you measured: where you isolated, how high it went, over how long, and where the water line sits for your temperature.
Can a vacuum decay test be fooled?
Yes, in four ordinary ways. The tool asks you to confirm three of them rather than assuming, and refuses outright on the fourth. A micron gauge left near the pump reads the deepest, cleanest part of the setup and can stay low while the system sits far higher, which is the false pass. Readings taken with the pump still pulling describe the pump, not the system. Valve cores left in the circuit restrict the path so the pump pulls the hose down while the system stays high, and the equalisation afterwards looks exactly like a decay curve. And below freezing, water in the system is ice, whose vapor pressure is far lower than liquid water's, so a wet system can sit at a deep flat reading that looks like a pass. The tool refuses below freezing, though the bound itself comes from the temperature window the water line can be derived over rather than from the ice argument.
Does a passing decay test mean the system has no leaks?
No, and this is worth being precise about. A pass here means your readings met the hold criterion you entered, over the time you entered. A decay test pulls the system inward, and a joint can seal under vacuum and open under a few hundred PSI of operating pressure. That is why manufacturers specify a nitrogen pressure test as a separate step rather than as an alternative. This test is good evidence that the system is dry and tight enough to charge; it is not a substitute for pressure testing it.
Next in the evacuation job
Nitrogen Pressure Test
The test that locates a leak, and the temperature correction between the pressure you set and the pressure you read hours later.
Line Set Charge Adjustment
How much refrigerant the line length adds or subtracts from the factory charge, once the circuit is ready for it.
Superheat & Subcooling
What the charge should read once it is in, including on R-454B.
Refrigerant Leak Rate
On a system that already holds a charge, the annualised leak rate and what the EPA rule requires you to do about it.