NEC Table 314.16(A)

How Many Wires Fit in a Handy Box?

The maximum conductors a handy box (also called a utility box (4 x 2-1/8 inch)) holds by wire size at the NEC 314.16 fill limit, the realistic count once a device is in the box, and the interactive calculator.

Quick answer: A 4 x 2-1/8 x 1-7/8" deep handy box (13 cu in) holds 6 #14, 5 #12, or 5 #10 conductors with nothing else inside. Add one receptacle, clamps, and a ground and it fits about 2 #14 or 1 #12 in practice.

Max Conductors in a Handy Box (NEC 314.16(A))

Maximum same-size conductors by box depth, with nothing else in the box. Each is the box volume divided by the per-conductor allowance from NEC Table 314.16(B)(1).

Maximum conductors in a handy box by depth and wire size, NEC 314.16(A)

Swipe the table sideways to see the rest of its columns. →

Box DepthVolume#14#12#10#8
4 x 2-1/8 x 1-1/2" deep10.35443
4 x 2-1/8 x 1-7/8" deep13.06554
4 x 2-1/8 x 2-1/8" deep14.57654

Volumes in cubic inches. Per-conductor allowance (Table 314.16(B)(1)): #14 = 2.00, #12 = 2.25, #10 = 2.50, #8 = 3.00 cu in. Counts assume one wire size and an otherwise empty box.


The Real Count: With a Receptacle in the Box

The bare maximum applies only to a box holding conductors alone. A real device box holds a receptacle or switch, cable clamps, and a ground, and each takes space before the conductors. In a 4 x 2-1/8 x 1-7/8" deep handy box (13 cu in), the yoke counts as two conductor allowances (NEC 314.16(B)(4)), all clamps together count as one (B)(2), and up to four grounds count as one (B)(5).

Conductors left in a 4 x 2-1/8 x 1-7/8" deep handy box after one device, clamps, and a ground

Swipe the table sideways to see the rest of its columns. →

Wire SizeBare MaxWith Device, Clamps, Ground
#14 AWG62
#12 AWG51
#10 AWG51
#8 AWG40

Device (2) + clamps (1) + ground (1) = four conductor allowances used before any wires. Assumes the device and fittings are sized to the same conductor. Two 14/2 cables plus a receptacle is one real load for this box.


Your Exact Box? Calculate It

The tables cover one wire size at a time. For a real box with mixed wire sizes, multiple devices, or an extension ring, enter the exact contents for the precise NEC 314.16 fill and a pass or fail verdict. The calculator opens on the 13 cu in handy box with the count from the table above: one receptacle, clamps, a ground and 2 #14 conductors.

Box Type

The standard boxes are the metal boxes of NEC Table 314.16(A). A nonmetallic box, or any box marked with its own volume, uses the marked volume (314.16(A)(2)): enter it as a custom volume. A box with a barrier is figured one space at a time (314.16(B)): enter each space's own volume, its share of the box less the space the barrier takes (314.16(A)).

Conductors

Count a conductor that passes through once, and a loop or coil of unbroken conductor at least twice the free length 300.14 requires as two (314.16(B)(1)).

Device Yokes

A device wider than a single 2 in. device box counts as one yoke for each gang it needs (314.16(B)(4)).

Internal Clamps

Clamps add one allowance based on the largest conductor present in the box (NEC 314.16(B)(2)).

Support Fittings

Each type adds one allowance at the largest conductor present (NEC 314.16(B)(3)).

Equipment Grounding

Terminal Blocks

One allowance for each terminal block, NEC 314.16(B)(6)

Box Fill Volume
12 / 13 cu in
NEC 314.16 PASS
#14 conductors2 × 2.00 = 4.00
Device yokes1 × 4.00 = 4.00
Internal clamps (all)1 × 2.00 = 2.00
Equipment grounding (all)1 × 2.00 = 2.00
Total Required12 cu in
Show the math
  1. TABLEThe box: 4x2-1/8x1-7/8, 13 cu in (Table 314.16(A), metal boxes)NEC Table 314.16(A)
  2. MATH#14 conductors: 2 × 2.00 = 4.00 cu inNEC 314.16(B)(1), Table 314.16(B)(1)
  3. MATHDevice yokes: 1 × 4.00 = 4.00 cu inNEC 314.16(B)(4)
  4. MATHInternal clamps (all): 1 × 2.00 = 2.00 cu inNEC 314.16(B)(2)
  5. MATHEquipment grounding (all): 1 × 2.00 = 2.00 cu inNEC 314.16(B)(5)
  6. RESULTTotal required: 12 cu inNEC 314.16(B)
  7. RESULT12 cu in ≤ 13 cu in = PASSNEC 314.16

