Manual J heating load by climate zone
How Many BTU to Heat 1,500 Square Feet?
A Manual J heating load our engine computes for DOE's 2021 code-built reference house at 1,500 sq ft, in each IECC climate zone DOE models the house in, with the weather station and the house stated.
The Numbers for 1,500 Sq Ft
Manual J heating load at the 99% design temperature for DOE's reference house scaled to 1,500 sq ft (two storeys, slab, ducts in the attic, the zone's 2021 code envelope), at the ASHRAE station nearest DOE's model site. The house in full is on the BTU per square foot chart.
Swipe the table sideways to see the rest of its columns. →
| Zone and station | Heating, BTU/h |
|---|---|
| 1A MIAMI NHC | 9,326 |
| 2A MACDILL AFB | 14,285 |
| 2B DAVIS-MONTHAN AFB | 18,306 |
| 3A ATLANTA HARTSFIELD-JACKSON | 19,639 |
| 3B EL PASO | 18,299 |
| 3C BROWN FIELD | 12,508 |
| 4A NEW YORK KENNEDY | 17,080 |
| 4B ALBUQUERQUE INTL | 15,000 |
| 4C SEATTLE TACOMA | 12,811 |
| 5A BUFFALO NIAGARA | 20,684 |
| 5B BUCKLEY AFB | 19,699 |
| 5C BREMERTON | 13,925 |
| 6A ROCHESTER INTL | 25,824 |
| 6B GREAT FALLS | 25,782 |
| 7 DULUTH INTL | 27,156 |
| 8 FAIRBANKS | 35,817 |
Bryant says of its own furnace chart: “These Bryant sizing ranges are general estimates, not equipment-selection requirements.” (Bryant, What Size Furnace Do I Need?, read 2026-11-12). A Manual J load calculation on your house is the accurate method.
Compute Your House's Load
Your ZIP code finds its ASHRAE weather station, and ACCA Manual J computes the heating and cooling loads from your floor area, insulation, windows, air tightness and ducts, with the answers it does not ask listed beside the load.
Frequently Asked Questions
How many BTU to heat 1,500 square feet?
It depends on the house and the climate. On DOE's 2021 code-built reference house at 1,500 sq ft, our Manual J engine computes 9,326 to 35,817 BTU per hour of heating, from zone 1A at MIAMI NHC to zone 8 at FAIRBANKS (zone 4A at NEW YORK KENNEDY: 17,080). Bryant says: "Well-insulated, tightly sealed homes may require less heating capacity than homes with significant heat loss."
What size furnace for 1,500 sq ft?
Size the furnace from the heating load of your house at your design temperature. Carrier says square footage alone should not be used to determine the correct furnace size, and the U.S. Department of Energy says: "Your contractor should use the Air Conditioning Contractors of America (ACCA) Manual J to calculate the proper size of HVAC equipment." The table above is that load for one stated house in each climate zone; the Manual J load calculator runs your own.
Does climate change how many BTU I need for 1,500 sq ft?
Yes. On the same house and floor area, the load runs from 9,326 BTU per hour in zone 1A to 35,817 in zone 8, because Manual J prices heat loss at each site's 99% design temperature.
Other Sizes
500 sq ft
4,804 to 17,494 BTU per hour across the climate zones, by Manual J.
800 sq ft
6,484 to 23,859 BTU per hour across the climate zones, by Manual J.
1,000 sq ft
7,102 to 26,534 BTU per hour across the climate zones, by Manual J.
1,200 sq ft
8,022 to 30,301 BTU per hour across the climate zones, by Manual J.
1,800 sq ft
10,355 to 40,791 BTU per hour across the climate zones, by Manual J.
All Sizes + Climate Table
The Manual J heating load per square foot by climate zone, and the load calculator.