NEC 430.248 & 430.250

Motor Full-Load Current (FLC, Wire & Breaker)

Enter horsepower, voltage and phase and get the circuit: full-load current, the conductor at 125% and the maximum inverse-time breaker at 250%. Use the table value, not the nameplate, to size the branch circuit.

Quick answer: Motor full-load current comes from the NEC tables, not the nameplate. Single-phase (NEC 430.248): a 1 HP motor is 16A at 115V and 8A at 230V; a 5 HP is 28A at 230V. Three-phase squirrel-cage (NEC 430.250's induction-type columns): a 10 HP motor is 14A at 460V; a 50 HP is 65A at 460V. A three-phase synchronous motor reads that table's own synchronous columns, which this page does not use. NEC 430.6(A)(1) requires you to size the branch-circuit conductors and breaker from these table values; the nameplate FLA sizes the separate overload device (430.6(A)(2), 430.32).
Where you left off
Saved in this browser, which can get cleared. The app keeps 10x the readings.Saved in this app.
Intry Pro keeps your saved readings on every device. See Intry Pro ›

Enter the motor's horsepower, not its nameplate amps. NEC 430.6(A)(1) sizes the branch circuit from the table full-load current; the nameplate current sizes the separate running overload device (430.6(A)(2), 430.32).

10 HP, 460V, three-phase
#14 Cu / 35A
conductor and maximum inverse-time breaker

#14 copper holds on the 75°C column only for a motor marked design letter B, C or D (NEC 110.14(C)(1)(a)(4)) or equipment listed and identified for 75°C conductors (110.14(C)(1)(a)(3)), with the breaker and controller terminals rated 75°C too; otherwise the 60°C column applies and it takes #12 copper.

Table full-load current
NEC Table 430.250
14 A
Conductor sizing ampacity
NEC 430.22, 125% of FLC
17.5 A
Minimum copper conductor
75C column, NEC Table 310.16, 110.14(C)(1)(a)
#14
Maximum inverse-time breaker
NEC Table 430.52(C)(1) and 430.52(C)(1)(a), 250% of FLC
35 A

The 35A breaker is deliberately larger than the #14 conductor's ampacity so the motor can draw its starting current without tripping. That is code-correct: NEC 240.4(G) exempts motor branch-circuit conductors from the small-conductor limits of 240.4(D), and the running overload device (430.32), not the branch breaker, is what protects the conductor from overload.

This is the largest standard breaker that Table 430.52(C)(1) and 430.52(C)(1)(a) permit for a single motor on this branch circuit. NEC 430.52(C)(1)(b) permits a higher standard rating only where this one is not sufficient for the motor's starting current, and never above 400 percent of the table FLC. A lower maximum applies where the motor controller's overload relay table or the equipment's marking sets one (NEC 430.52(C)(2)). Long runs may need a larger conductor for voltage drop, which this calculation does not include; a wire-type ground goes up in proportion with it (NEC 250.122(B)). Your AHJ and local amendments govern the install.

What this sizes. One single-phase motor or three-phase squirrel-cage motor in continuous duty, alone on its branch circuit, with copper conductors: the ordinary case, on rows of NEC Table 430.52(C)(1) that give this 250%. A three-phase synchronous motor's full-load current is in Table 430.250's own synchronous columns, which this tool does not read, so no answer here applies to one. A wound-rotor or DC motor takes a lower branch-circuit percentage from a different row of Table 430.52(C)(1), so the breaker here does not apply to one, and a motor in short-time, intermittent, periodic or varying duty takes its conductor under 430.22(E), so the conductor here does not apply to one.

Check voltage drop on the run →Check the conduit fill for these conductors →

Carries 3 conductors into the fill calculator. This tool sizes no equipment grounding conductor, so add the one you pull there: Chapter 9 Note 3 counts it.

