Electrical Calculator

Electrical Load Calculator: NEC 220.82 & 220.87

NEC 220.82 service sizing and the 220.87 existing-load check: whether this panel has room for the EV charger or heat pump you are adding.

Field brief
Size a servicethe 220.82 optional method: 100% of the first 10 kVA plus 40% of the remainder, add the largest heating or cooling load, divide by 240 V.NEC 220.82
Can it take more?the 220.87 existing-panel check: 125% of the highest metered demand over 12 months plus the new load must not exceed the service rating.NEC 220.87
EV or heat pumpthe electrification-era question: whether an existing service has the headroom for a new EV charger or heat pump.headroom?

Intry VerifiedA worked default reading, traceable end to end: what it was calculated from, what it was run with, how it was checked, and who has final say.

125 A service125 A service, 101.8 A load
Where this number comes fromIntry Verified
Calculated from
NEC 220.82. Computed from NEC 220.82 (new-service) or 220.87 (existing-panel) demand, with the EV charger added at 100% per 220.57, sized up to a 240.6(A) standard service rating. See the full receipt ↓
Run with
  • Floor area2,000 sqft
  • Small-appliance / laundry2 + 1 circuits
  • Fixed appliances5 items
  • Heating / coolingAir conditioning / cooling only, 4,800 VA
  • EV chargerNone
  • Service voltage240 V
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 30703 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from the cited NEC section. This is our own deterministic gate, not a third-party audit.
Final say
Your AHJ and local amendments have final say. Confirm before rough-in.
What Intry Verified means

Intry Verified · NEC 2023 · Build D32B7B5 · 2026-10-09

Formulas follow NEC 2023 (NFPA 70-2023) 220.82, 220.57, and 220.87. Local amendments change these numbers, and a permit-grade calculation belongs to a licensed electrician working from your jurisdiction's adopted edition; the AHJ has the final word.

New: run this inside your AI assistant

Prefer to just ask? Add this to Claude, free.

Connect Intry to Claude once, then just say “use Intry to…” to run the load calculator from a plain-English question, on your phone, on the job. You get the number (computed live, not guessed), what it means, and the cited NEC section. Works on every Claude plan.

Use this in Claude

The Six Heating/Cooling Options, NEC 220.82(C)

The optional method adds the largest of these six to the demand-factored general load. Heating and cooling never run at the same time, so only the biggest scenario counts, and this bucket gets no further demand factor.

The six NEC 220.82(C) heating and cooling load options; count only the largest that applies to the dwelling. Source: NEC (NFPA 70-2023) 220.82(C).
220.82(C)SituationWhat you count
(1)Air conditioning / cooling only100% of the air-conditioning and cooling equipment nameplate
(2)Heat pump without supplemental heat100% of the heat pump nameplate when used without supplemental electric heat
(3)Heat pump with supplemental electric heat100% of the compressor nameplate plus 65% of the supplemental electric heat
(6)Electric thermal storage heating100% where the usual load is expected to be continuous at full nameplate
(4)Electric space heat, fewer than 4 units65% of nameplate with fewer than four separately controlled units
(5)Electric space heat, 4 or more units40% of nameplate with four or more separately controlled units

Option (3) note: the code also addresses compressors interlocked so the compressor and the supplemental heat cannot run at the same time (the compressor then does not have to be added to the supplemental heat). Verify that wording in your copy of the book; this calculator conservatively counts both.


