HVAC Serial Number Lookup

Friedrich Serial Number Lookup

Friedrich has its own serial number formats; the rows below say which are read from the manufacturer's own document. Enter the serial from the data plate below to get the manufacture date with a character-by-character explanation, the unit's age, its refrigerant era, and the warranty picture.

Quick answer: Friedrich serial numbers (2017 to present): 10 characters; digits 1-2 = the year, digits 3-4 = the month, character 5 = a factory or product-line letter this tool does not read, digits 6-10 = the production sequence. Example: 1712M00001 = December 2017.

Starting the decoder. The serial formats, the refrigerant timeline and the warranty terms further down this page are already loaded, so you can read yours off them now.

7 of the 41 decode rules rest on a single secondary reference. Where two agree, that is weaker evidence than it looks: secondary references copy one another, and agreement between two is not a manufacturer document being read. Some of the formats on this page are read from the manufacturer's own document; the others rest on secondary references, and each row below says which. A date stamped or printed on the data plate always outranks a serial decode.


Friedrich Serial Number Formats

FormatEraExampleConfidence
10 characters; digits 1-2 = the year, digits 3-4 = the month, character 5 = a factory or product-line letter this tool does not read, digits 6-10 = the production sequenceManufacturer documents, held as retained copies. No secondary reference is relied on. Character 5 is labelled differently across Friedrich's own manuals and is never read.2017 to present1712M00001 = December 2017high
9 characters, four letters then 5 digits; letters 1-2 = the year pair, letter 3 = the month, letter 4 = the product line, digits 5-9 = the production runA manufacturer document, held as a retained copy. No secondary reference is relied on. The year pair and the month letter are decoded; the product-line letter is labelled and not enumerated, so it is not.2009 to 2017AKAM00001 = January 2010high
2 digits + letter + 6 digits; digits 1-2 = year. Year only; the month letter is not decoded hereCross-checked across 2 secondary references, not a manufacturer document. Year only.older units (~1990s)92J010915 = 1992medium

Some older or conflicting Friedrich formats are recognized but deliberately not decoded; the decoder explains why when it sees one instead of guessing.


Worked Example: Friedrich 1712M00001

Expected decode: December 2017. Character by character:

December 2017

17 = year 2017 (digits 1-2, Friedrich's own Serial Number Reference Guide)

12 = December (digits 3-4)

M at position 5 and 00001 at positions 6-10 carry no date. Friedrich labels position 5 differently across its own manuals, so this tool does not read it

Friedrich serials on government surplus listings

On these, the year is one a seller entered beside the serial in the listing's description, not a year the manufacturer or a public record states, so it is a weaker check than a public record. “The decoder reads” is what the serial lookup on this page returns for the serial, worked out when this page was built in 2026. The listings are not named here, because a seller's entry is not a citation. 1 serial; the decoder reads 1 of 1 as the year listed.

SerialEquipment, as listedYear a seller enteredThe decoder readsAgainst the year listed
AFLP00443ZoneAire Premier portable unit2016November 2016Same year

Reading Friedrich model numbers

The Friedrich lines the tonnage decoder reads or identifies, each from the maker document its row names; an example opens on the tonnage decoder.

Each line is identified from the maker document in its Document column. The example is a model in that line's layout, and the reading is what the tonnage decoder returns for it.
LineExample modelWhat the tonnage decoder readsDocument
Friedrich ZoneAire Select PTAC/PTHPPZH07K3SBA Friedrich ZoneAire Select packaged terminal unit (PTAC or PTHP): its legend prints this code in BTU/h, not a whole, half or quarter ton, so no tonnage is published94151400_09, 945152001_00
Friedrich FreshAire PTAC/PTHPPVH09K3FAA Friedrich FreshAire packaged terminal unit (PTAC or PTHP): 0.75 tons (9,000 BTU/h)94131400_06
Friedrich ZoneAire Premier PTAC/PTHPPDH07K3SGAA Friedrich ZoneAire Premier packaged terminal unit (PTAC or PTHP): its legend prints this code in BTU/h, not a whole, half or quarter ton, so no tonnage is published94141400_04
Friedrich Vert-I-PakVHA09K34RTQA Friedrich Vert-I-Pak single package vertical unit: 0.75 tons (9,000 BTU/h)95992013_03, 95992014_03, 95992012_06, VPAK Product Profile FFR-104 Rev 02 092026
Friedrich Kuhl and WallmasterKCM21B30AA Friedrich Kuhl or Wallmaster room unit: identified, no size is read93001406_01