Each conductor that starts outside the box and ends or is spliced in it counts once, and one that passes through without a splice counts once. A loop or coil of unbroken conductor at least twice the free length 300.14 requires counts twice, so enter it as two. A conductor that never leaves the box, such as a pigtail, does not count. NEC 314.16(B)(1)
Internal cable clamps: one allowance for all of them, at the largest conductor in the box. A connector whose clamp sits outside the box takes none. NEC 314.16(B)(2)

Luminaire studs and hickeys: one allowance for each type present, at the largest conductor in the box. NEC 314.16(B)(3)

Each yoke or strap: two allowances at the largest conductor connected to its device. A device wider than a single 2 in. device box takes two for each gang it needs, so enter one yoke for each gang. NEC 314.16(B)(4)

Ground wires: one allowance for up to four, at the largest ground wire, and a quarter allowance for each one after four. NEC 314.16(B)(5)

Terminal blocks: one allowance for each block, at the largest conductor terminated on it. This tool takes the largest conductor you entered, which covers every conductor that enters the box; a pigtail that never leaves the box is not entered, so where one larger than every entered conductor lands on a block, that block's allowance is at the pigtail's size: add the difference. NEC 314.16(B)(6)

Where this number comes fromIntry Verified
Calculated from
NEC 314.16(B), volumes per Table 314.16(A). Computed from NEC Table 314.16(B)(1) per-conductor volumes and the 314.16(B)(1)-(6) counting rules, against the Table 314.16(A) box volume. See the full receipt ↓
Run with
  • Box4x2-1/8x1-7/8
  • Conductors2 #14 AWG
  • Device yokes1
  • Internal clampsYes
  • Grounds (EGC)1
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit.
Final say
Your AHJ and local amendments have final say. Confirm before rough-in.
What Intry Verified means

Intry Verified · NEC 2023 · Build 525536D · 2026-11-13

12 / 13 cu inPASS

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

How many wires fit in a handy box?

A 4 x 2-1/8 x 1-7/8" deep handy box (13 cu in, NEC Table 314.16(A)) holds 6 #14, 5 #12, or 5 #10 conductors when nothing else is inside. Each conductor takes its volume allowance from NEC Table 314.16(B)(1): 2.00 cu in for #14, 2.25 for #12, 2.50 for #10. So 13 cu in / 2.00 = 6 #14 conductors. Add a device, clamps, or ground and the count drops.

How many wires fit in a handy box with a receptacle?

About 2 #14 or 1 #12 conductors, once you subtract for the device and fittings. In a 4 x 2-1/8 x 1-7/8" deep handy box (13 cu in), one receptacle yoke counts as two conductor allowances (NEC 314.16(B)(4)), all internal clamps together count as one (B)(2), and up to four grounds count as one (B)(5). That is four #14 allowances (8.00 cu in) gone before any conductors, leaving room for 2 #14. This is the number that matters on a real rough-in, not the bare maximum.

How many #12 THHN wires fit in a handy box?

5 #12 conductors fit in a 4 x 2-1/8 x 1-7/8" deep handy box at the NEC 314.16(A) limit. Each #12 counts as 2.25 cu in (Table 314.16(B)(1)), so 13 cu in / 2.25 = 5. With one receptacle, clamps, and a ground, that drops to about 1 #12 conductors.

What is the volume of a handy box?

A handy box comes in a few depths (NEC Table 314.16(A)): 4 x 2-1/8 x 1-1/2" deep is 10.3 cu in, 4 x 2-1/8 x 1-7/8" deep is 13 cu in, 4 x 2-1/8 x 2-1/8" deep is 14.5 cu in. Box fill uses the listed volume, or the value stamped on the box if the manufacturer marks a larger one.

Do devices and grounds count against the wire count in a handy box?

Yes. NEC 314.16(B) counts more than the wires. Each device yoke (a switch or receptacle) counts as two conductors at the largest connected size, all internal clamps together count as one, and up to four grounds count as one (a quarter more for each ground beyond four). That is why the 6-wire bare maximum for a 4 x 2-1/8 x 1-7/8" deep handy box becomes roughly 2 once the box holds a real device.


Wires in Other Boxes

Box passes. What about the pipe feeding it?

Box fill and conduit fill get cited together on inspection. Run the same conductors through the conduit fill calculator before you pull.