Electrical Calculator
Electrical Load Calculator: NEC 220.82 & 220.87
Service sizing by NEC 220.82 or the 2023 standard method, the 220.87 check from demand data, and the 220.83 check from nameplates: whether this panel has room for the EV charger or heat pump you are adding.
Intry VerifiedA worked default reading, traceable end to end: what it was calculated from, what it was run with, how it was checked, and who has final say.
Where this number comes fromIntry Verified
- Calculated from
- NEC 220.82. Computed from NEC 220.82 (new-service, optional method), the NEC 2023 standard method (220.40, Article 220 Part III), 220.87 (existing-panel, from demand data) or the existing-dwelling method of the edition you choose (220.83, from nameplates). On the first three the EV charger is added at 100% at the larger of 7,200 VA or its nameplate per 220.57, and the two new-service methods size the service up to the next size in this tool's dwelling list, never below the calculated load (230.79). See the full receipt ↓
- Run with
- Floor area2,000 sqft
- Small-appliance / laundry2 + 1 circuits
- Fixed appliances5 items
- Heating / coolingAir conditioning / cooling only, 4,800 VA
- EV chargerNone
- Service voltage240 V
- Compared withNone
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,006 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit.
- Final say
- Your AHJ and local amendments have final say. Confirm before rough-in.
Intry Verified · NEC 2023 · Build AF0D4B6 · 2026-11-11
The two new-service methods and the demand-data method follow NEC 2023 (NFPA 70-2023): 220.82, the standard method of Article 220 Part III (220.40), 220.57 and 220.87; the existing-dwelling method follows the edition you choose. Local amendments change these numbers, and a permit-grade calculation belongs to a licensed electrician working from your jurisdiction's adopted edition; the AHJ has the final word.
Run this inside your AI assistant
Prefer to just ask? Add this to Claude.
Connect Intry to Claude once, then just say “use Intry to…” to run the measured-demand check (220.87) from a plain-English question, on your phone, on the job. You get the number (computed live, not guessed), what it means, and the cited NEC section. Works on every Claude plan.
The Six Heating/Cooling Options, NEC 220.82(C)
The optional method adds the largest of these six to the demand-factored general load. Only the biggest scenario counts, each with the loads its own item names (a heat pump's compressor and 65% of its supplemental heat together, for one), and this bucket gets no further demand factor.
| 220.82(C) | Situation | What you count |
|---|---|---|
| (1) | Air conditioning / cooling only | 100% of the air-conditioning and cooling equipment nameplate |
| (2) | Heat pump without supplemental heat | 100% of the heat pump nameplate when used without supplemental electric heat |
| (3) | Heat pump with supplemental electric heat | 100% of the compressor nameplate plus 65% of the supplemental electric heat |
| (6) | Electric thermal storage heating | 100% where the usual load is expected to be continuous at full nameplate |
| (4) | Electric space heat, fewer than 4 units | 65% of nameplate with fewer than four separately controlled units |
| (5) | Electric space heat, 4 or more units | 40% of nameplate with four or more separately controlled units |
Option (3) note: the code also addresses compressors interlocked so the compressor and the supplemental heat cannot run at the same time (the compressor then does not have to be added to the supplemental heat). Verify that wording in your copy of the book; this calculator conservatively counts both.
The Standard Method, Line by Line: NEC 2023 Article 220, Part III
The calculator's standard method takes a new dwelling service in the book's order, one line per kind of load (220.40). NEC 220.82(A) permits the optional method instead, and the two can give different service sizes for one house: the calculator shows the method you choose, labelled, and never picks between them. It runs the book's own worked house, Annex D Example D1(a), to 18,600 VA, 77.5 A (the example rounds it to the nearest whole ampere, 78 A).
