Does outdoor HVAC need GFCI protection? NEC 210.8(F), by jurisdiction

The NEC’s exception for listed HVAC equipment expires 2026-09-01 by its own printed terms. That is a fact about the NEC, and it is not a fact about your job. States rewrite this section, and in 6 of the ones we have read the sunset never arrives at all. They do not get there the same way: some delete 210.8(F) from their adoption, some write their own exception that never carried an expiry, and some reproduce the NEC’s and leave the expiry sentence out. This tool answers where we have read the jurisdiction’s own primary documents, and refuses everywhere else, including for 13 jurisdictions we researched and still could not answer for.

6of 51
answerable

We can answer for 6 of 51 jurisdictions. We researched all 51 and verified 19 against the state’s own documents. Those are deliberately separate numbers. Each of those 19 comes from the issuing agency’s own document, fetched 2026-08-01; the NEC text itself we read from the printed book. Reading a state’s rules does not always produce an honest answer, and for 13 of them it did not, so those refuse with a stated reason instead. The remaining 32 were researched too, and what that research produced was leads rather than readings. We do not publish leads here: checked against the states we did verify, close to a third of them were wrong, and two would have taken required GFCI protection off a live circuit. So those rows say what our weaker compiled source claims and nothing more. We are not adding a national default to raise any of these numbers, because a national default is precisely the error this page exists to avoid.

Loading…

Same equipment, same day, opposite answers

A 30 A, 120 V outdoor circuit feeding listed HVAC equipment at a dwelling, hardwired to a disconnect, energised 2026-09-15, which is after the sunset. These are the 6 jurisdictions where we can answer that question:

One circuit, every jurisdiction we can answer for. Scrolls sideways.
JurisdictionVerdictControlling rule
GeorgiaNOT REQUIREDNEC 210.8(F) Exception No. 2 as amended by Georgia (Georgia State Amendments to the National Electrical Code (2023 Edition), Georgia Department of Community Affairs, revised January 1, 2026)
OhioNOT REQUIREDNEC 210.8(F) Exception No. 2 as amended by Ohio (Ohio Administrative Code 4101:1-35-01(C) (Ohio Building Code referenced standards, effective October 15, 2025), which incorporates "70-23 National Electrical Code (except that section 210.8(F) Exception No. 2 does not expire)"; corroborated by OAC 4101:8-34-01 (Residential Code of Ohio, Section 3401), effective April 15, 2024)
New MexicoNOT REQUIREDNEC 210.8(F) Exception No. 2 as amended by New Mexico (14.10.4.12 NMAC, Chapter 2 Wiring and Protection, A(1) (2020 New Mexico Electrical Code, effective March 28, 2023))
LouisianaNOT REQUIREDNEC 210.8(F) Exception No. 2 as amended by Louisiana (LAC 17:I.115 (Louisiana State Uniform Construction Code, NEC 2020 amendments), authority now R.S. 37:3727 through 37:3750 per Act 881 of 2026)
South DakotaNOT REQUIREDNEC 210.8(F) deleted by South Dakota (ARSD 20:44:14:01(11)(a) (South Dakota Electrical Commission, general definitions), effective November 12, 2024)
ArkansasNOT REQUIREDNEC 210.8(F) deleted by Arkansas (17 CAR Section 210-601(b)(2) (Arkansas Board of Electrical Examiners, adoption of the National Electrical Code), formerly numbered Rule 010.13-008)

In Arkansas, Georgia, Louisiana, New Mexico, Ohio and South Dakota the sunset never arrives, and they do not all get there the same way. The mechanism column below is not decoration: a state that deletes 210.8(F) from its adoption, a state that writes its own exception, and a state that disapplies the NEC’s expiry in words are three different legal objects, and the one under you is the one your inspector will read.

Every jurisdiction we verified against its own documents, and what it actually does

Four outcomes appear here and they are not degrees of the same thing. Two are answers. One is a refusal that follows from the state’s own rules rather than from our ignorance. We list the refusals beside the answers on purpose, because which of the two you are looking at is the most important thing on this page.