Size a motor circuit by horsepower →
Show the math
  1. GIVENMotor: 10 HP, 460 V, three-phase
  2. TABLENEC Table 430.250: 14 A full-load current, read from the table rather than the nameplate (NEC 430.6(A)(1)). Low-speed, high-torque, canned-pump and multispeed motors, and motors larger than the tables, use the nameplate (430.6(A)(2)); 430.6(A)(1) Exceptions No. 2 and 3 send some fan, blower and listed appliance motors to the equipment nameplateNEC Table 430.250, NEC 430.6(A)(1)
  3. MATH14 A × 1.25 = 17.5 A (NEC 430.22)NEC 430.22
  4. TABLESmallest copper conductor carrying 17.5 A in the 75°C column of Table 310.16: #14. #14 copper holds on the 75°C column only for a motor marked design letter B, C or D (NEC 110.14(C)(1)(a)(4)) or equipment listed and identified for 75°C conductors (110.14(C)(1)(a)(3)), with the breaker and controller terminals rated 75°C too; otherwise the 60°C column applies and it takes #12 copper.NEC Table 310.16, 110.14(C)(1)(a)
  5. MATH14 A × 2.50 = 35 A (Table 430.52(C)(1), inverse-time breaker)NEC Table 430.52(C)(1)
  6. ROUNDThat is already a standard rating in Table 240.6(A), so the maximum is 35 ANEC 430.52(C)(1)(a), Table 240.6(A)
  7. RESULTMinimum copper conductor: #14 at 75°CNEC 430.22, Table 310.16
  8. RESULTMaximum inverse-time breaker: 35 ANEC 430.52(C)(1)(a)

The 250% above is the percentage Table 430.52(C)(1) gives an inverse-time breaker on a single-phase, squirrel-cage or synchronous motor. A wound-rotor or DC motor takes a different percentage, and a three-phase synchronous motor reads its current from Table 430.250's own synchronous columns, so this working does not carry across to them.

Where this number comes fromIntry Verified
Calculated from
NEC Table 430.250, NEC 430.6(A)(1), 430.22, Table 310.16, 110.14(C)(1)(a), Table 430.52(C)(1), 430.52(C)(1)(a), 240.6(A). Full-load current read from NEC 2023 Table 430.250 (three-phase) or Table 430.248 (single-phase) per 430.6(A)(1); conductor computed at 125 percent of that current against Table 310.16 per 430.22, at the 60C column and, where 110.14(C)(1)(a) permits it (a motor marked design letter B, C or D, or equipment listed for it), the 75C column; maximum inverse-time breaker computed at 250 percent against the standard ratings in 240.6(A) per Table 430.52(C)(1) and 430.52(C)(1)(a). See the full receipt ↓
Run with
  • PhaseThree-phase
  • Voltage460 V
  • Horsepower10 HP
  • Table FLC14 A
  • Conductor materialCopper
  • Terminals75°C (design B, C or D motor or 75°C-listed equipment)
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC Table 430.250 and 430.248 full-load currents and the Article 430 branch-circuit rules. This is our own deterministic gate, not a third-party audit.
Final say
Your AHJ has final say. The table current sizes the branch circuit; your motor's nameplate sizes the running overload device (430.32), which this tool does not size. Wound-rotor and DC motors take a different percentage from Table 430.52(C)(1) and are out of scope; so is a three-phase synchronous motor, whose current is in Table 430.250's own synchronous columns, and a motor in other than continuous duty (430.22(E)).
What Intry Verified means

Intry Verified · NEC 2023 · Build 525536D · 2026-11-13

10 HP 460V#14 at 75°C, #12 at 60°C / 35A

How to Size a Motor Branch Circuit

A motor circuit is sized differently from an ordinary load, and it turns on one rule that trips people up: you size the circuit from the NEC table full-load current, not the motor nameplate. NEC 430.6(A)(1) says the values in Tables 430.247 through 430.250 determine the conductor ampacity, the disconnect, and the branch-circuit short-circuit and ground-fault protective device. The nameplate full-load amps (FLA) size the separate running-overload device (430.6(A)(2) and 430.32), and, under 430.6(A)(2), the conductors and protection of low-speed, high-torque, canned-pump and multispeed motors.

From the table FLC, the branch circuit has two independent parts. The conductor is sized so its ampacity is at least 125% of the FLC (NEC 430.22). The short-circuit/ground-fault breaker may be sized up to 250% of the FLC for a standard inverse-time breaker (NEC 430.52 and Table 430.52(C)(1)), rounded up to the next standard size where that value is not a standard rating (430.52(C)(1)(a)). That is why a motor circuit legally shows a small conductor under a large breaker: the conductor is protected from sustained overload by the separate overload device (430.32), and motor conductors are exempt from the 240.4(D) small-conductor limit via 240.4(G). The tables below apply these rules to the table FLC.

