NEC Chapter 9 Conduit Fill

How Many Wires Fit in 1/2" RMC?

The maximum THHN conductors per wire size in 1/2 inch RMC (RMC (rigid metal conduit)) at the NEC 40% fill limit, with the math and the interactive calculator for any mix of wires.

Quick answer: 1/2 inch RMC (internal area 0.314 sq in) holds 9 #12 THHN, 13 #14, 6 #10, or 3 #8 conductors at the 40% fill limit for three or more wires. Allowable fill area = 0.314 × 0.40 = 0.126 sq in.

Max THHN Conductors in 1/2" RMC (NEC Table 1 Fill Limit)

Maximum number of same-size THHN/THWN-2 conductors in 1/2 inch RMC at the NEC Chapter 9 40% fill limit. Count the equipment ground as a conductor.

Maximum THHN conductors in 1/2 inch RMC at 40% fill, by wire size

Swipe the table sideways to see the rest of its columns. →

Wire Size (THHN)Max ConductorsArea Each (sq in)
#14 AWG130.0097
#12 AWG90.0133
#10 AWG60.0211
#8 AWG30.0366
#6 AWG20.0507
#4 AWG10.0824

Based on 1/2 inch RMC internal area 0.314 sq in (NEC Chapter 9 Table 4). One conductor allows 53% fill, two allow 31%, three or more allow 40% (Table 1).


Mixed Wire Sizes? Calculate It

The chart is for one wire size at a time. For a real pull with mixed sizes, insulation types, or other conduit, enter your exact conductors for the precise fill percentage. The calculator opens on 1/2" RMC.

12.7%
conduit fill
NEC PASSThreshold: 40% (3+ conductors)

Within fill: 12.7% of 40%, room for 6 more #12

#12 AWG THHN × 30.0399 sq in
Total conductor area0.0399 sq in
Conduit area (1/2" RMC)0.3140 sq in
Remaining space0.0857 sq in
Quick Reference: Maximum #12 AWG THHN in 1/2" RMC: 9
Show the math
  1. GIVENConduit: 1/2" RMC; 3 conductors
  2. TABLE#12 AWG THHN: 0.0133 sq in each × 3 = 0.0399 sq inNEC Chapter 9 Table 5
  3. MATHTotal conductor area: 0.0399 sq inNEC Chapter 9 Table 5
  4. TABLE1/2" RMC total area: 0.3140 sq inNEC Chapter 9 Table 4
  5. TABLEFill limit for 3+ conductors: 40%, an allowable area of 0.1256 sq inNEC Chapter 9 Table 1
  6. MATHFill = 0.0399 / 0.3140 × 100 = 12.7%NEC Chapter 9 Table 1
  7. RESULTFill: 12.7% of a 40% limitNEC Ch. 9 Tables 1, 4, 5
  8. RESULTStatus: NEC PASSNEC Ch. 9 Tables 1, 4, 5
Where this number comes fromIntry Verified
Calculated from
NEC Ch. 9 Tables 1, 4, 5. Computed from NEC Chapter 9 Table 1 (fill percent), Table 4 (conduit area) and Table 5 (conductor area), with Note 7's round-up at a decimal of 0.8 or more for conductors all of one size. See the full receipt ↓
Run with
  • Conduit1/2" RMC
  • Conductors3 #12 AWG THHN
  • Fill limit40%
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit.
Final say
Your AHJ and local amendments have final say. Confirm before rough-in.
What Intry Verified means

Intry Verified · NEC 2023 · Build 525536D · 2026-11-13

12.7% fillNEC PASS

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

How many wires fit in 1/2 inch RMC?

Applying the NEC Chapter 9, Table 1 fill limit for the resulting number of conductors (53% for one, 31% for two, 40% for three or more), 1/2 inch RMC (internal area 0.314 sq in) holds 9 #12 THHN, 13 #14, 6 #10, or 3 #8 conductors. For three or more conductors the math is the conduit area times 0.40 (0.314 × 0.40 = 0.126 sq in allowable), divided by the conductor's area from NEC Chapter 9 Table 5.

How many 12 AWG THHN wires fit in 1/2 inch RMC?

9 #12 THHN conductors fit in 1/2 inch RMC at the 40% fill limit. Each #12 THHN is 0.0133 sq in, so 0.126 sq in allowable ÷ 0.0133 rounds to 9 conductors (NEC Chapter 9 Note 7 rounds up when the decimal is 0.8 or more). The same count applies to THWN-2, which has the identical area.

How many #10 THHN wires fit in 1/2 inch RMC?

6 #10 THHN conductors fit in 1/2 inch RMC at the NEC 40% fill limit. Each #10 THHN is 0.0211 sq in, so 0.126 sq in allowable (0.314 × 0.40) ÷ 0.0211 rounds to 6 conductors (NEC Chapter 9 Note 7). THWN-2 has the identical area and gives the same count. Count the equipment ground as a conductor.

How many 14 AWG wires fit in 1/2 inch RMC?

13 #14 THHN conductors fit in 1/2 inch RMC at 40% fill. Each #14 THHN is 0.0097 sq in, so 0.126 sq in ÷ 0.0097 rounds to 13 (NEC Chapter 9 Note 7). Remember the ground counts as a conductor, and more than three current-carrying conductors trigger ampacity derating per NEC 310.15(C)(1).

What is the fill limit for 1/2 inch RMC?

The maximum fill depends on how many conductors are in the raceway (NEC Chapter 9, Table 1): 53% for one conductor, 31% for two, and 40% for three or more. For 1/2 inch RMC (internal area 0.314 sq in, RMC (rigid metal conduit)) that is 0.166 sq in for one wire, 0.097 sq in for two, and 0.126 sq in for three or more. The 40% case is the common one.


Fill for Other RMC Sizes


1/2" in Other Conduit Types

The same 1/2 inch trade size holds a different number of wires depending on the conduit type, because each has a different internal area (NEC Chapter 9 Table 4).

Fill checks out. Will the wire reach?

Getting the conductors in the pipe is one thing. Confirm the gauge holds up over distance with the voltage drop calculator before you pull.