Adding Loads Without Metering Data: NEC 220.83

The code also addresses a third path. For a dwelling unit served by a 120/240-volt or 208Y/120-volt, 3-wire service or feeder, 220.83 lets you total the existing plus new loads with its own demand factors, an alternative to 220.87 that needs no metering data:

NEC 220.83 demand factors for adding load to an existing dwelling. Source: NEC 2023 (NFPA 70) 220.83.
CaseDemand factors
220.83(A): no additional AC or electric space heating being installedFirst 8 kVA of the total at 100%, remainder at 40%
220.83(B): additional AC or electric space heating IS being installedAir conditioning at 100%, central electric space heating at 100%, and fewer than four separately controlled space-heating units at 100%, counting only the larger of the air-conditioning or space-heating load, not both; all other loads at first 8 kVA 100% + 40% remainder

Read from the code itself: NEC 2023 (NFPA 70) 220.83. The (B) table has no row for four or more separately controlled space-heating units, such as baseboard heat in four or more rooms, so this page gives no percentage for that case. When 12 months of utility data exists, 220.87 (the calculator's second mode) is usually the stronger answer: measured reality beats estimated loads.


Three Ways to Answer "Will It Fit"

New or replacement service: 220.82. The optional method builds the load from scratch: square footage, circuits, appliance nameplates, then a steep demand factor (100% of the first 10 kVA, 40% of the rest) because no house runs everything at once. Heating and cooling ride on top at the largest of six options, and an EV charger adds the larger of 7,200 VA or its nameplate per 220.57. It applies to dwellings on a single 120/240 V or 208Y/120 V, 3-wire service of 100 A or more, per 220.82(A).

Existing panel with demand data: 220.87. This is the section built for the electrification era, and almost nobody has a tool for it. Instead of estimating, it uses what the house actually drew: the highest demand over 12 months of utility metering, or a 30-day recording under the exception. Multiply that peak by 125%, add the new load, and compare to the service rating. Because real demand is usually far below the calculated load, 220.87 regularly proves a 100 or 125 A panel can take a charger that a from-scratch calculation would reject.

Existing panel, no metering data: 220.83. The table above. More conservative than 220.87, less work than gathering 30 days of recordings. This calculator does not implement it yet; the table gives you the shape of the math.

The EV Charger Wrinkle in NEC 2023

NEC 2023 added 220.57 (EVSE at the larger of 7,200 VA or nameplate) but never said explicitly whether that number may ride the 40% second tier inside the 220.82 optional method or must be added at 100%. Practitioners argue both readings on the forums. This calculator adds EVSE at 100%, outside the 40% tier, for two reasons: it is the conservative reading of 2023, and the 2026 edition resolves the debate in exactly that direction with new 120.82(D), which counts EVSE at 100% of nameplate with no demand factor. Related: 220.53 explicitly excludes EVSE from the dwelling fixed-appliance demand factor, so there is no discount hiding there either.


Worked Examples

Example 1: 2,000 sqft house, full 220.82 calculation

General loads per 220.82(B): lighting and receptacles at 3 VA x 2,000 sqft = 6,000 VA. Circuits: 1,500 VA x 3 (two small-appliance plus one laundry) = 4,500 VA. Fixed appliances at nameplate: range 12,000 + water heater 4,500 + dryer 5,000 + dishwasher 1,200 + disposal 900 = 23,600 VA. General total: 6,000 + 4,500 + 23,600 = 34,100 VA.

Demand factor: 100% of the first 10,000 VA plus 40% of the remaining 24,100 VA. 10,000 + 0.40 x 24,100 = 10,000 + 9,640 = 19,640 VA.

HVAC per 220.82(C)(1): a 4,800 VA air conditioner at 100% adds 4,800 VA. Calculated load: 19,640 + 4,800 = 24,440 VA. Amps: 24,440 / 240 = 101.8 A. That clears 100 A by less than 2 A, so the sensible spec is a 125 A service, and remember 220.82(A) does not permit this method below 100 A in the first place.

Example 2: 200 A panel + 40 A EV charger, 220.87, PASS

The utility's interval data shows a 12-month peak demand of 9.6 kW, which is 9,600 VA, or 40 A at 240 V. Per 220.87, count it at 125%: 1.25 x 9,600 = 12,000 VA (50 A). The service rating is 200 A x 240 V = 48,000 VA, so the headroom before the new load is 48,000 - 12,000 = 36,000 VA (150 A).