| Line | What it takes | NEC 2023 |
|---|---|---|
| General lighting | 3 VA per sq ft of floor area, from the outside dimensions, without open porches or unfinished areas not adaptable for future use as a habitable room or occupiable space | 220.41, 220.5(C) |
| Small-appliance and laundry circuits | 1,500 VA each | 220.52(A), 220.52(B) |
| Their demand | the first 3,000 VA at 100%, up to 120,000 VA at 35%, the rest at 25% | Table 220.45 |
| Appliances fastened in place | 75% when 4 or more are rated 500 W or 1/4 hp or more (this tool counts a row only where you tick it as so rated, since a motor's volt-amperes do not tell its horsepower); never cooking, dryers, heat, air conditioning or an EV charger | 220.53 |
| Cooking appliances over 1 3/4 kW | Table 220.55, Column C (one range of 12 kW or less: 8 kW), raised by Notes 1 and 2 above 12 kW, Note 2 counting 12 kW for each appliance under 12 kW as the 2023 NEC Handbook's example does | 220.55 |
| Dryers | 5,000 VA or the nameplate, whichever is larger | 220.54 |
| Electric space heating | 100% of the connected load | 220.51 |
| Air conditioning | the rated-load current or the branch-circuit selection current, whichever is greater, by Article 440 | 220.50(B), 440.33 |
| Heat and air conditioning unlikely to run at the same time | the larger; this tool still counts the air conditioning toward the largest motor's 25% (430.24, 440.33) | 220.60 |
| EV charger | 7,200 VA or the nameplate, whichever is larger | 220.57 |
| Other specific loads | their rating | 220.14(A) |
| Largest motor or compressor, by current | 25% of it added: a motor's current from the motor tables (430.6(A)(1)), a compressor's as above | 220.50(A), 430.24, 440.33 |
| 120 V loads | split across the two lines, and each line worked on its own, as Annex D Example D1(b) does; the heavier line sizes the service | 220.40 |
| Service | a rating not below the load, or the heavier line | 230.79 |
It adds the loads in volt-amperes over 240 V, as Example D1(a) does, and where 120-volt loads are entered it works each line as Example D1(b) does, with those loads wired across the lines as it lists them; wired another way, one line can carry more. City worksheets can price lines differently from the book, and the form your authority having jurisdiction asks for decides what it accepts.
Adding Loads Without Metering Data: NEC 220.83
The code also addresses another path, and the calculator runs it as its existing-dwelling method. For a dwelling unit served by a 120/240-volt or 208Y/120-volt, 3-wire service or feeder, 220.83 lets you total the existing plus new loads with its own demand factors, an alternative to 220.87 that needs no metering data. Pick your job's code edition in the calculator: these are the 2020 and 2023 percentages, and the 2026 edition's are below.
| Case | Demand factors |
|---|---|
| 220.83(A): no additional AC or electric space heating being installed | First 8 kVA of the total at 100%, remainder at 40% |
| 220.83(B): additional AC or electric space heating IS being installed | Air conditioning at 100%, central electric space heating at 100%, and fewer than four separately controlled space-heating units at 100%, counting only the larger of the air-conditioning or space-heating load, not both; all other loads at first 8 kVA 100% + 40% remainder |
Read from the code itself: NEC 2023 (NFPA 70) 220.83. The (B) table has no row for four or more separately controlled space-heating units, such as baseboard heat in four or more rooms, so this page and the calculator give no percentage for that case. The 2026 edition moves the section to 120.83 with one table: the first 8 kVA of existing and new load at 100%, the remainder of the existing load at 40%, new EVSE at 80%, new central electric resistance space heating at 80%, and all other new loads at 50%, using the larger of air conditioning or space heating, not both. When you have a year of demand data, or a 30-day recording under the exception, run 220.87 first: it uses what the house drew. Both methods are permitted, except that NEC 2020 does not permit 220.87 at all where the service has a renewable energy system or any peak load shaving, and the 2023 and 2026 editions (120.87 in 2026) do not permit its 30-day recording there; they can disagree, and neither replaces a permit-grade calculation for the authority having jurisdiction.