Every jurisdiction verified against its own primary document. Scrolls sideways.
JurisdictionOutcomeInstrumentWhat the state didText, verbatim
AlabamaWe will not answerstate code listingAlabama has two building codes and neither one puts NEC 210.8(F) over a house. The State Building Code, which is the instrument that adopts the 2020 NEC, applies only to four things, in its own words at Ala. Admin. Code r. 355-12-1-.04: buildings erected or acquired by or on behalf of the State or any of its agencies or instrumentalities; schoolhouses, meaning public school buildings plus any private building where 25 or more persons are congregated regularly for instruction; hotels of 15 or more bedrooms; and moving picture theaters. A one- or two-family dwelling is none of those. Dwellings instead fall to the Alabama Residential Building Code under Code of Ala. Section 34-14A-12, which is based on a published edition of the INTERNATIONAL RESIDENTIAL CODE, whose electrical provisions are the E3902 series rather than NEC 210.8(F), and which is enforced only by local jurisdictions that run permitting and inspection programs. We hold no IRC primary, and we could not confirm which IRC edition Alabama dwellings are on today, so we will not answer across code books. Ask the local jurisdiction that issues your permit which residential code edition it enforcesno single quote settles it
AlaskaWe will not answerstate code listingAlaska's state electrical code does not bind a detached one- or two-family dwelling, so the September 2026 question does not reach your job through it. AS 18.60.640(b) says these standards "are the recommended minimum standards for all new structures in the state", and the mandatory inspection power is narrower still: AS 18.60.600(a)(2) reaches a "place of employment or public structure", and AS 18.60.660(4) defines public structures as hotels, "resident housing with more than one rental unit", restaurants, taverns, lodging houses, children's homes, auditoriums, town halls and structures used for public assembly. Alaska's own Department of Labor states the practice the same way: commercial structures and dwellings of three-plex and above are subject to inspection. Separately, we were unable to read an official Alaska source for the current text of 8 AAC 70.025, because every state and mirror host either refused us or failed, and we will not publish a verdict off a transcription we could not check. Note that AS 18.60.590(b) preserves municipal authority to be MORE stringent, so a city like Anchorage may bind your dwelling under its own ordinance. Ask your municipalityno single quote settles it
ArkansasNot required17 CAR Section 210-601(b)(2) (Arkansas Board of Electrical Examiners, adoption of the National Electrical Code), formerly numbered Rule 010.13-008the state deletes 210.8(F) entirely, so the section imposes nothing thereThe provisions of Section 2108F of the 2020 National Electrical Code, dealing with GFCI requirements for Heating, Ventilation, and Air Conditioning are excluded from the adoption of the 2020 National Electrical Code.
ConnecticutWe will not answer2022 Connecticut State Building Code (including Errata #1), Amendments to the 2020 NFPA 70 National Electrical Code, printed page 107an exception survives but it is NARROWER than the NEC's: mini-split-type heating/ventilating/air-conditioning (HVAC) equipment and other HVAC units employing power conversion equipment as a means to control compressor speed. A conventional single-speed condenser is NOT covered and never wasException No. 2: Ground-fault circuit-interrupter protection shall not be required for mini-split-type heating/ventilating/air-conditioning (HVAC) equipment and other HVAC units employing power conversion equipment as a means to control compressor speed.
GeorgiaNot requiredGeorgia State Amendments to the National Electrical Code (2023 Edition), Georgia Department of Community Affairs, revised January 1, 2026by omission: the state reproduces the exception and leaves the expiry sentence outException No. 2: GFCI protection shall not be required for listed HVAC equipment.
HawaiiWe will not answerstate code listingHawaii sets the electrical code county by county, and most of it predates the rule you are asking about. 210.8(F) entered the NEC in the 2020 edition. Honolulu is on the 2017 NEC by Revised Ordinances Section 17-1.1, Hawaii County is on the 2017 NEC, and MAUI IS ON THE 2008 NEC by Ordinance 3726, effective 2010-06-06. In all three, 210.8(F) does not exist at all, so there is no exception to expire and no September 2026 event. We could not read Kauai's electrical adoption (403 twice), so we do not characterise it. At the state layer the position is genuinely undecidable rather than merely unread: the State Building Code Council's own listing says the 2020 NEC adopted 2022-03-15, while HRS 107-24(c) automatically adopts a code the Council fails to act on within two years, and the Governor's Twentieth Proclamation of July 2026 recites that automatic adoption has in fact occurred while suspending the Council's power to adopt. Those cannot all be resolved from the documents. One thing worth knowing about the state's own page: it labels its electrical link "2018 NFPA 70", an edition that has never existed, and the document behind it is the 2020 code. Ask your county building department which NEC edition it enforcesno single quote settles it
LouisianaNot requiredLAC 17:I.115 (Louisiana State Uniform Construction Code, NEC 2020 amendments), authority now R.S. 37:3727 through 37:3750 per Act 881 of 2026the state wrote its own HVAC exception, which never carried an expiry, so it does not depend on the NEC's exception reaching the state at allAmend Article 210.8, Ground-Fault Circuit-Interrupter Protection For Personnel. Amend Item (F) Outdoor Outlets Amend Exception Adopt Item (2) Ground-fault circuit-interrupter protection shall not be required on HVAC equipment.
MarylandWe will not answerstate code listingMaryland has no binding statewide electrical code for dwellings, so there is no single Maryland answer to give you. Md. Public Safety Section 12-603 says each electrical installation shall conform to either the National Electrical Code or the electrical code and amendments adopted by the COUNTY where the work is done, and it names no edition at all. The statewide building code is mandatory but deliberately hands electrical off: COMAR 09.12.51.04 writes it out of scope twice, once for IBC Chapter 27 and once for IRC chapters 34 through 43, each time pointing at the local electrical code. The state instrument that DOES amend 210.8(F), the Model Performance Code at COMAR 09.12.50, says at .02B(1) that it may not be binding upon any subdivision unless that subdivision adopts it. Here is the part worth carrying to your county: where the model code HAS been adopted, Maryland incorporates the 2020 NEC with its own words added to the 210.8(F) exception, "and heating, air-conditioning, and refrigeration equipment that serve the dwelling", and that carve-out carries NO expiry, so a county on the model code likely has no September 2026 cliff at all. Ask your county which electrical code and which edition it has adopted, and whether it took the Maryland Model Performance Code with itno single quote settles it