The new 40 A EVSE is 9,600 VA, already above the 7,200 VA floor of 220.57. Check: 12,000 + 9,600 = 21,600 VA, well under 48,000 VA. PASS, with 26,400 VA (110 A) still spare after the charger. This is the typical outcome on a 200 A service: gas-heated houses rarely peak above 10 kW.

Example 3: 100 A panel with electric heat + the same charger, FAIL

Metered peak: 18 kW = 18,000 VA (75 A at 240 V), a realistic January number for a small all-electric house. At 125%: 1.25 x 18,000 = 22,500 VA (93.75 A). The service is 100 A x 240 V = 24,000 VA, leaving just 24,000 - 22,500 = 1,500 VA (6.25 A) of headroom.

Adding the 9,600 VA charger: 22,500 + 9,600 = 32,100 VA, over the 24,000 VA rating by 8,100 VA (33.75 A). FAIL. Options in order of cost: an energy management system per NEC 625.42 that holds the charger to the 1,500 VA that fits (or dynamically to whatever is free moment to moment), a full 220.82 recalculation with its demand factors, or a service upgrade.


Frequently Asked Questions

Can a 100 A panel handle a Level 2 EV charger?

It has to be proven with a load calculation, not guessed. NEC 220.87 is the cleanest path: take the highest demand from 12 months of utility metering data, multiply by 125 percent, and add the charger load. A 100 A, 240 V service is 24,000 VA, so the install works when 1.25 times the metered peak plus the charger stays at or below 24,000 VA. Example: a metered peak of 8 kW gives 1.25 x 8,000 = 10,000 VA, leaving 14,000 VA, which is plenty for a 40 A (9,600 VA) charger. A peak of 18 kW leaves only 1,500 VA and fails. When it fails, a listed energy management system per NEC 625.42(A), in accordance with NEC 750.30, can set the maximum equipment load used in the service calculation instead of forcing a service upgrade.

What is the difference between the standard method and the optional method?

The standard method in NEC Article 220 Part III itemizes each load category with its own demand factor table. The optional method in 220.82 is a simplified alternative for a dwelling served by a single 120/240 V or 208Y/120 V, 3-wire service or feeder of 100 A or larger: everything except heating and cooling goes into one bucket taken at 100 percent of the first 10 kVA plus 40 percent of the remainder, then the largest of the six heating and cooling options in 220.82(C) is added on top. Both methods are code-legal. The optional method usually produces the smaller number and is what most residential service calculations use.

Can I use NEC 220.87 without 12 months of utility data?

Yes, through the exception in 220.87. If a year of utility demand data is not available, you may base the calculation on the maximum demand recorded continuously for at least 30 days, defined as the highest average kilowatts reached and maintained over a 15-minute interval, using a recording ammeter or power meter on the highest loaded phase. The recording must be taken while the building is occupied, and it must include, by measurement or calculation, the larger of the heating or cooling load plus other loads that are periodic or seasonal in nature. The exception is not permitted where the service has a renewable energy system such as solar PV or wind, or uses any form of peak load shaving.

What is the difference between connected load and demand load?

Connected load is the sum of every nameplate in the house, as if everything ran flat out at once. Demand load is what the code lets you count after applying demand factors, because real homes never run every load simultaneously. In the worked example on this page, NEC 220.82 turns 34,100 VA of connected general load into 19,640 VA of demand. NEC 220.87 skips the estimate entirely and starts from the demand the meter actually recorded. Service size is always based on the calculated demand load, never on the connected total.

How many VA is an EV charger in a load calculation?

