HVAC Decoder

Trane Tonnage From Model Number

Where Trane puts the capacity code, what each code means, and the readings that look like capacity but are not. Read out of 6 documents Trane publishes itself, and 3 American Standard publishes, named further down with the date each was fetched.

Field brief
4TTR4036N1000is 3 tons (36,000 BTU/h). Capacity code 36, read at characters 7-8.3 ton
Where it sitspositions 7-8. Position 6 is the field-connection digit, not part of the capacity, and position 1 is the refrigerant.3 layouts
Divide by 12works on most codes but not all: Trane prints 19, 25, 31, 37, 43, 49, 61 where the division is wrong.7 off-ladder
SourceTrane's own 22-1904-1M-EN and 22-1746-04 and 22-1725-04 and DLR-PSD004A-EN and 22-8301-39 and ODR-PSD038A-EN, and American Standard's own 12-1173-03 and 12-1175-03 and 14-1011-43, fetched 2026-07-24 and 2026-10-01 and 2026-10-11 and 2026-10-12.9 docs

Starting the decoder. The capacity tables below this box are already loaded, so you can read your code off them now.

Nominal capacity from a model number is a nameplate convention, not a measurement. Actual delivered capacity depends on the matched indoor unit, line set, airflow and conditions. Confirm against the data plate's BTU/h rating and the AHRI certificate for the matched system.


Trane Capacity Codes and Tonnage

R-410A generation

Capacity sits at positions 7-8. Position 6 is the field-connection digit, not part of the capacity, and position 1 is the refrigerant. Example: 4TTR4036N1000.

The tonnage is the one the maker's own document prints for this capacity code; any BTU/h shown beside it is converted from that tonnage.

The 15 capacity codes DLR-PSD004A-EN prints for this generation, each decoded here by the same engine the calculator above runs on.
CodeNominal BTU/hTonsCode / 12
1212,0001same answer
1818,0001.5same answer
1918,0001.51.58, so the division is wrong here
2424,0002same answer
2524,00022.08, so the division is wrong here
3030,0002.5same answer
3130,0002.52.58, so the division is wrong here
3636,0003same answer
3736,00033.08, so the division is wrong here
4242,0003.5same answer
4342,0003.53.58, so the division is wrong here
4848,0004same answer
4948,00044.08, so the division is wrong here
6060,0005same answer
6160,00055.08, so the division is wrong here

Table transcribed from Product and Submittal Data, Outdoor Unit 5HCL9 (DLR-PSD004A-EN, February 2026), published by elibrary.tranetechnologies.com, fetched 2026-07-24.

R-454B Low Profile (ODR-PSD038A-EN)

Capacity sits at positions 7-8 again, but on the Low Profile layout positions 2-3 become a two letter system type (HP heat pump, HC cold climate heat pump) instead of the brand letter and unit type. Example: 5HCL5060B1000A.

The tonnage is the one the maker's own document prints for this capacity code; any BTU/h shown beside it is converted from that tonnage.

The 15 capacity codes ODR-PSD038A-EN prints for this generation, each decoded here by the same engine the calculator above runs on.
CodeNominal BTU/hTonsCode / 12
1212,0001same answer
1818,0001.5same answer
1918,0001.51.58, so the division is wrong here
2424,0002same answer
2524,00022.08, so the division is wrong here
3030,0002.5same answer
3130,0002.52.58, so the division is wrong here
3636,0003same answer
3736,00033.08, so the division is wrong here
4242,0003.5same answer
4342,0003.53.58, so the division is wrong here
4848,0004same answer
4948,00044.08, so the division is wrong here
6060,0005same answer
6160,00055.08, so the division is wrong here

Table transcribed from Inverter Side Discharge Heat Pump 5HCL5 (ODR-PSD038A-EN, December 2025), published by elibrary.tranetechnologies.com, fetched 2026-07-24.

R-454B outdoor units (2026 handbook)

Capacity sits at positions 7-8, with the refrigerant at position 1, the brand at 2, the system type at 3 (C, T, W), the product family at 4, Nominal Rated SEER2 at 5 and the field connection at 6. Example: 5TTR5024A1000AA.

The tonnage is the one the maker's own document prints for this capacity code; any BTU/h shown beside it is converted from that tonnage.