MissouriWe will not answerstate code listingMissouri has no statewide electrical code reaching a site-built one- or two-family dwelling, so there is no statewide answer to give you. RSMo 64.170 EMPOWERS first- and second-class counties to adopt building regulations rather than requiring it, and counties without a code predating August 28, 2001 need voter approval. RSMo 324.920 is statewide electrical contractor LICENSING, and the only place the National Electrical Code appears in it is as the basis for a written examination, which is exam content and not a construction standard. A full-text search of Missouri's own revisor site does return the National Electrical Code in several statutes, so the absence here is evidence rather than a failed search, and not one of those provisions adopts it as a building code for dwellings. The one statewide instrument that DOES adopt the NEC, 20 CSR 4240-123.080, covers modular units only: it applies to "modular units which entered the first stage of production after July 1, 1976", a modular unit being a TRANSPORTABLE factory-built building unit under RSMo 700.010. For those units Missouri adopts NFPA 70-2020 and states that "the referenced codes do not include any later amendments or additions", in a rule amended April 2024 and effective November 30 2024, which is well after the amendment that created the HVAC exception, so those units never received it. None of that reaches a house framed on site. Ask your city or county which electrical code it has adoptedno single quote settles it
MontanaWe will not answerstate code listingMontana is a case where the practical answer is probably clear and our evidence is not good enough to publish it. Two things are worth knowing regardless. First, Montana is on the 2020 NEC, not the 2023, whatever a tracker tells you: the state's own current-codes page and its own rule both say 2020, and the rule was amended as recently as September 2024. Second, Montana never adopted the amendment that created the listed-HVAC exception, so the exception is not in Montana's code at all. What exists instead is a September 2022 enforcement memo from the Building Codes Program allowing installers to use the exception, and that memo quotes the expiry itself: it lets you "utilize this exception", and this exception expires September 1, 2026 by the very words the memo reproduces. So the relief lapses on that date rather than surviving it. We are still refusing, because the only copy of Montana's adopting rule we have been able to read is a third-party reproduction (the state's own rules site returns 403 to us), and if that rule turns out to pick up tentative interim amendments then this whole reading changes. Ask the Montana Building Codes Program directly, and ask specifically whether the 2022 HVAC memo is still in force after September 1, 2026no single quote settles it
New MexicoNot required14.10.4.12 NMAC, Chapter 2 Wiring and Protection, A(1) (2020 New Mexico Electrical Code, effective March 28, 2023)the state wrote its own HVAC exception, which never carried an expiry, so it does not depend on the NEC's exception reaching the state at allSection 210.8 (F) Outdoor outlets. See this section of the NEC and add the following exception: Exception No. 2 GFCI protection shall not be required for listed HVAC equipment.
North CarolinaWe will not answerstate code listingwe have read North Carolina's rules and they do not produce a clean answer. The 2023 State Electrical Code, which appends only a submersible-well-pump exception and leaves the NEC sunset intact, is on INDEFINITE DELAY under Session Law 2025-2 (House Bill 47). What is actually in force is the 2020 State Electrical Code, effective November 1, 2021, and it amends 210.8(F) to read "Deleted" while also stating that it does not apply to one- and two-family dwellings. So for most dwelling work the governing document is the NC Residential Code, which we have not been able to read. Ask the NC Office of State Fire Marshal which document governs your job before relying on any national article about the September 2026 sunsetno single quote settles it
OhioNot requiredOhio Administrative Code 4101:1-35-01(C) (Ohio Building Code referenced standards, effective October 15, 2025), which incorporates "70-23 National Electrical Code (except that section 210.8(F) Exception No. 2 does not expire)"; corroborated by OAC 4101:8-34-01 (Residential Code of Ohio, Section 3401), effective April 15, 2024stated explicitly: the state's own instrument disapplies the NEC's expiry in words70-23 National Electrical Code (except that section 210.8(F) Exception No. 2 does not expire)
OregonWe will not answerstate code listingOregon rewrote 210.8(F) rather than deleting it, and the rewrite cuts both ways at once. The important part first: Oregon STRUCK the listed-HVAC exception, and the sentence "This exception shall expire September 1, 2026" along with it, when it adopted the 2023 Oregon Electrical Specialty Code effective October 1, 2023. So there is no HVAC exception in Oregon, there has not been one under this code, and NOTHING happens there on September 1, 2026. If you have read a national article about the exception expiring, it is about a provision Oregon does not have. What we will not do is tell you whether your particular outlet is covered, because Oregon also rewrote the scope: it struck "For dwellings" so the section reaches every occupancy, and it replaced "outlets" with "general-purpose receptacles" so it no longer reaches hardwired equipment. An outdoor general-purpose receptacle needs GFCI protection in Oregon unconditionally, with no exception of any kind. A hardwired condenser feed is outside the rewritten section, which is a narrowing and not a clearance. Oregon defines "general-purpose receptacle" nowhere: the phrase occurs exactly once in all eighteen pages of Table 1-E, in this amendment. Read OAR 918-305-0105 Table 1-E page 4 and ask the Building Codes Division which side your installation is onno single quote settles it
South CarolinaWe will not answerS.C. Code Ann. Regs. 8-1104 (Building Codes Council, Article 11, National Electrical Code 2020 modifications)the state deletes 210.8(F) entirely, so the section imposes nothing there8-1104. NEC Article 210.8(F) Outdoor Outlets. This article does not apply in this State.
South DakotaNot requiredARSD 20:44:14:01(11)(a) (South Dakota Electrical Commission, general definitions), effective November 12, 2024the state deletes 210.8(F) entirely, so the section imposes nothing there"National Electrical Code," the code published by the National Fire Protection Association (2023 edition, including tentative interim amendments 23-1 through 23-15) with the following exceptions: (a) Section 210.8(F);
UtahWe will not answerUtah Code 15A-3-601(7) (NEC amendments) and, separately, 15A-3-206(21) (IRC amendments), both effective July 1, 2025the state deletes 210.8(F) entirely, so the section imposes nothing there15A-3-601(7): NEC, Section 210.8(F), is deleted.
VirginiaWe will not answer13VAC5-63-300(B) (Virginia Construction Code, Chapter 27 Electrical, amending the IBC) and, separately, 13VAC5-63-210(R) VCC Section 310.8 item 116 (amending the IRC)the state deletes 210.8(F) entirely, so the section imposes nothing thereAdd Section 2701.1.1 to the IBC ... The following changes shall be made to NFPA 70: ... 3. Delete Section 210.8(F) in its entirety.
West VirginiaWe will not answerstate code listingWest Virginia's State Building Code binds only where a local jurisdiction has adopted it. W. Va. Code Section 7-1-3n says the state building code "shall not apply to or affect any territory within the boundaries of any municipal corporation which has not adopted the state building code", and 87CSR4 Section 87-4-7.1 requires each adopting jurisdiction to notify the Fire Commission in writing. So there is no statewide answer to give you. What we can tell you about the state rule, if your jurisdiction has adopted it: West Virginia is on the 2020 NEC, effective 2022-08-01, and its adoption contains no tentative-interim-amendment language of any kind, so the NEC's own listed-HVAC exception never reached it. West Virginia did write an HVAC exception of its own, and it has already expired: 87-4-4.1.m.1 excepted mini-split and power-conversion HVAC "until January 1, 2023". GFCI protection has been required on outdoor HVAC there since that date, and nothing further happens on September 1, 2026. A 2023 NEC package was AGENCY-APPROVED on 2026-07-31 and filed with the Legislative Rule-Making Review Committee, which cannot put it in force and which carries no effective date. Ask whether your city or county has adopted the state building code, and which versionno single quote settles it