Motor Branch-Circuit Sizing (Conductor & Breaker)

Single-phase 230V motors in continuous duty: conductor at 125% FLC and the maximum inverse-time breaker at 250% FLC (NEC 430.22 and 430.52). The 60°C column is the rule on these circuits (NEC 110.14(C)(1)(a)); the 75°C size holds only for a motor nameplate marked design letter B, C or D, or equipment listed and identified for 75°C conductors.

Swipe the table sideways to see the rest of its columns. →

HPFLC (A)Min. conductor, 60°C Cu75°C Cu, design B, C or D motor or 75°C-listed equipmentMax. inverse-time breaker
1/62.2#14#1410A
1/42.9#14#1410A
1/33.6#14#1410A
1/24.9#14#1415A
3/46.9#14#1420A
18#14#1420A
1-1/210#14#1425A
212#14#1430A
317#10#1245A
528#8#1070A
7-1/240#6#8100A
1050#4#6125A

Three-phase 460V squirrel-cage motors in continuous duty (a three-phase synchronous motor reads Table 430.250's own synchronous columns, which these rows do not use): conductor at 125% FLC and the maximum inverse-time breaker at 250% FLC (NEC 430.22 and 430.52). At 100 A or less and on 14 through 1 AWG terminations the 75°C size holds only for a motor marked design letter B, C or D, or equipment listed and identified for 75°C conductors (NEC 110.14(C)(1)(a)); otherwise use the 60°C size.

Swipe the table sideways to see the rest of its columns. →

HPFLC (A)Min. conductor, 60°C Cu75°C Cu, design B, C or D motor or 75°C-listed equipmentMax. inverse-time breaker
1/21.1#14#1410A
3/41.6#14#1410A
12.1#14#1410A
1-1/23#14#1410A
23.4#14#1410A
34.8#14#1415A
57.6#14#1420A
7-1/211#14#1430A
1014#12#1435A
1521#10#1060A
2027#8#1070A
2534#6#890A
3040#6#8100A
4052#4#6150A
5065#3#4175A
6077#1#3200A
75961/0#1250A
100124n/a2/0350A
125156n/a3/0400A
150180n/a4/0450A
200240n/a350 kcmil600A

Each conductor is the smallest copper wire whose Table 310.16 ampacity meets 125% of the FLC. On a circuit rated 100 A or less, or on terminations marked for 14 through 1 AWG, NEC 110.14(C)(1)(a) makes the 60°C size the rule; the 75°C size needs a motor marked design letter B, C or D, or equipment listed and identified for 75°C conductors, with the breaker and controller terminals rated 75°C too. NM-B cable is limited to the 60°C column. “n/a” marks a circuit over 100 A on larger conductors, where 110.14(C)(1)(b) makes 75°C the rule. The breaker shown is the maximum permitted short-circuit/ground-fault device; a smaller standard size is used when the motor will start on it. Overload protection is separate and sized from the nameplate (430.32).


Worked Example

10 HP, 460V, three-phase squirrel-cage motor

Table 430.250 FLC = 14A. Conductor = 14 × 1.25 = 17.5A. Breaker = 14 × 2.5 = 35A.

The conductor needs 17.5A of ampacity, so #14 copper (20A at 75°C) works. #14 copper holds on the 75°C column only for a motor marked design letter B, C or D (NEC 110.14(C)(1)(a)(4)) or equipment listed and identified for 75°C conductors (110.14(C)(1)(a)(3)), with the breaker and controller terminals rated 75°C too; otherwise the 60°C column applies and it takes #12 copper. The maximum inverse-time breaker is 35A, which is a standard size. So the branch circuit is #14 copper (design B, C or D motor or 75°C-listed equipment; #12 Cu at 60°C) on a 35A breaker, with the overload device set from the nameplate (about 125% of nameplate FLA). If you had (wrongly) sized from a nameplate reading of, say, 13A, you would get a different, non-code result. The table value governs.


Frequently Asked Questions

What is the full-load current of a 1 HP motor?

