NEC 310.16 Feeder Sizing

What Size Wire for a 200 Amp Sub-Panel?

The feeder conductor, equipment ground, breaker, conduit, and voltage drop for a 200 amp sub-panel, plus the 4-wire feeder and neutral-isolation rules that pass inspection. Pick your material and run length below.

Quick answer: a 200 A sub-panel feeder is 3/0 copper (or 250 aluminum) with a 6 Cu equipment ground on a 200 A breaker, sized from NEC Table 310.16 and Table 250.122. Run it as a 4-wire feeder and keep the neutral isolated from ground in the sub-panel.
Loading planner...

Sub-Panel Wire Size Chart (Copper & Aluminum)

Feeder conductor (Table 310.16, 75°C), equipment ground (Table 250.122), and breaker (240.6) per sub-panel rating. Copper and aluminum.
Sub-panelCopper feederCu groundAluminum feederAl groundBreaker
60 A6 Cu104 Al860 A
100 A3 Cu81 Al6100 A
125 A1 Cu62/0 Al4125 A
150 A1/0 Cu63/0 Al4150 A
200 A3/0 Cu6250 Al4200 A

Conductors at the 75°C column of Table 310.16 (feeder lugs are 75°C-rated, NEC 110.14(C)). Aluminum is one to two sizes larger than copper for the same rating. The equipment grounding conductor is sized from Table 250.122 by the breaker, not by the feeder size.


How to Wire a 200 Amp Sub-Panel: Isolate the Neutral

The single most-failed sub-panel detail is the neutral bond. A sub-panel is on the load side of the service, so the neutral and ground are separated here and bonded only back at the main panel.

Run a 4-wire feeder NEC 215.6

A sub-panel feeder carries four conductors: two ungrounded (hot) legs, a grounded (neutral) conductor, and a separate equipment grounding conductor. The neutral and the ground are separate conductors all the way to the sub-panel - never a shared 3-wire feed.

Isolate the neutral bar from the ground bar NEC 408.40, 250.24

In the sub-panel the grounded (neutral) bus and the equipment-ground bus must be kept separate. Remove the main bonding jumper - the green bonding screw or strap that ties the neutral bar to the metal can. Bonding neutral to ground here would put normal neutral current onto the ground path and every metal enclosure downstream.

Bond neutral to ground at the service only NEC 250.24

The one place the neutral and ground are bonded is the service disconnect (the main panel), via the main bonding jumper. The grounded conductor cannot be reconnected to ground on the load side of that service disconnect, which is exactly what a sub-panel is.

Detached building: add a grounding electrode NEC 250.32

A sub-panel in a separate building or structure still gets a 4-wire feeder with the neutral isolated, plus its own grounding electrode (a ground rod or rods) connected to the sub-panel's ground bar. New feeders to a separate structure must include an equipment grounding conductor - the old 3-wire feed is allowed only on existing installations.


Frequently Asked Questions

What size wire do I need for a 200 amp sub-panel?

A 200 amp sub-panel feeder uses 3/0 copper or 250 aluminum ungrounded (hot) and neutral conductors, sized from NEC Table 310.16 at the 75°C column. Run a 6 copper (or 4 aluminum) equipment grounding conductor with them per Table 250.122, protected by a 200 amp feeder breaker (NEC 240.6). This is a 4-wire feeder: two hots, a neutral, and a separate ground.

Is #4 copper enough for a 100 amp sub-panel?

Only when the feeder carries the entire dwelling load. NEC 310.12 permits a reduced conductor (#4 copper at 100 A) for the service or the main feeder that supplies an entire one-family dwelling. A sub-panel that feeds only part of the home does not qualify, so it is sized from Table 310.16 instead - #3 copper for 100 A on 75°C-marked terminations (at 60°C or on NM-B cable, #1 AWG). Using the 310.12 number on a partial-load sub-panel is the most common sizing mistake.

Do you bond the neutral and ground in a 200 amp sub-panel?

No. The neutral (grounded) bar and the ground (equipment grounding) bar must be kept separate in any sub-panel. Remove the main bonding jumper - the green bonding screw or strap. The neutral-to-ground bond is made only at the service disconnect (NEC 250.24, 408.40). Bonding them in the sub-panel puts normal neutral current on the ground path and every metal enclosure downstream, which is a shock hazard and a failed inspection.

What size equipment ground for a 200 amp sub-panel?

6 copper or 4 aluminum. The equipment grounding conductor is sized from NEC Table 250.122 by the feeder breaker rating (200 A), not from the size of the feeder conductors and not from Table 250.66 (that is the grounding electrode conductor, a service conductor). If the feeder is upsized for voltage drop, the EGC is upsized proportionally per 250.122(B).

Does a detached-garage sub-panel need a ground rod?

Yes. A sub-panel in a separate building or structure gets its own grounding electrode (a ground rod or rods, or other electrode present) connected to the sub-panel ground bar, plus the 4-wire feeder with the neutral still isolated (NEC 250.32). New feeders to a separate structure must include an equipment grounding conductor; the old 3-wire feed is allowed only on existing installations.


Other Sub-Panel Sizes

Feeder sized. Will the main panel carry it?

A 200 A sub-panel adds load to the service. Check whether the main panel has the headroom before you tap it.