The 16 capacity codes 22-8301-39 prints for this generation, each decoded here by the same engine the calculator above runs on.
CodeNominal BTU/hTonsCode / 12
1212,0001same answer
1818,0001.5same answer
1918,0001.51.58, so the division is wrong here
2424,0002same answer
2524,00022.08, so the division is wrong here
3030,0002.5same answer
3130,0002.52.58, so the division is wrong here
3636,0003same answer
3736,00033.08, so the division is wrong here
4242,0003.5same answer
4342,0003.53.58, so the division is wrong here
4848,0004same answer
4948,00044.08, so the division is wrong here
6060,0005same answer
6160,00055.08, so the division is wrong here
7272,0006same answer

Table transcribed from 2026 Residential and Light Commercial Product Handbook (22-8301-39, Effective 1/1/26), published by elibrary.tranetechnologies.com, fetched 2026-10-01.


The Trane codes that dividing by 12 gets wrong

The usual shortcut is that a capacity code is the nominal BTU/h divided by 1,000, so dividing it by 12 gives the tonnage. Trane prints 7 codes where that arithmetic disagrees with Trane's own table, and the table is what the equipment is sold against:

CodeTrane printsCode / 12 gives
191.5 tons1.58
252 tons2.08
312.5 tons2.58
373 tons3.08
433.5 tons3.58
494 tons4.08
615 tons5.08

These are not derivable, only transcribable, which is why this decoder carries Trane's printed table rather than a formula. If you meet one of these codes in the field, arithmetic will land you between two real sizes, and the printed table is the only thing that resolves it.


Worked example: Trane 4TTR4036N1000

4TTR4036N1000Trane3 tons

Capacity code 36 at characters 7-8 of 4TTR4036N1000: 36,000 BTU/h, which is 3 tons at 12,000 BTU/h per ton. Positions 7-8 are the nominal capacity code in Trane's own model nomenclature; position 6 is the field-connection digit, not part of it.

  • Refrigerant: R-410A. Position 1 digit 4 (2 = R-22, 4 = R-410A, 5 = R-454B).
  • Brand letter: Trane. Position 2 letter T, which Trane's legends this reading cites print as TRANE.
  • Product type: Split AC condenser. Position 3 character T.
  • Efficiency: SEER class 14. Position 5 is the Family SEER digit: Trane's legends 22-1746-04, 22-1725-04, 22-1904-1M-EN each print "4 = 14".

Trane has 3 documented layouts: R-410A generation reads capacity at positions 7-8; R-454B Low Profile (ODR-PSD038A-EN) reads capacity at positions 7-8; R-454B outdoor units (2026 handbook) reads capacity at positions 7-8. They agree on where the capacity sits and differ in what the surrounding positions mean, so the size decodes the same way on both while the refrigerant and efficiency digits do not.


What is specific to Trane


Trane equipment in the decoder

The decoder reads or identifies these Trane lines; each one says what it rests on. Open an example to see the decoder's full answer for it.

Each line is identified from the maker document in its Document column. The example is a model in that line's layout, and the reading is what the decoder returns for it.
LineExample modelWhat the decoder readsDocument
Trane legacy split outdoor unit4TWV0036A1000AA3 tons (36,000 BTU/h)22-1746-04, 22-1725-04, 22-1904-1M-EN
Trane R-454B split outdoor unit5TTR5024A1000AA2 tons (24,000 BTU/h)22-8301-39
Trane R-454B Low Profile outdoor unit5HPL5036A1000AA3 tons (36,000 BTU/h)22-8301-39, ODR-PSD038A-EN, DLR-PSD004A-EN
RunTru by Trane outdoor unitA5AC3024B10002 tons (24,000 BTU/h)22-8301-39
Trane ProSpace PTAC (PTEF/PTHF)PTEF0702GAAA Trane packaged terminal unit (PTAC or PTHP): its legend prints this code in BTU/h, not a whole, half or quarter ton, so no tonnage is publishedPTAC-SVX002A-EN
Trane split system (1996 nomenclature, Pub. 22-1633-04)TWN018C100B1.5 tons (18,000 BTU/h), an estimatePub. No. 22-1633-04-1296 (EN)
Trane RTAC air-cooled Series R chillerRTAC140An air-cooled rotary chiller: large commercial equipment, outside this tool's range, so no tonnage is readRLC-PRC006M-EN
Trane Horizon outdoor air unit (OAD, OAN)OAND360A dedicated outdoor air unit: large commercial equipment, outside this tool's range, so no tonnage is readOAU-PRC008A-EN
Trane air handler (1996 nomenclature, Pub. 22-1633-04)TWV018B14An air handler: identified; its maker's document prints no model number legend, so no size is readPub. No. 22-1633-04-1296 (EN)
Trane indoor coil (1996 nomenclature, Pub. 22-1633-04)TXC031E5An indoor coil: identified; its maker's document prints no model number legend, so no size is readPub. No. 22-1633-04-1296 (EN)
  • Trane Precedent packaged rooftop (3 to 10 tons): packaged or light commercial; its capacity is read from the maker's own printed legend or table, for the codes it prints.
  • Trane Precedent packaged rooftop, R-410A J and R-454B K (3 to 25 tons): packaged or light commercial; its capacity is read from the maker's own printed legend or table, for the codes it prints.
  • Trane Foundation packaged rooftop (3 to 25 tons): packaged or light commercial; its capacity is read from the maker's own printed legend or table, for the codes it prints.
  • Trane Precedent packaged heat pump, R-410A WSC (3 to 10 tons): packaged or light commercial; its capacity is read from the maker's own printed legend or table, for the codes it prints.
  • Trane Voyager packaged rooftop (12.5 to 25 tons): packaged or light commercial; its capacity is read from the maker's own printed legend or table, for the codes it prints.