Four Methods, and the Question Each Answers
New or replacement service: 220.82, or the standard method. The standard method (the section above) prices the house line by line; both are permitted, they can give different sizes, and the calculator shows the one you choose. The optional method builds the load from scratch: square footage, circuits, appliance nameplates, then a steep demand factor (100% of the first 10 kVA, 40% of the rest), since the code does not expect every load to run at once. Heating and cooling ride on top at the largest of six options, and an EV charger adds the larger of 7,200 VA or its nameplate per 220.57. It applies to dwellings on a single 120/240 V or 208Y/120 V, 3-wire service of 100 A or more, per 220.82(A).
Existing panel with demand data: 220.87. Instead of estimating, it uses what the house actually drew: the highest demand over 12 months of utility metering, or a 30-day recording under the exception, which is not permitted where the service has a renewable energy system (solar PV, wind) or any form of peak load shaving, and NEC 2020 does not permit 220.87 at all there. Multiply that peak by 125%, add the new load, and compare to the service rating. Because it starts from measured demand, 220.87 can prove a 100 or 125 A panel can take a charger that a from-scratch calculation would reject.
Existing panel, no metering data: 220.83. The table above, and the calculator's existing-dwelling method. It adds nameplates and floor area by the code's percentages and asks which code edition your job is held to. Coming up short here is not the end of it: 220.87 is also permitted, and it can pass a load these percentages do not, except that NEC 2020 does not permit 220.87 at all where the service has a renewable energy system or any peak load shaving, and the 2023 and 2026 editions (120.87 in 2026) do not permit its 30-day recording there.
The EV Charger Wrinkle in NEC 2023
NEC 2023 added 220.57 (EVSE at the larger of 7,200 VA or nameplate), and its 220.82 optional method names no EVSE, so it does not say whether that number may ride the 40% second tier or must be added at 100%. 220.82(A) is also used instead of Part III, where 220.57 sits, so the floor is not the optional method's own rule. This calculator's optional method adds EVSE at the 220.57 figure at 100%, outside the 40% tier, for two reasons: it is the conservative choice under 2023, and the 2026 edition settles it in exactly that direction with new 120.82(D), which adds EVSE at 100% of its 120.57 load (the nameplate, or 7,200 VA where there is none). Related: 220.53 explicitly excludes EVSE from the dwelling fixed-appliance demand factor, so there is no discount hiding there either.
Worked Examples
Example 1: 2,000 sqft house, full 220.82 calculation
Two small-appliance circuits and one laundry circuit; appliances at nameplate under 220.82(B)(3): electric range 12,000 VA, water heater 4,500 VA, electric dryer 5,000 VA, dishwasher 1,200 VA, disposal 900 VA; central air conditioning and no EV charger, on a 120/240 V service. The working below is the calculator's own, step by step, with the section each step comes from.
