Electrical / runnable MCP tool

Run the Conduit Fill Calculator in your AI assistant

Through the free Intry MCP server, Claude, ChatGPT, or Cursor runs this exact calculator and hands back a verdict and the cited source, not a guess. Tool name: conduit_fill.

What it runs: Whether your wires fit the pipe, how full it ends up, and the next size up if they do not.

What you get back: fill %, the limit, remaining capacity, jam risk, and the next size up if over.

How it computes the answer

Computed from NEC Chapter 9 Table 1 (fill percent), Table 4 (conduit area) and Table 5 (conductor area), with Note 7's round-up at a decimal of 0.8 or more for conductors all of one size.

What it cites

Your assistant calls the same engine the interactive calculator calls, with the inputs listed under Inputs. These are the sources that engine reads.

NEC Chapter 9, Table 1
Maximum percent of conduit cross-section that may be filled: 53% for one conductor, 31% for two, 40% for three or more, and the Note 4 nipple allowance (60%) for a nipple not over 600 mm (24 in.) installed between boxes, cabinets, and similar enclosures. Read from the primary.
NEC Chapter 9, Table 4
Internal cross-sectional area of each conduit and tubing type by trade size, for the raceway types this tool supports (EMT, IMC, RMC, PVC-40, PVC-80, ENT); the usable area is that internal area times the Table 1 percentage. Read from the primary.
NEC Chapter 9, Table 5
Approximate cross-sectional area of each insulated conductor by AWG/kcmil and insulation type (THHN/THWN, XHHW, and others). Read from the primary.
NEC Chapter 9, Note 7
The rounding rule for conductors all of one size, quoted from the printed page (NFPA 70-2023, page 70-715): "When calculating the maximum number of conductors or cables permitted in a conduit or tubing, all of the same size (total cross-sectional area including insulation), the next higher whole number shall be used to determine the maximum number of conductors permitted when the calculation results in a decimal greater than or equal to 0.8. When calculating the size for conduit or tubing permitted for a single conductor, one conductor shall be permitted when the calculation results in a decimal greater than or equal to 0.8." So a set whose conductors all share one area passes at the Note 7 count even where its percent reads a little over the Table 1 limit, and the result says Note 7 is why. A set of different sizes keeps the plain percent, as Note 6 directs. The one-size counts match the counts Annex C Table C.1 prints for EMT with THHN conductors (page 70-775).

The code sections those sources name, each with the edition and the page the book prints it on:

Swipe the table sideways to see the rest of its columns. →

Code and editionSectionPrinted page
NEC 2023Chapter 9 Table 170-715
NEC 2023Chapter 9 Table 470-716
NEC 2023Chapter 9 Table 570-720
NEC 2023Chapter 9 Note 770-715

These are NEC Chapter 9 table values, looked up and summed by the engine for the conductors you enter, not measurements. The result is the code fill calculation; the installer still confirms the actual conductors and raceway on site.

The full receipt, with every source and how each is cross-checked, is on the interactive Conduit Fill Calculator.

Ask your assistant

The one rule that makes it reliable: name Intry in your question. That is what tells Claude to run the conduit_fill tool and answer with the real number, the verdict, and the citation. Leave Intry out and Claude may just guess from memory, which is exactly what you are trying to avoid. Type something like:

“Ask Intry if nine #12 THHN fit in 3/4 inch EMT or I need to go up a size.”
“Use Intry to get the fill percentage for six #10 and three #8 in 1 inch PVC40.”

Inputs

Swipe the table sideways to see the rest of its columns. →

FieldRequiredAcceptsRangeWhat it is
conduitTypeyesEMT, IMC, RMC, PVC40, PVC80, ENTEMT, IMC, RMC, PVC40, PVC80, or ENT.
conduitSizeyes1/2, 3/4, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3, 3-1/2, 4Trade size, e.g. '3/4'.
nippleoptionalbooleanIs this a nipple ≤24" (60% fill, no derate)? Default false.
conductorsyesarray of { size: 1 | 2 | 3 | 4 | 6 | 8 | 10 | 12 | 14 | 250 | 300 | 350 | 400 | 500 | 600 | 700 | 750 | 800 | 900 | 1000 | 1/0 | 2/0 | 3/0 | 4/0; insulation: THHN | THWN-2 | XHHW | XHHW-2 | RHH* | RHW* | RHW-2* | TW | THW; qty: number }Conductors in the raceway.

Add Intry to Claude

One paste and Claude can run this tool and the other calculators on Intry's MCP server, right from your phone.

Add Intry to ClaudeOpens Claude with Intry already filled in.
  1. Claude opens with the Intry connector already filled in. Review it and click Add.
  2. (If a field is blank, paste the link below into the URL field.)
  3. In any chat, tap + then Connectors and switch Intry on. Then name Intry in your question (“use Intry to…”) so Claude runs the tool instead of guessing.
https://www.intrysys.com/api/mcp

No login, no API key, and it works on every Claude plan, right from your phone.

Using ChatGPT, Cursor, or a dev tool? See the developer setup on the main page. The endpoint is https://www.intrysys.com/api/mcp.

Every answer comes with the cited NEC section, so you can check it or show an inspector. The numbers come from the same calculator we run on intrysys.com, and our automated checks hold its answers against their sources before anything goes live, for the cases the checks cover, not for every input you can enter.

Also on Intry