NEC 314.16(A)

How Many Wires in a Box

The maximum number of conductors each standard electrical box holds, by wire size, per NEC Table 314.16(A). Plus how devices, clamps, and grounds reduce the count.

Quick answer: Max conductors = box volume ÷ the per-wire allowance (2.00 cu in for #14, 2.25 for #12, 2.50 for #10). An 18 cu in box holds nine #14 or eight #12 with nothing else inside. Each device subtracts two, all clamps subtract one, and up to four grounds subtract one (a quarter more for each beyond four).

Maximum Conductors per Box (NEC 314.16(A))

The most conductors of one size a box holds with no devices, clamps, or grounds. Computed as the box volume divided by the per-conductor allowance from NEC Table 314.16(B)(1).

Maximum number of conductors per standard box by wire size, computed from the box volume and the per-conductor allowance. Per NEC 314.16(A). Check the box shape, not just the dimensions. A round or octagonal box and a square box share the same trade dimensions and hold different volumes: a 4 x 1-1/4 octagonal is 12.5 cu in where the square is 18, so it takes fewer conductors.

Swipe the table sideways to see the rest of its columns. →

Box TypeVolume#14#12#10#8
4 x 1-1/4 round/octagonal12.56554
4 x 1-1/2 round/octagonal15.57665
4 x 2-1/8 round/octagonal21.510987
4 x 1-1/4 square18.09876
4 x 1-1/2 square21.010987
4 x 2-1/8 square30.315131210
4-11/16 x 1-1/4 square25.51211108
4-11/16 x 1-1/2 square29.51413119
4-11/16 x 2-1/8 square42.021181614
3 x 2 x 1-1/2 device7.53332
3 x 2 x 2 device10.05443
3 x 2 x 2-1/4 device10.55443
3 x 2 x 2-1/2 device12.56554
3 x 2 x 2-3/4 device14.07654
3 x 2 x 3-1/2 device18.09876
4 x 2-1/8 x 1-1/210.35443
4 x 2-1/8 x 1-7/813.06554
4 x 2-1/8 x 2-1/814.57654
Masonry 3-3/4 x 2 x 2-1/214.07654
Masonry 3-3/4 x 2 x 3-1/221.010987
FS single gang13.56654
FD single gang18.09876
FS double gang18.09876
FD double gang24.0121098

Volumes in cubic inches. These counts assume all conductors are the same size and the box holds nothing else. Subtract for devices, clamps, and grounds below.


What Subtracts from the Count

A box with a device or fittings holds more than bare wires. Each item below takes conductor-equivalent space (NEC 314.16(B)):

  • Each device yoke (switch, receptacle, dimmer): counts as 2 conductors at the largest wire connected to it; a device wider than a single 2 in. device box counts 2 for each gang it needs.
  • All internal cable clamps together: count as 1 conductor at the largest wire in the box.
  • One to four equipment grounding conductors: count as 1 conductor total at the largest ground (each beyond four adds a quarter).
  • Each type of support fitting (a luminaire stud, a hickey): counts as 1 conductor at the largest wire in the box.
  • Each terminal block: counts as 1 conductor at the largest wire terminated on it.
  • A loop or coil of unbroken conductor at least twice the free length 300.14 requires: counts as 2 conductors.

Example: an 18 cu in box rated for nine #14 wires, once you add a receptacle (2), clamps (1), and a ground (1), has room for only about five actual #14 conductors.

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

How many wires can go in a box?

It depends on the box volume and the wire size. Per NEC 314.16(A), the maximum number of same-size conductors is the box volume divided by the per-conductor allowance: 2.00 cubic inches for #14, 2.25 for #12, 2.50 for #10. An 18.0 cubic inch box holds nine #14 or eight #12 conductors when nothing else is inside. Devices, cable clamps, and grounds each take space and lower the count.

How many wires can I put in a 4-inch square box?

A standard 4 x 1-1/4 inch square box is 18.0 cubic inches and holds nine #14, eight #12, or seven #10 conductors with nothing else inside. A deeper 4 x 2-1/8 square box is 30.3 cubic inches and holds fifteen #14 or thirteen #12. Subtract two conductors for each device (switch or receptacle), one for all clamps together, and one for up to four grounds (a quarter more for each ground beyond four).

How many conductors can a single-gang device box hold?

NEC Table 314.16(A) lists the 3 x 2 x 3-1/2 inch device box (75 x 50 x 90 mm) at 18.0 cubic inches and 9 #14 conductors with nothing else inside (NEC 2023, page 70-196). A single receptacle counts as two conductors and the grounds as one (314.16(B)), which leaves 6: the hot and neutral of 3 14/2 cables, or 2 where the box has internal cable clamps, which count as one more. The 3 x 2 x 2 device box (75 x 50 x 50 mm) is 10.0 cubic inches and holds 5 #14 with nothing else inside.

Do devices and grounds count against the wire limit?

Yes. NEC 314.16(B) counts more than just the wires. Each device yoke (a switch or receptacle) counts as two conductors at the largest connected wire size. All internal cable clamps together count as one. Up to four equipment grounding conductors count as one (a quarter more for each ground beyond four). So a box rated for nine #14 wires might only fit five actual conductors once you add a receptacle, clamps, and a ground. Use the box fill calculator to account for all of it.

What happens if I overfill a box?

An overfilled box is a code violation (NEC 314.16) and a real hazard. Too many conductors trap heat, make reliable connections hard, and force wires against sharp edges where the insulation can be nicked. The fix is a larger box, a marked extension ring or fewer items in this one, not cramming. Calculate the fill before you rough in so you install the right box the first time.


Related Calculators

Know the count. Now check the real box.

The max-conductor chart is the bare-wire ceiling. Run your actual devices, clamps, and grounds through the box fill calculator to confirm the box you picked passes NEC 314.16.