Friedrich Refrigerant Timeline

Manufacture yearRefrigerant the years point toNotes
through 1995R-22R-22 was the standard refrigerant for equipment of this age. R-410A did not become an EPA-accepted substitute for HCFC-22 in household and light commercial air conditioning until February 8, 1996, so a unit built before then predates it. Standard refrigerant of the era. EPA ended U.S. production and import of R-22 on January 1, 2020; an existing system can still be serviced with recycled, reclaimed or previously produced R-22.
1996 to 2024R-22 or R-410AFriedrich room, window, and PTAC units in this window ran R-22 or R-410A. No Friedrich document held here dates the change, so the year does not tell which; read the refrigerant on the nameplate.
2025 and laterR-32Friedrich moved Chill Premier, Uni-Fit, Kuhl, and PDH PTAC lines to A2L-compliant R-32 for 2025.

The refrigerant printed on the nameplate is authoritative. This timeline reads each year range from the EPA dates and maker notes in its Notes column; it tells you what the age points to, not what is in a specific unit.


Friedrich Warranty Terms

Friedrich warranty lookup

No page of Friedrich's own for looking up a warranty is linked here, and this page does not read any maker's records, so it cannot show whether a unit was registered.

What this page works out is the next question. Enter the serial and the model number in the lookup on this page and the result works out the parts term the Friedrich warranty certificates held here print for that build date, naming the edition and quoting its clause, or says plainly why it cannot and what would answer it. It asks only for answers that would change a line it shows, each naming the line it moves, and a Service Brief carries the result to whoever works on the unit.

The Friedrich warranty terms held here

2 Friedrich single package vertical (Vert-I-Pak) warranty certificate editions covering Friedrich are held here, from VERT-I-PAK A SERIES (footer code 11-10) to VERT-I-PAK A SERIES (footer code 11-19). Every one prints a base parts term of 1 year for its parts row. They start the term at installation, or at shipment plus a set time when the install date cannot be shown (a date no serial gives). They do not pay for "Parts or labor provided by anyone other than an authorized service center." For a Friedrich PTAC no parts term is worked out: its dated PTAC certificates held here include one per series (SG (9-12), PZ (9-14), PV (10-17) and PD (8-20)), each printing two years on parts (PV-SERIES PACKAGED TERMINAL AIR CONDITIONERS LIMITED WARRANTY (10-17): "LIMITED WARRANTY - TWO YEAR (Twenty-four (24) months from the date of installation)."), while the undated PZ-SERIES warranty in Friedrich's ZoneAire installation manual prints "LIMITED WARRANTY - FIRST YEAR (Twelve (12) months from the date of installation)."

Enter the serial and the model number above: the result works out the base parts term only for the models these certificates list (VERT-I-PAK A SERIES (footer code 11-10): VEA, VHA; VERT-I-PAK A SERIES (footer code 11-19): VHA), where a held edition is dated before the build and one after it, each with the edition it rests on, and dates a window only from an install month given; otherwise it says so and names what would answer it. For a Friedrich PTAC it quotes the two parts terms Friedrich's documents print and works none out.

Source: the maker's own limited warranty certificates, each identified by the part number printed on it; the serial result names the edition each term comes from, and the statute where a line quotes one.

The Friedrich certificate editions held here

Each is listed by the identifier and the date or code printed on it.

  • VERT-I-PAK A SERIES (footer code 11-10): VERT-I-PAK® A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONERS LIMITED WARRANTY
  • VERT-I-PAK A SERIES (footer code 11-19): VERT-I-PAK® A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONERS LIMITED WARRANTY

Frequently Asked Questions

How old is my Friedrich unit?