Per NEC Table 430.248, a single-phase 1 HP motor is 16A at 115V and 8A at 230V. Per NEC Table 430.250's induction-type columns, a three-phase 1 HP squirrel-cage motor is 4.2A at 230V, 2.1A at 460V, and 1.7A at 575V. Use these table values, not the nameplate amps, to size the branch-circuit conductors and the short-circuit/ground-fault breaker (NEC 430.6(A)(1)).

Do I use the nameplate amps or the NEC table to size a motor circuit?

Use the NEC table. NEC 430.6(A)(1) requires the values in Tables 430.247 through 430.250 to size the branch-circuit conductors, the ampacity, the disconnect, and the short-circuit/ground-fault protective device. The motor nameplate full-load amps (FLA) size the separate running-overload device, per 430.6(A)(2) and 430.32; 430.6(A)(2) also sends the nameplate current to the conductors and protection of low-speed, high-torque, canned-pump and multispeed motors.

What size wire and breaker for a 10 HP three-phase motor at 460V?

A 10 HP, 460V, three-phase squirrel-cage motor has a table full-load current of 14A (NEC Table 430.250). The branch-circuit conductor is sized at 125% of FLC = 17.5A. #14 copper holds on the 75°C column only for a motor marked design letter B, C or D (NEC 110.14(C)(1)(a)(4)) or equipment listed and identified for 75°C conductors (110.14(C)(1)(a)(3)), with the breaker and controller terminals rated 75°C too; otherwise the 60°C column applies and it takes #12 copper. The maximum inverse-time breaker is 250% of FLC = 35A (NEC 430.52, Table 430.52(C)(1)). So #14 copper (design B, C or D motor or 75°C-listed equipment; #12 Cu at 60°C) on a 35A breaker, with the overload device set from the nameplate. A small conductor under a larger breaker is code-correct here because motor conductors are exempt from the 240.4(D) small-conductor rule (240.4(G)); the overload device protects the wire, not the breaker.

Why is the motor breaker so much bigger than the wire ampacity?

A motor draws several times its running current for a moment at startup (locked-rotor / inrush). NEC 430.52 lets the branch-circuit short-circuit/ground-fault breaker be sized up to 250% of the full-load current (inverse-time type) so it does not trip on that inrush. The conductor is only sized to 125% of FLC (430.22) and is protected against sustained overload by the separate overload device (430.32), not by the branch breaker. That is why you see a small conductor under a large breaker on a motor circuit, and why motor conductors are exempt from the 240.4(D) small-conductor limit via 240.4(G).

What is the full-load current of a 5 HP single-phase motor at 230V?

Per NEC Table 430.248, a 5 HP single-phase motor at 230V has a full-load current of 28A (56A at 115V). Sized to 125%, the conductor ampacity is 35A and the maximum inverse-time breaker is 70A per NEC 430.52. #8 copper on the 60°C column, which NEC 110.14(C)(1)(a) makes the rule for this circuit; #10 copper on the 75°C column only where the motor nameplate is marked design letter B, C or D (110.14(C)(1)(a)(4)) or the equipment is listed and identified for 75°C conductors (110.14(C)(1)(a)(3)), with the breaker and controller terminals rated 75°C too.

Are the NEC motor FLC tables the same in the 2017, 2020, and 2023 editions?

Yes. The full-load current values in NEC Tables 430.248 (single-phase) and 430.250 (three-phase) have not changed across the 2017, 2020, and 2023 editions of NFPA 70. The section numbers for the sizing rules (430.6, 430.22, 430.32, 430.52) are also unchanged.

How do I size motor overload protection?

Overload protection is sized from the motor nameplate full-load amps (FLA), not the NEC table. Per NEC 430.32(A)(1), a continuous-duty motor over 1 HP uses 125% of nameplate FLA when the motor has a marked service factor of 1.15 or higher, or a marked temperature rise of 40°C or less; otherwise 115%. This overload device, separate from the branch-circuit breaker, is what protects the motor and conductor from a sustained overload.


Related Calculators & Charts

Have the FLC. Now size the whole circuit.

The wire size calculator sizes any conductor for a load and picks the protecting breaker, and the well-pump and air-compressor pages walk a real motor branch circuit end to end.