Show the math
- GIVENFloor area: 2,000 sqft
- GIVENService voltage: 240 V
- TABLELighting: 3 VA x 2,000 sqft = 6,000 VANEC 220.82(B)(1)
- TABLECircuits: 1,500 VA x (2 small appliance + 1 laundry) = 4,500 VANEC 220.82(B)(2)
- MATHFixed appliances (5): 23,600 VANEC 220.82(B)(3)
- MATHGeneral loads = 34,100 VANEC 220.82(B)
- MATHDemand = 10,000 + 0.40 x 24,100 = 19,640 VANEC 220.82(B)
- TABLEHVAC: 100% x 4,800 = 4,800 VANEC 220.82(C)(1)
- MATHCalculated load = 19,640 + 4,800 = 24,440 VANEC 220.82(A)
- MATH24,440 VA / 240 V = 101.8 A
- ROUNDService: the next size up in this tool's list of dwelling services (100, 125, 150, 200, 225, 400 A) at or above 101.8 A is 125 A; NEC 230.79 requires a rating not less than the calculated load. Table 240.6(A) also has 110 A, the smallest standard rating at or above the load, which meets 230.79 as wellNEC 230.79
- RESULTRecommended service: 125 ANEC 230.79
Example 2: 200 A panel + 40 A EV charger, 220.87, PASS
The utility's interval data gives a 12-month peak demand of 9.6 kW, and the new load is a 40 A charger at 240 V, entered at its nameplate VA (already above the 220.57 floor). The working:
Show the math
- GIVENExisting service: 200 A at 240 V
- MATH12-month utility peak: 9.6 kW = 9,600 VA (40 A at 240 V)NEC 220.87(1)
- MATH125% x 9,600 = 12,000 VA (50 A)NEC 220.87(2)
- MATHService: 200 A x 240 V = 48,000 VA
- MATHHeadroom before new load: 48,000 - 12,000 = 36,000 VA (150 A)
- MATHNew load: 9,600 VA (40 A)
- MATHCheck: 12,000 + 9,600 = 21,600 VA vs 48,000 VA serviceNEC 220.87(2)
- RESULTPASS: 26,400 VA (110 A) spare after the new loadNEC 220.87(2)
Example 3: 100 A panel with electric heat + the same charger, FAIL
A metered peak of 18 kW, an illustrative winter figure for a small all-electric house, and the same charger. The working:
Show the math
- GIVENExisting service: 100 A at 240 V
- MATH12-month utility peak: 18 kW = 18,000 VA (75 A at 240 V)NEC 220.87(1)
- MATH125% x 18,000 = 22,500 VA (93.8 A)NEC 220.87(2)
- MATHService: 100 A x 240 V = 24,000 VA
- MATHHeadroom before new load: 24,000 - 22,500 = 1,500 VA (6.2 A)
- MATHNew load: 9,600 VA (40 A)
- MATHCheck: 22,500 + 9,600 = 32,100 VA vs 24,000 VA serviceNEC 220.87(2)
- RESULTFAIL: over by 8,100 VA (33.8 A)NEC 220.87(2)
Options: an energy management system per NEC 625.42(A) that holds the charger to the 1,500 VA that fits before it (or dynamically to whatever is free moment to moment), a full 220.82 recalculation with its demand factors, or a service upgrade.
Frequently Asked Questions
Can a 100 A panel handle a Level 2 EV charger?
It has to be proven with a load calculation, not guessed. With a year of demand data, NEC 220.87: take the highest demand from 12 months of utility metering data, multiply by 125 percent, and add the charger load. A 100 A, 240 V service is 24,000 VA, so the install works when 1.25 times the metered peak plus the charger stays at or below 24,000 VA. Example: a metered peak of 8 kW gives 1.25 x 8,000 = 10,000 VA, leaving 14,000 VA, which is plenty for a 40 A (9,600 VA) charger. A peak of 18 kW leaves only 1,500 VA and fails. When it fails, a listed energy management system per NEC 625.42(A), in accordance with NEC 750.30, can set the maximum equipment load used in the service calculation instead of forcing a service upgrade.
What is the difference between the standard method and the optional method?
The standard method in NEC Article 220 Part III itemizes each load with its own rule: lighting and the small-appliance and laundry circuits by Table 220.45, fastened appliances by 220.53, cooking by Table 220.55, dryers by 220.54, heat at 100 percent by 220.51, and 25 percent of the largest motor. The optional method in 220.82 is a simplified alternative for a dwelling served by a single 120/240 V or 208Y/120 V, 3-wire service or feeder of 100 A or larger: everything except heating and cooling goes into one bucket taken at 100 percent of the first 10 kVA plus 40 percent of the remainder, then the largest of the six heating and cooling options in 220.82(C) is added on top; this calculator also keeps an EV charger out of that bucket and adds its 220.57 figure at 100 percent. 220.82(A) permits it instead of Part III, so both are code methods, and they can give different service sizes for one house. The calculator runs both, shows the one you choose, and never picks between them; the authority having jurisdiction decides which calculation it accepts.