Decode the serial number from the data plate. The dominant Friedrich format (2017 to present) is: 10 characters; digits 1-2 = the year, digits 3-4 = the month, character 5 = a factory or product-line letter this tool does not read, digits 6-10 = the production sequence. Example: 1712M00001 decodes to December 2017. Subtract the decoded year from the current year for the age.

Has the Friedrich serial decode been checked against serials somebody else dated?

Friedrich PTAC letter-led year pair: Read against 1 serial where a seller entered a year beside the serial in the listing's description on a government surplus listing for the serial (government surplus auction listings), ZoneAire premier portable unit: 1 matched the reading shown first; a seller's year is shown here for the record and is not counted toward this format's check.

No serial with a date published outside this tool has produced a reading through the Friedrich year and month digits format yet. That format is read from a document published by the company that built the unit.

No serial with a date published outside this tool has produced a reading through the Friedrich leading 2-digit year format yet. No document from the company that built the unit is held for it, so the rule rests on the secondary references this tool records.

What refrigerant does a Friedrich unit use?

By manufacture year: through 1995: R-22; 1996 to 2024: R-22 or R-410A; 2025 and later: R-32. The refrigerant printed on the nameplate is authoritative; the year-based mapping tells you what the age points to, not what is in a specific unit.

How do I look up my Friedrich warranty?

No page of Friedrich's own for looking up a warranty is linked here, and this page does not read any maker's records, so it cannot show whether a unit was registered. What this page works out is the next question. Enter the serial and the model number in the lookup on this page and the result works out the parts term the Friedrich warranty certificates held here print for that build date, naming the edition and quoting its clause, or says plainly why it cannot and what would answer it. It asks only for answers that would change a line it shows, each naming the line it moves, and a Service Brief carries the result to whoever works on the unit.

Is my Friedrich unit still under warranty?

2 Friedrich single package vertical (Vert-I-Pak) warranty certificate editions covering Friedrich are held here, from VERT-I-PAK A SERIES (footer code 11-10) to VERT-I-PAK A SERIES (footer code 11-19). Every one prints a base parts term of 1 year for its parts row. They start the term at installation, or at shipment plus a set time when the install date cannot be shown (a date no serial gives). They do not pay for "Parts or labor provided by anyone other than an authorized service center." For a Friedrich PTAC no parts term is worked out: its dated PTAC certificates held here include one per series (SG (9-12), PZ (9-14), PV (10-17) and PD (8-20)), each printing two years on parts (PV-SERIES PACKAGED TERMINAL AIR CONDITIONERS LIMITED WARRANTY (10-17): "LIMITED WARRANTY - TWO YEAR (Twenty-four (24) months from the date of installation)."), while the undated PZ-SERIES warranty in Friedrich's ZoneAire installation manual prints "LIMITED WARRANTY - FIRST YEAR (Twelve (12) months from the date of installation)." Enter the serial and the model number above: the result works out the base parts term only for the models these certificates list (VERT-I-PAK A SERIES (footer code 11-10): VEA, VHA; VERT-I-PAK A SERIES (footer code 11-19): VHA), where a held edition is dated before the build and one after it, each with the edition it rests on, and dates a window only from an install month given; otherwise it says so and names what would answer it. For a Friedrich PTAC it quotes the two parts terms Friedrich's documents print and works none out.

Why do some Friedrich serial numbers refuse to decode?

A ten-character Friedrich serial that begins with a letter is not a layout Friedrich prints in any of the service manuals this tool holds, so this tool reads no date from it. Read the date printed on the data plate, or contact Friedrich with the serial. Friedrich's PTAC Serial Number Identification Guide reads a letter-led serial as four printed groups: one of nine year pairs covering 2009 through 2017, one of twelve month letters (A through M, with I skipped), a product-line letter the chart names but does not enumerate, and a five-digit production run. This serial does not sit inside those groups, so this tool reads no date from it. Read the date printed on the data plate, or contact Friedrich with the serial. Friedrich's own Serial Number Reference Guide reads this ten-character layout as a year, a month, one character Friedrich labels differently across its own manuals, and a sequence, from 2017 onward up to the current year. The leading four digits here do not resolve to a month in that window, so this tool reads no date from them. If the unit is not a Friedrich, choose its brand instead; otherwise read the date printed on the data plate or contact Friedrich with the serial.