13 jurisdictions we researched and still will not answer

Reading a state’s amendment is not the same as being able to answer for it. This is the group that proves it, and it is the reason we do not trust a national article on this subject, including our own first draft of this page. Every entry below cost real work and ends in a refusal. That is the tool functioning, not failing.

01researched
refusing

Alabama

We refuse because Alabama has two building codes and neither one puts NEC 210.8(F) over a house. The State Building Code, which is the instrument that adopts the 2020 NEC, applies only to four things, in its own words at Ala. Admin. Code r. 355-12-1-.04: buildings erected or acquired by or on behalf of the State or any of its agencies or instrumentalities; schoolhouses, meaning public school buildings plus any private building where 25 or more persons are congregated regularly for instruction; hotels of 15 or more bedrooms; and moving picture theaters. A one- or two-family dwelling is none of those. Dwellings instead fall to the Alabama Residential Building Code under Code of Ala. Section 34-14A-12, which is based on a published edition of the INTERNATIONAL RESIDENTIAL CODE, whose electrical provisions are the E3902 series rather than NEC 210.8(F), and which is enforced only by local jurisdictions that run permitting and inspection programs. We hold no IRC primary, and we could not confirm which IRC edition Alabama dwellings are on today, so we will not answer across code books. Ask the local jurisdiction that issues your permit which residential code edition it enforces. Source ›

02researched
refusing

Alaska

We refuse because Alaska's state electrical code does not bind a detached one- or two-family dwelling, so the September 2026 question does not reach your job through it. AS 18.60.640(b) says these standards "are the recommended minimum standards for all new structures in the state", and the mandatory inspection power is narrower still: AS 18.60.600(a)(2) reaches a "place of employment or public structure", and AS 18.60.660(4) defines public structures as hotels, "resident housing with more than one rental unit", restaurants, taverns, lodging houses, children's homes, auditoriums, town halls and structures used for public assembly. Alaska's own Department of Labor states the practice the same way: commercial structures and dwellings of three-plex and above are subject to inspection. Separately, we were unable to read an official Alaska source for the current text of 8 AAC 70.025, because every state and mirror host either refused us or failed, and we will not publish a verdict off a transcription we could not check. Note that AS 18.60.590(b) preserves municipal authority to be MORE stringent, so a city like Anchorage may bind your dwelling under its own ordinance. Ask your municipality. Source ›

