NEC Chapter 9 Conduit Fill
How Many Wires Fit in 3/4" PVC?
The maximum THHN conductors per wire size in 3/4 inch PVC (Schedule 40 PVC) at the NEC 40% fill limit, with the math and the interactive calculator for any mix of wires.
Max THHN Conductors in 3/4" PVC (NEC Table 1 Fill Limit)
Maximum number of same-size THHN/THWN-2 conductors in 3/4 inch PVC at the NEC Chapter 9 40% fill limit. Count the equipment ground as a conductor.
Maximum THHN conductors in 3/4 inch PVC at 40% fill, by wire size
Swipe the table sideways to see the rest of its columns. →
| Wire Size (THHN) | Max Conductors | Area Each (sq in) |
|---|---|---|
| #14 AWG | 21 | 0.0097 |
| #12 AWG | 15 | 0.0133 |
| #10 AWG | 9 | 0.0211 |
| #8 AWG | 5 | 0.0366 |
| #6 AWG | 4 | 0.0507 |
| #4 AWG | 2 | 0.0824 |
Based on 3/4 inch PVC internal area 0.508 sq in (NEC Chapter 9 Table 4). One conductor allows 53% fill, two allow 31%, three or more allow 40% (Table 1).
Mixed Wire Sizes? Calculate It
The chart is for one wire size at a time. For a real pull with mixed sizes, insulation types, or other conduit, enter your exact conductors for the precise fill percentage. The calculator opens on 3/4" PVC.
Within fill: 7.9% of 40%, room for 12 more #12
Show the math
- GIVENConduit: 3/4" PVC Schedule 40; 3 conductors
- TABLE#12 AWG THHN: 0.0133 sq in each × 3 = 0.0399 sq inNEC Chapter 9 Table 5
- MATHTotal conductor area: 0.0399 sq inNEC Chapter 9 Table 5
- TABLE3/4" PVC Schedule 40 total area: 0.5080 sq inNEC Chapter 9 Table 4
- TABLEFill limit for 3+ conductors: 40%, an allowable area of 0.2032 sq inNEC Chapter 9 Table 1
- MATHFill = 0.0399 / 0.5080 × 100 = 7.9%NEC Chapter 9 Table 1
- RESULTFill: 7.9% of a 40% limitNEC Ch. 9 Tables 1, 4, 5
- RESULTStatus: NEC PASSNEC Ch. 9 Tables 1, 4, 5
Where this number comes fromIntry Verified
- Calculated from
- NEC Ch. 9 Tables 1, 4, 5. Computed from NEC Chapter 9 Table 1 (fill percent), Table 4 (conduit area) and Table 5 (conductor area), with Note 7's round-up at a decimal of 0.8 or more for conductors all of one size. See the full receipt ↓
- Run with
- Conduit3/4" PVC40
- Conductors3 #12 AWG THHN
- Fill limit40%
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit.
- Final say
- Your AHJ and local amendments have final say. Confirm before rough-in.
Intry Verified · NEC 2023 · Build 525536D · 2026-11-13
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
How many wires fit in 3/4 inch PVC?
Applying the NEC Chapter 9, Table 1 fill limit for the resulting number of conductors (53% for one, 31% for two, 40% for three or more), 3/4 inch PVC (internal area 0.508 sq in) holds 15 #12 THHN, 21 #14, 9 #10, or 5 #8 conductors. For three or more conductors the math is the conduit area times 0.40 (0.508 × 0.40 = 0.203 sq in allowable), divided by the conductor's area from NEC Chapter 9 Table 5.
How many 12 AWG THHN wires fit in 3/4 inch PVC?
15 #12 THHN conductors fit in 3/4 inch PVC at the 40% fill limit. Each #12 THHN is 0.0133 sq in, so 0.203 sq in allowable ÷ 0.0133 rounds to 15 conductors (NEC Chapter 9 Note 7 rounds up when the decimal is 0.8 or more). The same count applies to THWN-2, which has the identical area.
How many #10 THHN wires fit in 3/4 inch PVC?
9 #10 THHN conductors fit in 3/4 inch PVC at the NEC 40% fill limit. Each #10 THHN is 0.0211 sq in, so 0.203 sq in allowable (0.508 × 0.40) ÷ 0.0211 rounds to 9 conductors (NEC Chapter 9 Note 7). THWN-2 has the identical area and gives the same count. Count the equipment ground as a conductor.
How many 14 AWG wires fit in 3/4 inch PVC?
21 #14 THHN conductors fit in 3/4 inch PVC at 40% fill. Each #14 THHN is 0.0097 sq in, so 0.203 sq in ÷ 0.0097 rounds to 21 (NEC Chapter 9 Note 7). Remember the ground counts as a conductor, and more than three current-carrying conductors trigger ampacity derating per NEC 310.15(C)(1).
What is the fill limit for 3/4 inch PVC?
The maximum fill depends on how many conductors are in the raceway (NEC Chapter 9, Table 1): 53% for one conductor, 31% for two, and 40% for three or more. For 3/4 inch PVC (internal area 0.508 sq in, Schedule 40 PVC) that is 0.269 sq in for one wire, 0.157 sq in for two, and 0.203 sq in for three or more. The 40% case is the common one.
Fill for Other PVC Sizes
Wires in 1/2" PVC
8 #12 THHN and the full count for 1/2 inch pipe.
Wires in 1" PVC
25 #12 THHN and the full count for 1 inch pipe.
Wires in 1-1/4" PVC
43 #12 THHN and the full count for 1-1/4 inch pipe.
Wires in 1-1/2" PVC
59 #12 THHN and the full count for 1-1/2 inch pipe.
Wires in 2" PVC
99 #12 THHN and the full count for 2 inch pipe.
Wires in 2-1/2" PVC
141 #12 THHN and the full count for 2-1/2 inch pipe.
Wires in 3" PVC
218 #12 THHN and the full count for 3 inch pipe.
Wires in 3-1/2" PVC
293 #12 THHN and the full count for 3-1/2 inch pipe.
Wires in 4" PVC
377 #12 THHN and the full count for 4 inch pipe.
3/4" in Other Conduit Types
The same 3/4 inch trade size holds a different number of wires depending on the conduit type, because each has a different internal area (NEC Chapter 9 Table 4).
3/4" EMT Fill
16 #12 THHN (EMT (electrical metallic tubing), 0.533 sq in).
3/4" RMC Fill
16 #12 THHN (RMC (rigid metal conduit), 0.549 sq in).
3/4" IMC Fill
17 #12 THHN (IMC (intermediate metal conduit), 0.586 sq in).
3/4" PVC-80 Fill
12 #12 THHN (Schedule 80 PVC, 0.409 sq in).
3/4" ENT Fill
15 #12 THHN (ENT (electrical nonmetallic tubing), 0.508 sq in).
Conduit Fill Chart (all sizes)
Max THHN per conduit size from #14 to 500 kcmil in one table.
Fill checks out. Will the wire reach?
Getting the conductors in the pipe is one thing. Confirm the gauge holds up over distance with the voltage drop calculator before you pull.