Electrical / runnable MCP tool
Run the Existing-Load Panel Check (NEC 220.87) in your AI assistant
Through the free Intry MCP server, Claude, ChatGPT, or Cursor runs this exact calculator and hands back a verdict and the cited source, not a guess. Tool name: load_can_panel_handle.
What you get back: pass/fail, the total, and the remaining margin.
How it computes the answer
NEC 220.87, the measured-demand method for an existing dwelling: the measured peak demand at 125% plus the new load, compared to the service rating.
What it cites
Your assistant calls the same engine the interactive calculator calls, with the inputs listed under Inputs. It runs the NEC 220.87 measured-demand check alone (with NEC 220.57 for an EV charger); the interactive load calculator also takes a new service's NEC 220.82 inputs and gives a service-size recommendation, runs the NEC 2023 standard method (Article 220, Part III) as a second way to size a new service, and runs the NEC 220.83 existing-dwelling check (120.83 in the 2026 edition) for a job with no demand data. These are the interactive calculator's sources, including the ones for inputs only it takes.
- NEC 220.82
- Dwelling optional calculation (the new-service mode): the 3 VA per square foot general load plus the fastened-in-place appliances, with the first 10 kVA at 100% and the remainder at 40%, and the larger of heating or air conditioning. NFPA 70-2023.
- NEC 220.40
- The standard method (Article 220, Part III, the new-service standard mode), NFPA 70, 2023 edition, pages 70-93 to 70-97: general lighting at 3 VA per square foot of the floor area 220.5(C) defines (220.41) and 1,500 VA for each small-appliance and laundry circuit (220.52), taken at 100% of the first 3,000 VA, 35% up to 120,000 VA and 25% above (Table 220.45); appliances fastened in place at 75% where four or more are rated 500 W or 1/4 hp or more (220.53), counted toward the four only where the person marks a row as so rated; cooking appliances over 1 3/4 kW by Table 220.55, Column C and its Notes 1 and 2, Note 2 counting 12 kW for each appliance under 12 kW as the 2023 NEC Handbook's example does; dryers at 5,000 VA or the nameplate, whichever is larger (220.54); fixed electric space heating at 100% (220.51); air conditioning and heat unlikely to run at the same time, the larger (220.60); other specific loads at their rating (220.14(A)); air conditioning by 220.50(B), at the rated-load or branch-circuit selection current, whichever is greater (440.33); and 25% of the largest motor or compressor (220.50(A), 430.24, 440.33), a motor's current by 430.6(A)(1). The loads are added in volt-amperes over 240 V, as Annex D Example D1(a) does, and where 120-volt loads are entered each line is worked on its own, as Example D1(b) does, the heavier line sizing the service.
- NEC 220.87
- Existing-dwelling demand from a metered maximum (the existing-panel mode): the maximum demand at 125% plus the new load must not exceed the service. NFPA 70, 2023 edition, page 70-100.
- NEC 220.83
- Existing dwelling unit (the no-demand-data mode): existing and new loads at the code's percentages, by table (A) or (B), the larger of air conditioning or space heating, not both, under (B). NFPA 70, 2023 edition, page 70-99; 2020 edition, page 70-80. Under 2020 and 2023, no figure is given where four or more separately controlled space-heating units are the larger load under (B), or under (A) as this tool's limit. The 2026 edition renumbers this method (in the code index below) and gives one table for existing and new loads, the larger of air conditioning or space heating, not both, NFPA 70, 2026 edition, page 70-85. The calculator reads the edition you choose. An EV charger in this method is inside the percentages: at the larger of 7,200 VA or nameplate under 2023, at nameplate under 2020; under 2026 at nameplate, a new charger on the table's new-EVSE row and an existing one in the existing load.
- NEC 220.57
- On the two new-service methods and the demand-data method, EV supply equipment enters this service and feeder calculation at the larger of 7,200 VA or its nameplate rating, at 100% (no demand factor). NFPA 70-2023. This line applies only when you add an EV charger.
- NEC 210.20(A)
- Optional continuous-load screen. When you mark the new load continuous, the existing-panel check carries it at 125% of its rating (210.20(A)), the conservative sizing for a load that runs three hours or more. Off by default.