03researched
refusing

Connecticut

We hold Connecticut’s primaries and still refuse, because an exception survives but it is NARROWER than the NEC's: mini-split-type heating/ventilating/air-conditioning (HVAC) equipment and other HVAC units employing power conversion equipment as a means to control compressor speed. A conventional single-speed condenser is NOT covered and never was. Source ›

04researched
refusing

Hawaii

We refuse because Hawaii sets the electrical code county by county, and most of it predates the rule you are asking about. 210.8(F) entered the NEC in the 2020 edition. Honolulu is on the 2017 NEC by Revised Ordinances Section 17-1.1, Hawaii County is on the 2017 NEC, and MAUI IS ON THE 2008 NEC by Ordinance 3726, effective 2010-06-06. In all three, 210.8(F) does not exist at all, so there is no exception to expire and no September 2026 event. We could not read Kauai's electrical adoption (403 twice), so we do not characterise it. At the state layer the position is genuinely undecidable rather than merely unread: the State Building Code Council's own listing says the 2020 NEC adopted 2022-03-15, while HRS 107-24(c) automatically adopts a code the Council fails to act on within two years, and the Governor's Twentieth Proclamation of July 2026 recites that automatic adoption has in fact occurred while suspending the Council's power to adopt. Those cannot all be resolved from the documents. One thing worth knowing about the state's own page: it labels its electrical link "2018 NFPA 70", an edition that has never existed, and the document behind it is the 2020 code. Ask your county building department which NEC edition it enforces. Source ›

05researched
refusing

Maryland

We refuse because Maryland has no binding statewide electrical code for dwellings, so there is no single Maryland answer to give you. Md. Public Safety Section 12-603 says each electrical installation shall conform to either the National Electrical Code or the electrical code and amendments adopted by the COUNTY where the work is done, and it names no edition at all. The statewide building code is mandatory but deliberately hands electrical off: COMAR 09.12.51.04 writes it out of scope twice, once for IBC Chapter 27 and once for IRC chapters 34 through 43, each time pointing at the local electrical code. The state instrument that DOES amend 210.8(F), the Model Performance Code at COMAR 09.12.50, says at .02B(1) that it may not be binding upon any subdivision unless that subdivision adopts it. Here is the part worth carrying to your county: where the model code HAS been adopted, Maryland incorporates the 2020 NEC with its own words added to the 210.8(F) exception, "and heating, air-conditioning, and refrigeration equipment that serve the dwelling", and that carve-out carries NO expiry, so a county on the model code likely has no September 2026 cliff at all. Ask your county which electrical code and which edition it has adopted, and whether it took the Maryland Model Performance Code with it. Source ›

06researched
refusing

Missouri

We refuse because Missouri has no statewide electrical code reaching a site-built one- or two-family dwelling, so there is no statewide answer to give you. RSMo 64.170 EMPOWERS first- and second-class counties to adopt building regulations rather than requiring it, and counties without a code predating August 28, 2001 need voter approval. RSMo 324.920 is statewide electrical contractor LICENSING, and the only place the National Electrical Code appears in it is as the basis for a written examination, which is exam content and not a construction standard. A full-text search of Missouri's own revisor site does return the National Electrical Code in several statutes, so the absence here is evidence rather than a failed search, and not one of those provisions adopts it as a building code for dwellings. The one statewide instrument that DOES adopt the NEC, 20 CSR 4240-123.080, covers modular units only: it applies to "modular units which entered the first stage of production after July 1, 1976", a modular unit being a TRANSPORTABLE factory-built building unit under RSMo 700.010. For those units Missouri adopts NFPA 70-2020 and states that "the referenced codes do not include any later amendments or additions", in a rule amended April 2024 and effective November 30 2024, which is well after the amendment that created the HVAC exception, so those units never received it. None of that reaches a house framed on site. Ask your city or county which electrical code it has adopted. Source ›

07researched
refusing

Montana

We refuse because Montana is a case where the practical answer is probably clear and our evidence is not good enough to publish it. Two things are worth knowing regardless. First, Montana is on the 2020 NEC, not the 2023, whatever a tracker tells you: the state's own current-codes page and its own rule both say 2020, and the rule was amended as recently as September 2024. Second, Montana never adopted the amendment that created the listed-HVAC exception, so the exception is not in Montana's code at all. What exists instead is a September 2022 enforcement memo from the Building Codes Program allowing installers to use the exception, and that memo quotes the expiry itself: it lets you "utilize this exception", and this exception expires September 1, 2026 by the very words the memo reproduces. So the relief lapses on that date rather than surviving it. We are still refusing, because the only copy of Montana's adopting rule we have been able to read is a third-party reproduction (the state's own rules site returns 403 to us), and if that rule turns out to pick up tentative interim amendments then this whole reading changes. Ask the Montana Building Codes Program directly, and ask specifically whether the 2022 HVAC memo is still in force after September 1, 2026. Source ›