CPSC recall notices naming Trane

Recall 25-369 · 2025-07-03

Hazard, in the notice's words: “The fuel gas valve can open unexpectedly, allowing a gas leak and posing a fire hazard.”

Recall 17-709 · 2016-11-08

Hazard, in the notice's words: “The ground wire in the furnace’s junction box can become loose. If an electrical component then fails and short circuits, the unit poses a shock hazard.”

Recall 14-737 · 2014-06-24

Hazard, in the notice's words: “The ground screws used in some units do not have the two threads required to provide sufficient grounding, posing a shock hazard to consumers.”

Recall 05-104 · 2005-02-11

Hazard, in the notice's words: “A gas leak can occur if there is a crack in the gas valve body near the inlet pipe connection. A build-up of gas in the burner compartment of the unit could occur, which could be ignited by an internal spark.”

Whether a particular unit is inside a recall depends on the models and serials the notice lists. The Trane serial number lookup checks a unit against the notices.

American Standard, same family as Trane

American Standard is in Trane's family. These are American Standard's lines; each one says what it rests on.

Each line is identified from the maker document in its Document column. The example is a model in that line's layout, and the reading is what the decoder returns for it.
LineExample modelWhat the decoder readsDocument
American Standard split outdoor unit4A7A4036B1000AA3 tons (36,000 BTU/h)12-1173-03, 12-1175-03
American Standard R-454B split outdoor unit5A7A4024A1000AA2 tons (24,000 BTU/h)14-1011-43

Other CPSC recall notices naming American Standard

Notices that also name Trane are listed above.

Recall 97-012 · 1996-10-29

Hazard, in the notice's words: “Heat exchangers in the furnace can crack.”

Whether a particular unit is inside a recall depends on the models and serials the notice lists. The American Standard serial number lookup checks a unit against the notices.


The Trane documents behind this page

22-1904-1M-EN · April 2020
Product Data 4TTR4-L Split System Air Conditioner

Published by trane.com. Fetched 2026-07-24. Covers the R-410A position layout, from a Model Nomenclature diagram that numbers its own positions 1-15: position 5 Family SEER (printing 0 = 20), position 6 Split System Connections (0 = Brazed), positions 7-8 Nominal Capacity in 000s of BTUs.

22-1746-04 · 04/09
Split System Cooling Product & Performance Data XL19i

Published by elibrary.tranetechnologies.com. Fetched 2026-10-01. Covers the legacy outdoor model nomenclature on p6, whose Family SEER prints 0 = 10, 1 = 11 and 2 = 12 beside Refrigerant Type 2 = R-22, 4 = R-410A.

22-1725-04 · 02/10
Split System Heat Pump Product Data

Published by elibrary.tranetechnologies.com. Fetched 2026-10-01. Covers the legacy outdoor model nomenclature on p6, printing the same Family SEER (0 = 10) and Refrigerant Type lines as 22-1746-04.

DLR-PSD004A-EN · February 2026
Product and Submittal Data, Outdoor Unit 5HCL9

Published by elibrary.tranetechnologies.com. Fetched 2026-07-24. Covers the explicit Digit 7, 8 Nominal Tonnage table, including every code the divide-by-12 rule gets wrong. The table is Trane's shared capacity table and this tool applies it to both generations; this document itself is an R-454B sheet.

22-8301-39 · Effective 1/1/26
2026 Residential and Light Commercial Product Handbook

Published by elibrary.tranetechnologies.com. Fetched 2026-10-01. Covers NOM-1 on p15: the R-454B outdoor layout for Trane-branded units (System Type C Cold Climate Heat Pump, T AC, W HP; Nominal Rated SEER2 0 and 3 to 8; Field Connection 0 Brazed, 5 Mechanical; Nominal Tonnage 12 to 72) and the Low Profile layout (HP, HC; SEER2 0 and 3 to 9); RTNOM-1 on p272 and its product rows for RunTru by Trane.