Per NEC 220.57, new in the 2023 edition, EVSE is calculated at 7,200 VA or the nameplate rating, whichever is larger. The 7,200 VA floor corresponds to a 30 A, 240 V circuit. So a 40 A charger counts as 9,600 VA and a 48 A charger as 11,520 VA, while a small 16 A unit still counts as 7,200 VA. NEC 2023 is genuinely ambiguous about whether EVSE inside the 220.82 optional method may ride the 40 percent second tier; this calculator adds it at 100 percent outside that tier, which is the conservative reading of 2023 and the explicit rule of the 2026 edition. Where a listed energy management system per 625.42(A), in accordance with 750.30, controls the EVSE, the managed maximum setting can be used instead.

What is NEC 220.83 and when does it apply instead?

220.83 is a permitted way to check whether an existing service or feeder can take additional load, for a dwelling unit served by a 120/240-volt or 208Y/120-volt, 3-wire service or feeder. Per 220.83(A), when no additional air conditioning or electric space heating is being installed, existing plus new loads are taken at 100 percent of the first 8 kVA plus 40 percent of the remainder. Per 220.83(B), when air conditioning or electric space heating is being added, air-conditioning equipment is taken at 100 percent, central electric space heating at 100 percent, and fewer than four separately controlled space-heating units at 100 percent, using only the larger of the air-conditioning or space-heating load, not both; all other loads get 100 percent of the first 8 kVA and 40 percent of the remainder. Table 220.83(B) has no row for four or more separately controlled space-heating units. This calculator implements 220.82 and 220.87, not 220.83; 220.87 is usually the better answer when demand data exists because measured reality beats estimates.

Does the NEC 2026 change these calculations?

Yes, in ways worth knowing before your state adopts it. The 2026 edition renumbers Article 220 to Article 120, so 220.82 becomes 120.82 and 220.87 becomes 120.87. Inside the optional method, the general lighting allowance drops from 3 VA to 2 VA per square foot and the 100 percent first tier drops from 10 kVA to 8 kVA, so the two changes partially offset. New 120.82(D) settles the EV question: EVSE counts at 100 percent of nameplate with no demand factor. Secondary sources also report that 120.87 will newly allow subtracting removed loads, useful when swapping resistance heat for a heat pump, but verify that in the published book. See our NEC 2026 changes page for the full delta list and which states have adopted it.

Do I calculate at 240 V or 208 V?

Use 240 V for the standard single-phase, three-wire service in detached homes. Use 208 V when the dwelling is fed from two legs of a 208Y/120 V three-phase system, which is common in apartment and condo buildings. The choice matters: the same 24,440 VA calculated load is 101.8 A at 240 V but 117.5 A at 208 V, which can push the answer past a service size. NEC 220.82(A) permits the optional method for both service types.

The calculation passes; why might an electrician still recommend an upgrade?

A load calculation only answers whether the service capacity is sufficient. An electrician on site also weighs physical breaker space, panel age and condition, whether the panel brand is one of the known problem lines, aluminum branch wiring, available fault current, and local amendments that can be stricter than the NEC as published. This calculator is a planning and estimating tool. A permit-grade calculation, stamped where required, belongs to a licensed electrician working from your jurisdiction's adopted code edition.

How do I know if my electrical panel is overloaded?

There are two different ways a panel is overloaded. The first is calculated: your demand load exceeds the service rating. Run a load calculation (NEC 220.83 when adding loads to an existing home, or 220.87 from a year of metered data), and if the demand comes out above your service amps, more than 100 A of demand on a 100 A panel for example, the service is undersized and needs an upgrade. The second is physical: breakers that trip often, a panel with no open slots, two wires landed under one breaker (a double-tap), or a warm panel cover. The calculated check is what this tool answers, returning service adequate, tight, or upgrade likely; the physical check needs a licensed electrician's eyes on the panel. Adding a large new load like an EV charger, heat pump, or electric range is the usual reason a panel that was fine becomes overloaded.


Related Calculators

Panel passes? Now build the circuit.

The load calculation answers whether the service can take the charger. The EV charger calculator answers everything after that: wire size, breaker, GFCI, receptacle rules, and how fast the car actually charges.