- NEC 240.6(A)
- Standard overcurrent-device ratings (Table 240.6(A)). The recommended service is the next size up in this tool's list of dwelling services (100, 125, 150, 200, 225, 400 A), each a rating in this table, and never below the calculated load, which NEC 230.79 requires (p.70-113). The table also has 110, 175, 250, 300, 350 A, which the list skips; where one of those is the smaller rating at or above the load, the working names it.
The code sections those sources name, each with the edition and the page the book prints it on:
Swipe the table sideways to see the rest of its columns. →
| Code and edition | Section | Printed page |
|---|---|---|
| NEC 2023 | 220.82 | 70-98 |
| NEC 2023 | 220.40 | 70-94 |
| NEC 2023 | 220.87 | 70-100 |
| NEC 2023 | 220.83 | 70-99 |
| NEC 2023 | 220.57 | 70-96 |
| NEC 2023 | 210.20(A) | 70-84 |
| NEC 2023 | 240.6(A) | 70-124 |
These are NEC Article 220 demand rules, applied by the engine to the loads you enter, not field measurements. The optional (220.82) and standard (Part III) methods both size a service and can give different sizes; the existing-demand (220.87) and existing-dwelling (220.83) methods check an existing one. The tool shows the method you chose, labelled, and the AHJ has final say on the calculation method.
The full receipt, with every source and how each is cross-checked, is on the interactive Existing-Load Panel Check.
Ask your assistant
The one rule that makes it reliable: name Intry in your question. That is what tells Claude to run the load_can_panel_handle tool and answer with the real number, the verdict, and the citation. Leave Intry out and Claude may just guess from memory, which is exactly what you are trying to avoid. Type something like:
Inputs
Swipe the table sideways to see the rest of its columns. →
| Field | Required | Accepts | Range | What it is |
|---|---|---|---|---|
| serviceAmps | yes | number | more than 0 | Service / main breaker rating (e.g. 200). |
| voltage | optional | number | more than 0 | Service voltage (default 240). |
| demandSource | optional | utility, recording | Source of the peak-demand figure (default utility). | |
| demandValue | yes | number | 0 or more | Existing peak demand value. |
| demandUnit | optional | kw, a | Unit of demandValue (default a). | |
| newLoadValue | yes | number | 0 or more | New load to add. |
| newLoadUnit | optional | va, a | Unit of newLoadValue (default a). | |
| newLoadKind | optional | ev-charger, other | What the new load is (default other). Set ev-charger for an EV charger: NEC 220.57 counts it at 7,200 VA or its nameplate rating, whichever is larger, as the site's EV panel check does. | |
| continuous | optional | boolean | Optional conservative screen. When true, the new load enters the check at 125% of its rating. Leave false (the default) for the literal NEC 220.87 reading: a new load, including an EV charger at its 220.57 value, is added at 100% here; the 125% continuous factor (NEC 625.42 declares EV charging a continuous load; 210.20(A)/625.41 apply the 125%) sizes the charger's own branch circuit, not this service-adequacy check. A strict 2023-edition AHJ may instead apply 125% to a continuous new load; set continuous:true for that conservative screen. |
Add Intry to Claude
One paste and Claude can run this tool and the other calculators on Intry's MCP server, right from your phone.
- Claude opens with the Intry connector already filled in. Review it and click Add.
- (If a field is blank, paste the link below into the URL field.)
- In any chat, tap + then Connectors and switch Intry on. Then name Intry in your question (“use Intry to…”) so Claude runs the tool instead of guessing.
https://www.intrysys.com/api/mcpNo login, no API key, and it works on every Claude plan, right from your phone.
Using ChatGPT, Cursor, or a dev tool? See the developer setup on the main page. The endpoint is https://www.intrysys.com/api/mcp.
Every answer comes with the cited NEC section, so you can check it or show an inspector. The numbers come from the same calculator we run on intrysys.com, and our automated checks hold its answers against their sources before anything goes live, for the cases the checks cover, not for every input you can enter.