R-290 (Propane, natural, A3)

R-290 (Propane) PT Chart

The full R-290 pressure-temperature reference table, from -20 to 130°F. R-290 is pure propane, a single-component refrigerant, so the chart is one saturation column with zero glide. Checked cell by cell against one other published table, not a separate publisher: Hudson Technologies. A separate publisher catches a transcription, edition or rounding error; a cross-check that resolves to the same equation of state is a consistency check rather than independent confirmation, and this page says which is which.

Field brief
40°F / 100°FR-290 saturates at about 64 psig at 40°F and 174 psig at 100°F (93 psig at 60°F, 151 psig at 90°F).64/174 psig
SafetyA3, highly flammable. Only in equipment listed for R-290, under the charge limits of the applicable UL standard. Never a field drop-in.A3 flammable
GlideZero. One saturation column serves both superheat and subcooling; there is no separate bubble and dew point.single column
Where you left off
Saved in this browser, which can get cleared. The app keeps 10x the readings.Saved in this app.
Intry Pro, coming soon, keeps your saved readings on every device. See Intry Pro ›

Read the R-290 chart at your gauge pressure

The chart below is the reference. This reads it at the pressure you actually have, including between the published rows, and works out superheat or subcooling once you add the line temperature.

the big insulated line, for superheat

Saturation temperature one saturation column4.4°C

4.41 bar is a published row of the R-290 (Propane) chart, not an interpolated value.

Add the suction line temperature to get superheat from this reading.

Where this number comes fromIntry Verified
Calculated from
R-290 (Propane) PT chart. Table looked up from a named datasheet; rack statements quoted from publisher documents, cited beside the sentence. See the full receipt ↓
Run with
  • Pressure4.41 bar, suction line
  • Saturation4.4°C
  • Chart rowa published row of the chart
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 31163 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from the locked modules each figure is traced to: the manufacturer PT tables behind the saturation temperatures, superheat and subcooling, and the transcribed code and service-literature constants behind the charge, metering, airflow, approach and discharge line figures, each quoted with its own source in the panel it appears in. This is our own deterministic gate, not a third-party audit.
Final say
The unit nameplate and the manufacturer's charging chart have final say.
What Intry Verified means

Intry Verified · Build 2731D30 · 2026-10-15

R-290 Pressure-Temperature Table

R-290 (propane) saturation temperature at gauge pressure (psig). Single column, zero glide.
R-290
Pressure (psig)Sat. Temp (°F)
10.7-20°F
16.7-10°F
23.70°F
31.810°F
41.120°F
46.325°F
51.830°F
57.735°F
63.940°F
70.645°F
77.650°F
85.155°F
9360°F
101.465°F
110.270°F
119.575°F
129.380°F
139.785°F
150.590°F
161.995°F
173.9100°F
186.5105°F
199.6110°F
227.8120°F
258.7130°F
Where this table comes from. National Refrigerants R-290 bulletin, NIST REFPROP.
  • Checked against Hudson Technologies R-290 chart, within 0.1 psig [same model]

Both tables resolve to the same propane equation of state, so that agreement is a consistency check rather than an independent measurement.

A separate publisher can catch a transcription, edition or rounding error. A cross-check marked same model resolves to the same equation of state as the base table, so it is a consistency check rather than independent confirmation. One marked same printing prints numbers identical to another table listed here, so the two are one witness and we do not count them twice. Sources last re-verified 2026-08-25.

Read the low-side (suction) pressure and find its saturation temperature for superheat, and read the high-side (liquid) pressure and its saturation temperature for subcooling. The chart is in psig (gauge) and °F. To convert: kPa gauge = psig × 6.895; °C = (°F − 32) / 1.8. The table opens in psig and °F; the buttons above it show the same rows in bar or kPa (gauge) and °C.


R-290 PT Chart FAQs

What is the R-290 pressure at 40F and 100F?

On the R-290 (propane) PT chart, 40F saturation is about 64 psig and 100F is about 174 psig; 60F is about 93 psig and 90F is about 151 psig. R-290 is a single-component refrigerant with zero glide, so the same saturation temperature serves both superheat (suction) and subcooling (liquid); there is no bubble and dew split.

Is R-290 the same pressure as R-22?

Their pressures sit close, so the numbers look similar on a gauge. That similarity does not make R-290 a substitute: R-290 is an A3 highly flammable refrigerant, so it is only used in equipment specifically designed and listed for it, with strict charge limits, and is never charged into a system built for R-22.

How much R-290 can a system hold?

R-290 is classified A3 (highly flammable) by ASHRAE 34, so the charge is capped by the equipment safety standard rather than by system tonnage. The ceiling depends on the appliance type, the room, and the UL or IEC standard the unit is listed to, and it is set by that listing, not by a field rule of thumb. Always follow the equipment nameplate and the standard the unit is built and listed to.

What units is this R-290 PT chart in, and how do I convert to kPa or Celsius?

The table is in psig (gauge pressure) and degrees Fahrenheit, the field-standard units in North America. To convert pressure to kPa (gauge), multiply psig by 6.895. To convert temperature to Celsius, use C = (F - 32) / 1.8. The table opens in psig and degrees Fahrenheit; the buttons above it show the same rows in bar or kPa (gauge) and degrees Celsius.