Can I use NEC 220.87 without 12 months of utility data?
Yes, through the exception in 220.87. If a year of utility demand data is not available, you may base the calculation on the maximum demand recorded continuously for at least 30 days, defined as the highest average kilowatts reached and maintained over a 15-minute interval, using a recording ammeter or power meter on the highest loaded phase. The recording must be taken while the building is occupied, and it must include, by measurement or calculation, the larger of the heating or cooling load plus other loads that are periodic or seasonal in nature. The exception is not permitted where the service has a renewable energy system such as solar PV or wind, or uses any form of peak load shaving.
What is the difference between connected load and demand load?
Connected load is the sum of every nameplate in the house, as if everything ran flat out at once. Demand load is what the code lets you count after applying demand factors, because the code does not expect every load in a home to run at once. In the worked example on this page, NEC 220.82 turns 34,100 VA of connected general load into 19,640 VA of demand. NEC 220.87 skips the estimate entirely and starts from the demand the meter actually recorded. Service size is always based on the calculated demand load, never on the connected total.
How many VA is an EV charger in a load calculation?
Per NEC 220.57, new in the 2023 edition, EVSE is calculated at 7,200 VA or the nameplate rating, whichever is larger. The 7,200 VA floor corresponds to a 30 A, 240 V circuit. So a 40 A charger counts as 9,600 VA and a 48 A charger as 11,520 VA, while a small 16 A unit still counts as 7,200 VA. The 2023 optional method (220.82) names no EVSE, so it does not settle whether the charger may ride the 40 percent second tier as an appliance fastened in place under 220.82(B)(3); and 220.82(A) is used instead of Part III, where 220.57 sits, so the 7,200 VA floor is not the optional method's own rule either. This calculator's optional method adds the charger at the 220.57 figure at 100 percent outside that tier, a load at or above any reading of 220.82, the conservative choice under 2023. The 2026 edition's 120.82(D) adds EVSE at 100 percent of its 120.57 load, which is the nameplate rating, or 7,200 VA where there is none. Under the 2023 NEC, where a listed energy management system per 625.42(A), in accordance with 750.30, controls the EVSE, the managed maximum setting can be used instead.
What is NEC 220.83 and when does it apply instead?
220.83 is a permitted way to check whether an existing service or feeder can take additional load, for a dwelling unit served by a 120/240-volt or 208Y/120-volt, 3-wire service or feeder. Per 220.83(A), when no additional air conditioning or electric space heating is being installed, existing plus new loads are taken at 100 percent of the first 8 kVA plus 40 percent of the remainder. Per 220.83(B), when air conditioning or electric space heating is being added, air-conditioning equipment is taken at 100 percent, central electric space heating at 100 percent, and fewer than four separately controlled space-heating units at 100 percent, using only the larger of the air-conditioning or space-heating load, not both; all other loads get 100 percent of the first 8 kVA and 40 percent of the remainder. Table 220.83(B) has no row for four or more separately controlled space-heating units. The calculator runs 220.83 as its existing-dwelling method, 120.83 under the 2026 edition, for the edition you choose; where four or more separately controlled units leave it without a figure, it offers its standard method for the house. If you have a year of demand data, or a 30-day recording under the exception, run 220.87 first: it uses what the house drew. Both are permitted, except that NEC 2020 does not permit 220.87 at all where the service has a renewable energy system or any peak load shaving, and the 2023 and 2026 editions (120.87 in 2026) do not permit its 30-day recording there; the authority having jurisdiction decides.
Does the NEC 2026 change these calculations?