08researched
refusing

North Carolina

We refuse because we have read North Carolina's rules and they do not produce a clean answer. The 2023 State Electrical Code, which appends only a submersible-well-pump exception and leaves the NEC sunset intact, is on INDEFINITE DELAY under Session Law 2025-2 (House Bill 47). What is actually in force is the 2020 State Electrical Code, effective November 1, 2021, and it amends 210.8(F) to read "Deleted" while also stating that it does not apply to one- and two-family dwellings. So for most dwelling work the governing document is the NC Residential Code, which we have not been able to read. Ask the NC Office of State Fire Marshal which document governs your job before relying on any national article about the September 2026 sunset. Source ›

09researched
refusing

Oregon

We refuse because Oregon rewrote 210.8(F) rather than deleting it, and the rewrite cuts both ways at once. The important part first: Oregon STRUCK the listed-HVAC exception, and the sentence "This exception shall expire September 1, 2026" along with it, when it adopted the 2023 Oregon Electrical Specialty Code effective October 1, 2023. So there is no HVAC exception in Oregon, there has not been one under this code, and NOTHING happens there on September 1, 2026. If you have read a national article about the exception expiring, it is about a provision Oregon does not have. What we will not do is tell you whether your particular outlet is covered, because Oregon also rewrote the scope: it struck "For dwellings" so the section reaches every occupancy, and it replaced "outlets" with "general-purpose receptacles" so it no longer reaches hardwired equipment. An outdoor general-purpose receptacle needs GFCI protection in Oregon unconditionally, with no exception of any kind. A hardwired condenser feed is outside the rewritten section, which is a narrowing and not a clearance. Oregon defines "general-purpose receptacle" nowhere: the phrase occurs exactly once in all eighteen pages of Table 1-E, in this amendment. Read OAR 918-305-0105 Table 1-E page 4 and ask the Building Codes Division which side your installation is on. Source ›

10researched
refusing

South Carolina

We hold South Carolina’s primaries and still refuse, because the state deletes 210.8(F) entirely, so the section imposes nothing there. Source ›

11researched
refusing

Utah

We hold Utah’s primaries and still refuse, because the state deletes 210.8(F) entirely, so the section imposes nothing there. Source ›

12researched
refusing

Virginia

We hold Virginia’s primaries and still refuse, because the state deletes 210.8(F) entirely, so the section imposes nothing there. Source ›

13researched
refusing

West Virginia

We refuse because West Virginia's State Building Code binds only where a local jurisdiction has adopted it. W. Va. Code Section 7-1-3n says the state building code "shall not apply to or affect any territory within the boundaries of any municipal corporation which has not adopted the state building code", and 87CSR4 Section 87-4-7.1 requires each adopting jurisdiction to notify the Fire Commission in writing. So there is no statewide answer to give you. What we can tell you about the state rule, if your jurisdiction has adopted it: West Virginia is on the 2020 NEC, effective 2022-08-01, and its adoption contains no tentative-interim-amendment language of any kind, so the NEC's own listed-HVAC exception never reached it. West Virginia did write an HVAC exception of its own, and it has already expired: 87-4-4.1.m.1 excepted mini-split and power-conversion HVAC "until January 1, 2023". GFCI protection has been required on outdoor HVAC there since that date, and nothing further happens on September 1, 2026. A 2023 NEC package was AGENCY-APPROVED on 2026-07-31 and filed with the Legislative Rule-Making Review Committee, which cannot put it in force and which carries no effective date. Ask whether your city or county has adopted the state building code, and which version. Source ›

A countdown article keyed to the 2023 NEC would give every one of these a confident answer. For North Carolina it would be reading a code book the state has not put into force. For Virginia, Utah and South Carolina it would be citing the NEC at a house those states govern through the International Residential Code instead. So would we have, until we checked which document was actually current, and then which book actually applied.

The failure that runs the other way

The listed-HVAC exception did not ship with the 2020 NEC. It arrived by Tentative Interim Amendment, and that matters for every jurisdiction still on the 2020 edition:

How the listed-HVAC exception entered each edition. Scrolls sideways.
TIALogEditionIssuedEffect on 210.8(F)
TIA 20-13#159320202021-08-26Revised 210.8(F). Carried the LIGHTING exception only: no listed-HVAC exception.
TIA 20-19#165320202022-08-12Added Exception No. 2, the listed-HVAC exception, expiring 2026-09-01.
TIA 23-3#165420232022-08-12Added Exception No. 2 to the 2023 edition. Incorporated into the document prior to printing, so every 2023 printing carries it.

So a jurisdiction that adopted the 2020 NEC before TIA 20-19 took effect, and that does not incorporate TIAs issued after its adoption date, has no HVAC exception at all. Outdoor HVAC has needed GFCI protection there the whole time, and nothing changes on 2026-09-01 because there was never an exemption to lose. A countdown page tells those readers the opposite. We do not know which jurisdictions are in that position, because it turns on the wording of each adoption instrument, so the tool refuses and says why.