ODR-PSD038A-EN · December 2025
Inverter Side Discharge Heat Pump 5HCL5

Published by elibrary.tranetechnologies.com. Fetched 2026-07-24. Covers the R-454B system-type letters and the Digit 5 Nominal Rated SEER2 map, for heat pumps. Its capacity table is the same manufacturer boilerplate as the sheet above rather than an independent second reading of it.

American Standard's own documents, listed here because American Standard models share this nomenclature

12-1173-03 · May 2008
SPLIT SYSTEM COOLING MODELS 4A7A4018-24C/30-060B

Published by www.asdealernet.com. Fetched 2026-10-11. Covers American Standard's Outdoor Units model nomenclature on p6: Refrigerant Type 2 = R-22, 4 = R-410A; position 2 AMERICAN STANDARD; Product Type 6 = Split Heat Pump, 7 = Split Cooling; Family SEER 0 = 10 to 9 = 19; Split System Connections 1-6 Tons 0 = Brazed; Nominal Capacity in 000s of BTUs at positions 7-8.

12-1175-03 · June 2008
SPLIT SYSTEM HEAT PUMP MODELS 4A6H4018-060B

Published by www.asdealernet.com. Fetched 2026-10-11. Covers the same Outdoor Units model nomenclature as 12-1173-03, on p6.

14-1011-43 · Effective 1/1/26 (page 12, NOM-1)
2026 RESIDENTIAL & LIGHT COMMERCIAL PRODUCT HANDBOOK

Published by americanstandardair.com. This is a distributor's copy, served from the distributor host of Denver Winair Co., which American Standard lists as a distributor. Fetched 2026-10-12. Covers American Standard's Model Nomenclature Residential - Outdoor on p12 (NOM-1): Refrigerant Type 5 = R-454B; Brand A = American Standard; System Type 5 = Cold Climate HP, 6 = HP, 7 = AC; Product Family A = Silver/Gold AC, C = Light Commercial, H = Silver/Gold HP, V = Platinum VSPD; Nominal Rated SEER2; Field Connection 0 = Brazed, 5 = Mechanical straight fitting; Nominal Tonnage 12 = 1.0 to 61 = 5.0 at positions 7-8.


Frequently asked questions

How do I find the tonnage of a Trane unit from the model number?

Read the capacity code: on Trane it sits at positions 7-8. Position 6 is the field-connection digit, not part of the capacity, and position 1 is the refrigerant. On 4TTR4036N1000 that code is 36, which is 36,000 BTU/h, or 3 tons, because one ton of cooling is 12,000 BTU/h. Use the OUTDOOR unit's model number for system cooling capacity; the indoor air handler or coil carries its own number. This position comes from Trane's own 22-1904-1M-EN, not from a third-party chart.

Can I just divide the Trane capacity code by 12?

Not on every code. Trane prints 7 capacity codes where that division gives the wrong answer: 19 is 1.5 tons where dividing gives 1.58, 25 is 2 tons where dividing gives 2.08, 31 is 2.5 tons where dividing gives 2.58, 37 is 3 tons where dividing gives 3.08, 43 is 3.5 tons where dividing gives 3.58, 49 is 4 tons where dividing gives 4.08, 61 is 5 tons where dividing gives 5.08. Those values come from Trane's own printed table rather than from arithmetic, which is the whole reason the table exists. On every other code in the table the division does work.

Where is the model number on a Trane unit?

On the data plate on the outdoor unit's side panel, labeled M/N or MODEL, usually directly above the serial number. It is labeled M/N, MODEL or MODEL NO., usually printed directly above or beside the serial number. The model number describes what the unit is, including its capacity. The serial number describes when it was built and carries no capacity information at all.

Which Trane document is this based on?