Yes, in ways worth knowing whether or not your state has adopted it; this calculator's new-service and demand-data methods answer from the 2023 edition, and its existing-dwelling method from the edition you choose (120.83 in 2026). The 2026 edition renumbers Article 220 to Article 120, so 220.82 becomes 120.82 and 220.87 becomes 120.87. Inside the optional method, the general lighting allowance drops from 3 VA to 2 VA per square foot and the 100 percent first tier drops from 10 kVA to 8 kVA, and both changes lower the calculated load: the kVA between 8 and 10 moves from 100 percent to 40 percent. New 120.82(D) adds an EV charger at 100 percent of its 120.57 load, which is the nameplate rating, or 7,200 VA where there is no nameplate, so the 7,200 VA minimum this calculator applies under 2023 is gone. And 120.87 now takes "the maximum demand at 125 percent plus the new load minus any removed load", useful when swapping resistance heat for a heat pump. See our NEC 2026 changes page for the main changes, each beside what the 2023 edition printed, and which states have adopted it.
Do I calculate at 240 V or 208 V?
Use 240 V for the standard single-phase, three-wire service in detached homes. Use 208 V when the dwelling is fed from two legs of a 208Y/120 V three-phase system, as an apartment or condo building can be. The choice matters: the same 24,440 VA calculated load is 101.8 A at 240 V but 117.5 A at 208 V, which can push the answer past a service size. NEC 220.82(A) permits the optional method for both service types.
The calculation passes; why might an electrician still recommend an upgrade?
A load calculation only answers whether the service capacity is sufficient. An electrician on site also weighs physical breaker space, panel age and condition, whether the panel brand is one of the known problem lines, aluminum branch wiring, available fault current, and local amendments that can be stricter than the NEC as published. This calculator is a planning and estimating tool. A permit-grade calculation, stamped where required, belongs to a licensed electrician working from your jurisdiction's adopted code edition.
How do I know if my electrical panel is overloaded?
There are two different ways a panel is overloaded. The first is calculated: your demand load exceeds the service rating. Run a load calculation (NEC 220.83 when adding loads to an existing home, or 220.87 from a year of metered data), and if the demand comes out above your service amps, more than 100 A of demand on a 100 A panel for example, the calculation does not support that load under that method; NEC 220.87 is also permitted and can pass where 220.83 does not, except that NEC 2020 does not permit 220.87 at all where the service has a renewable energy system or any peak load shaving, and the 2023 and 2026 editions (120.87 in 2026) do not permit its 30-day recording there. The second is physical: breakers that trip repeatedly, a panel with no open slots, two wires landed under one breaker (a double-tap), or a warm panel cover. The calculated check is what this tool answers, naming a fit, a tight result or a shortfall under the method you ran; the physical check needs a licensed electrician's eyes on the panel. Adding a large new load like an EV charger, heat pump, or electric range is one way a panel that was fine becomes overloaded.
Related Calculators
Electrical Panel Schedule
Save a 220.82 run, then attach it to the panel's schedule: every circuit by space, the connected VA on each phase, and this calculated load beside it.
EV Charger Circuit Calculator
Once the panel passes, size the branch circuit: wire, breaker, GFCI, and charging speed for Level 2 EVSE.
NEC 2026 Changes
Article 220 becomes Article 120, 2 VA per sqft, the 8 kVA tier, and the other main 2026 changes, each beside what the 2023 edition printed.
MCA & MOCP Calculator
The heat pump side of electrification: wire and breaker straight from the HVAC nameplate per Article 440.
Wire Size Calculator
Conductor sizing for the new feeder or branch circuit, with temperature correction and bundling derates.
EV Load Management (Biggest Charger)
Invert the 220.87 check: the biggest EV charger your service takes, and how a load-management device raises it without a panel upgrade.
120V Induction Range Circuit
The plug-in induction range that skips the 240V circuit: it adds only ~1.4-1.8 kVA to the service calc, not the 8 kW a 240V range gets.
Panel passes? Now build the circuit.
The load calculation answers whether the service can take the charger. The EV charger calculator answers everything after that: wire size, breaker, GFCI, receptacle rules, and how fast the car actually charges.