The 2023 edition does not have this problem. TIA 23-3 carries the note Text of the TIA was issued and approved for incorporation into the document prior to printing, so every 2023 printing already contains the exception.

All 51 jurisdictions, and exactly where each one stands

Every jurisdiction is selectable in the tool above, and every one of them gets an answer of some kind. All 51 were researched. Three of those answers are different things, and the difference is the point: we can answer for 6, we verified 13 against their own primary documents and still refuse for a reason we can state, and for the remaining 32 the research produced leads we will not publish in place of reading the state’s own amendment.

source
quality

Why the last column is not our answer

The edition shown for a jurisdiction we have not read comes from a compiled adoption dataset, not from that state’s own listing, and it is the weaker of the two sources by some distance. Compiled trackers report a single statewide edition even where there is not one: Hawaii sets its code county by county, with Maui still on the 2008 NEC, and the 2023 often quoted for Maryland is an amendment’s effective date rather than the edition in force. That is why the tool refuses whenever the dataset and a state’s own listing disagree, rather than picking a winner.

All 51 jurisdictions. Four outcomes, and “not yet read” is not a refusal. Scrolls sideways.
JurisdictionWhere it standsEdition, verified from the state’s own listingEdition per the compiled dataset (weaker)
AlabamaResearched, still refusesnot read2020
AlaskaResearched, still refusesnot read2020
ArizonaAmendment not readnot readNone (local option)
ArkansasNot required
210.8(F) does not exist in Arkansas
20202020
CaliforniaAmendment not readnot read2023 (via 2025 California Electrical Code, Title 24 Part 3)
ColoradoAmendment not readnot read2023
ConnecticutResearched, still refuses20202020
DelawareAmendment not readnot read2023
District of ColumbiaAmendment not readnot read2014
FloridaAmendment not readnot read2020 (via Florida Building Code 8th Edition)
GeorgiaNot required
GFCI is not required for listed HVAC equipment in Georgia
20232023
HawaiiResearched, still refusesnot readBy county (no single statewide edition)
IdahoAmendment not readnot read2023
IllinoisAmendment not readnot readNone (local option)
IndianaAmendment not readnot read2017
IowaAmendment not readnot read2023
KansasAmendment not readnot readNone (local option)
KentuckyAmendment not readnot read2023
LouisianaNot required
GFCI is not required for listed HVAC equipment in Louisiana
20202020
MaineAmendment not readnot read2023
MarylandResearched, still refusesnot read2020 (2023 amendment date is often quoted as the edition)
MassachusettsAmendment not readnot read2026 (527 CMR 12.00 with MA amendments)
MichiganAmendment not readnot read2023
MinnesotaAmendment not readnot read2023
MississippiAmendment not readnot readNone statewide (local option)
MissouriResearched, still refusesnot readNone (local option)
MontanaResearched, still refusesnot read2020
NebraskaAmendment not readnot read2023
NevadaAmendment not readnot readNone (local option)
New HampshireAmendment not readnot read2023
New JerseyAmendment not readnot read2023
New MexicoNot required
GFCI is not required for listed HVAC equipment in New Mexico
20202020
New YorkAmendment not readnot read2023 (via 2025 Uniform Code)
North CarolinaResearched, still refuses20202020
North DakotaAmendment not readnot read2023
OhioNot required
GFCI is not required for listed HVAC equipment in Ohio
20232023
OklahomaAmendment not readnot read2023
OregonResearched, still refusesnot read2023 (with amendments)
PennsylvaniaAmendment not readnot read2020
Rhode IslandAmendment not readnot read2023
South CarolinaResearched, still refuses20202020 (with amendments)
South DakotaNot required
210.8(F) does not exist in South Dakota
20232023
TennesseeAmendment not readnot read2023
TexasAmendment not readnot read2023
UtahResearched, still refuses20232023
VermontAmendment not readnot read2023
VirginiaResearched, still refuses20202020 (USBC 2021 cycle)
WashingtonAmendment not readnot read2023 (with L&I amendments)
West VirginiaResearched, still refusesnot read2020
WisconsinAmendment not readnot read2017 (SPS 316)
WyomingAmendment not readnot read2023

How a jurisdiction gets onto the answered list

A jurisdiction becomes answerable here only when we hold TWO independently fetched primary documents that AGREE: the state's own current-code listing saying which edition it enforces today, and the state's own amendment to 210.8(F). Reading one without the other is what produced a confident wrong answer for North Carolina, whose amendment we had read correctly and whose code was on indefinite delay. Where the two disagree, or where either is missing, this tool refuses.

We are not going to give you a date for the rest, because a date is a claim about the future that nobody can check and that goes stale quietly. What we can tell you is what is actually in the way right now, which you can check today:

Changes already filed that will move these answers

None of these is in force, and none of them changes an answer above. They are here because “approved” is not “in force”, and confusing the two is the single most expensive mistake available on this subject.