Product Data 4TTR4-L Split System Air Conditioner (22-1904-1M-EN, April 2020), published by trane.com and fetched 2026-07-24, which covers the R-410A position layout, from a Model Nomenclature diagram that numbers its own positions 1-15: position 5 Family SEER (printing 0 = 20), position 6 Split System Connections (0 = Brazed), positions 7-8 Nominal Capacity in 000s of BTUs. Split System Cooling Product & Performance Data XL19i (22-1746-04, 04/09), published by elibrary.tranetechnologies.com and fetched 2026-10-01, which covers the legacy outdoor model nomenclature on p6, whose Family SEER prints 0 = 10, 1 = 11 and 2 = 12 beside Refrigerant Type 2 = R-22, 4 = R-410A. Split System Heat Pump Product Data (22-1725-04, 02/10), published by elibrary.tranetechnologies.com and fetched 2026-10-01, which covers the legacy outdoor model nomenclature on p6, printing the same Family SEER (0 = 10) and Refrigerant Type lines as 22-1746-04. Product and Submittal Data, Outdoor Unit 5HCL9 (DLR-PSD004A-EN, February 2026), published by elibrary.tranetechnologies.com and fetched 2026-07-24, which covers the explicit Digit 7, 8 Nominal Tonnage table, including every code the divide-by-12 rule gets wrong. The table is Trane's shared capacity table and this tool applies it to both generations; this document itself is an R-454B sheet. 2026 Residential and Light Commercial Product Handbook (22-8301-39, Effective 1/1/26), published by elibrary.tranetechnologies.com and fetched 2026-10-01, which covers NOM-1 on p15: the R-454B outdoor layout for Trane-branded units (System Type C Cold Climate Heat Pump, T AC, W HP; Nominal Rated SEER2 0 and 3 to 8; Field Connection 0 Brazed, 5 Mechanical; Nominal Tonnage 12 to 72) and the Low Profile layout (HP, HC; SEER2 0 and 3 to 9); RTNOM-1 on p272 and its product rows for RunTru by Trane. Inverter Side Discharge Heat Pump 5HCL5 (ODR-PSD038A-EN, December 2025), published by elibrary.tranetechnologies.com and fetched 2026-07-24, which covers the R-454B system-type letters and the Digit 5 Nominal Rated SEER2 map, for heat pumps. Its capacity table is the same manufacturer boilerplate as the sheet above rather than an independent second reading of it. Also listed, as American Standard's own and not Trane's: SPLIT SYSTEM COOLING MODELS 4A7A4018-24C/30-060B (12-1173-03, May 2008), published by www.asdealernet.com and fetched 2026-10-11, which covers American Standard's Outdoor Units model nomenclature on p6: Refrigerant Type 2 = R-22, 4 = R-410A; position 2 AMERICAN STANDARD; Product Type 6 = Split Heat Pump, 7 = Split Cooling; Family SEER 0 = 10 to 9 = 19; Split System Connections 1-6 Tons 0 = Brazed; Nominal Capacity in 000s of BTUs at positions 7-8. SPLIT SYSTEM HEAT PUMP MODELS 4A6H4018-060B (12-1175-03, June 2008), published by www.asdealernet.com and fetched 2026-10-11, which covers the same Outdoor Units model nomenclature as 12-1173-03, on p6. 2026 RESIDENTIAL & LIGHT COMMERCIAL PRODUCT HANDBOOK (14-1011-43, Effective 1/1/26 (page 12, NOM-1)), published by americanstandardair.com (a distributor's copy, served from the distributor host of Denver Winair Co., which American Standard lists as a distributor) and fetched 2026-10-12, which covers American Standard's Model Nomenclature Residential - Outdoor on p12 (NOM-1): Refrigerant Type 5 = R-454B; Brand A = American Standard; System Type 5 = Cold Climate HP, 6 = HP, 7 = AC; Product Family A = Silver/Gold AC, C = Light Commercial, H = Silver/Gold HP, V = Platinum VSPD; Nominal Rated SEER2; Field Connection 0 = Brazed, 5 = Mechanical straight fitting; Nominal Tonnage 12 = 1.0 to 61 = 5.0 at positions 7-8. Every capacity value in the capacity tables above traces to one of those documents, and each is named with the date it was fetched so you can pull it yourself. The sizes in the equipment table are read from the document named in its Document column, listed on this page's source receipt.

Is the decoded tonnage the size I should install?

No. Nominal tonnage is what the unit was built to deliver, not what the building needs, and the old unit may have been oversized or sized before insulation and window changes. Treat it as a starting clue and run a load calculation before matching a replacement. Actual delivered capacity also depends on the matched indoor unit, line set, airflow and conditions.


Related tools

Other brands with their own manufacturer nomenclature document: Carrier tonnage by model number, American Standard tonnage by model number, Lennox tonnage by model number, Goodman tonnage by model number, Amana tonnage by model number.

Got a central system's tonnage? Check it against the house's load.

The old unit's nominal size is a clue, not a load calculation. Oversized systems short-cycle and dehumidify poorly. For central equipment that conditions the whole house, run the numbers before you match a replacement. A PTAC, a single package vertical unit, a room air conditioner or one unit of a VRF system conditions a room or a zone, which this load calculator does not size.