Filed, not in force. None of these changes an answer above. Scrolls sideways.
JurisdictionTo editionEffectiveStatus todayWhat it would do
Arkansas2026no date announcedapproved not filedRead from an IMAGE, because the text layer of the markup does not show the redline and would read as if nothing had changed. If this package is ever filed, Arkansas stops being a section-deleted state and becomes a voltage-threshold state-authored exception, which is a different model shape and needs its own row rather than an edit to this one. Nothing about it changes today's answer.
South Carolina20232027-01-01adopted not yet effectiveThe 2027 package is NOT a continuation of South Carolina's current deletion; it reverses the mechanism. New R.8-1104 enacts 210.8(F) with a PERMANENT listed-HVAC exception carrying no expiry, and the matching IRC modification (new R.8-1267, IRC Section E3902.14 Outdoor Outlets) grants the same permanent exception on the residential path, which is what closes the split that makes South Carolina unanswerable today. The same package repeals 8-1106, so South Carolina will begin enforcing NEC 230.67 surge protection, and it corrects the R.8-1252 catchline that currently mis-cites E3902.17 for AFCI. Two limits on this reading, both ours: the State Register PDF is image-only, so this text was read from a 260 DPI raster of pages 43 and 44, and we did not locate an explicit "effective January 1, 2027" line inside Document No. 5418 itself; the date rests on the Council's own published implementation date plus S.C. Code Section 6-9-40 plus the identical 2021-cycle precedent.

What this tool does not know

New: run this inside your AI assistant

Prefer to just ask? Add this to Claude, free.

Connect Intry to Claude once, then just say “use Intry to…” to run the outdoor hvac gfci requirement from a plain-English question, on your phone, on the job. You get the number, what it means, and the cited NEC section together with your state's own amendment to it, computed live, not guessed. Works on every Claude plan.

Use this in Claude

Questions

Does the NEC HVAC GFCI exception really expire on 1 September 2026?

Yes, in the NEC's own text. NEC 2023 210.8(F) Exception No. 2 reads, verbatim: "GFCI protection shall not be required for listed HVAC equipment. This exception shall expire September 1, 2026." That sentence is in the printed book. What it does NOT tell you is whether it is in force where you work, because states rewrite this section, and they do it by at least three different mechanisms. Of the jurisdictions we have read, Arkansas, Georgia, Louisiana, New Mexico, Ohio and South Dakota do not follow the sunset: some reproduce the exception and leave the expiry sentence out, some write their own exception that never carried one, and some delete 210.8(F) from their adoption entirely. Those are different legal objects reaching the same practical answer, and the table above says which one is under you.

Why will a national countdown article be wrong?

Because it fails in two opposite directions at once. In one direction, states that deleted the expiry keep exempting HVAC after the date. In the other, the exception only entered the 2020 NEC through TIA 20-19, issued 2022-08-12 and effective 2022-09-01. A jurisdiction on the 2020 edition whose adoption predates that TIA, and which does not pick up later TIAs, never had the exception at all. Telling those readers they are exempt "until September" is wrong today, not just after the date.

Does 210.8(F) apply to a commercial rooftop unit?

No. 210.8(F) opens "For dwellings", so it does not reach other-than-dwelling work. That is not the same as saying no GFCI is required: 210.8(B) governs other-than-dwelling units and has different thresholds, reaching 125 V through 250 V receptacles and three-phase branch circuits up to 100 A. Where we have read your jurisdiction’s amendment, this tool refuses and points you at 210.8(B). Where we have not, it refuses on that ground first and never reaches the 210.8(B) note.

What ampere rating does 210.8(F) reach?

On the 2023 edition, single-phase branch circuits rated 150 volts or less to ground and 50 amperes or less. The ceiling is edition-specific, so do not carry a number across editions. We publish a ceiling only for editions whose text we have actually read (2023 and 2020).

Why does this tool refuse for my state?

There are two different reasons, and the tool tells you which one applies. All 51 jurisdictions were researched, but for most of them that research produced leads rather than a reading of the state's own amendment to 210.8(F), and this is a question where guessing is worse than declining. The other reason is a different thing entirely: 13 of the 19 jurisdictions we VERIFIED against their own documents still get a refusal, because we read the rules and they do not produce an honest answer. Alabama, Alaska, Connecticut, Hawaii, Maryland, Missouri, Montana, North Carolina, Oregon, South Carolina, Utah, Virginia and West Virginia are in that group, each for a stated reason. Rather than apply a national default, which would be wrong in both directions, the tool tells you exactly what it does not know and sends you to your AHJ.

Is a Class C SPGFCI device the way out?

We do not publish an answer on that. Class C special-purpose GFCI is reported to be a 2026-edition provision, and we hold no primary for the 2026 edition's text of 210.8(F). UL 943C is an Outline of Investigation rather than a published standard. This tool prints nothing about it. Note that our separate 2026-changes summary page does carry the widely reported 60 A figure from trade change-summaries; that is a secondary source, and it is why this tool refuses on the 2026 edition rather than reusing it.

Related