Electrical / runnable MCP tool
Run the Saddle Bend Calculator in your AI assistant
Through the free Intry MCP server, Claude, ChatGPT, or Cursor runs this exact calculator and hands back a verdict and the cited source, not a guess. Tool name: saddle_bend.
How it computes the answer
Marks and shrink from the bender-chart constants where a manufacturer prints the angle (offset multiplier, 3-point saddle multiplier and shrink per inch) and from bend geometry elsewhere (offset 1/sin, saddle depth/sin(half-angle), kick travel); take-up from the EMT bender profile for your conduit size, or the deduct you entered (the only take-up carried for IMC and RMC), and gain from that conduit's own radius and outside diameter.
What it cites
Your assistant calls the same engine the interactive calculator calls, with the inputs listed under Inputs. These are the sources that engine reads.
- Bender-manufacturer offset multiplier table
- Distance between the two offset marks = offset depth x the multiplier: 6.0 at 10 degrees, 2.6 at 22.5, 2.0 at 30, 1.4 at 45, 1.2 at 60. Printed as a constant beside the shrink column, under the heading 'applies to any size conduit', in the Greenlee Offset Table (Hand Bender Instruction Manual IM 1071 REV 4 5/98), in the Greenlee SITE-RITE Hand Benders manual, and in the Gardner Bender 960-Series How to Bend guide; all three agree cell for cell on the values (Gardner Bender's angle column misprints 22-1/2 as 21-1/2; its own instructions on the same page say 22-1/2), and Klein's Zip Guide distance-between-bends table is computed with the same constants (8 inches of depth at 60 degrees prints 9-5/8 inches, which is 8 x 1.2 to the nearest eighth). Each constant is 1/sin(angle) taken to a tape-measure value: four of the five are the cosecant to one decimal (2.61, 2.00, 1.41 and 1.15 unrounded) and 10 degrees is rounded up from 5.76 to 6.0, and the calculator applies the chart value at a charted angle so its marks match the table cast on the bender. At any other angle it applies the exact 1/sin and says so.
- Bend geometry (trigonometry)
- Where no chart row exists the engine works from geometry: the offset multiplier is 1/sin(angle), the three-point saddle center-to-outer distance is depth/sin(half the center angle) at a center no held saddle table prints, a kick's travel is kick height/sin(kick angle), and a rolling offset is the Pythagorean combination of the rise and the roll. No held document prints a kick constant, so the kick is geometry alone: the kick mark sits kick height/sin(kick angle) past the 90 mark, and that mark distance is the bend the engine checks and the 3D draws. The receipt names which basis produced each answer.
- Bender-manufacturer 3-point saddle table
- Distance from the center mark to each outer mark = saddle depth x 2.5 for a 45 degree center (22.5 degree outer bends), printed as a saddle table in four held documents that agree cell for cell: the Greenlee Hand Bender Instruction Manual IM 1071 REV 4 5/98 ('Table for 45 degree Saddles', 1 in -> 2-1/2 in, 2 in -> 5 in, 3 in -> 7-1/2 in, 4 in -> 10 in, 5 in -> 12-1/2 in, 6 in -> 15 in, 'for each additional inch add 2-1/2 in', under 'applies to any size conduit'), the Greenlee SITE-RITE Hand Benders manual (the same table), the Gardner Bender 960-Series How to Bend guide ('outer bend marks at a distance of 2-1/2 in x the object size') and the Klein Tools Conduit Bender and Angle Setter Guide (MKT200815 Rev. 09/20 A) Zip Guide for Saddles (the 45 degree column). Klein's 60 degree column (30 degree outer bends) prints 2 in per inch of depth: 2, 4, 6, 8, 10, 12. The calculator applies the table value at those two center angles so its marks match the table on the bender; exact 1/sin of the outer angle is 2.61 at a 45 degree center (the table is that value rounded for a tape measure, and the marks at the table spacing lay out a sharp-corner peak 4.3 percent below the requested depth, before the bend radius rounds the top) and exactly 2.00 at 60, and both are shown beside the applied value. The peak the calculator and its 3D report is the centerline height once the center arc is laid at the NEC Chapter 9, Table 2 radius, which sits R x (sec(outer angle) minus 1) below that sharp corner; pure geometry, no sourced constant. One printed cell is refused rather than matched: Klein's 1 inch row at a 60 degree center (2 inches from center) cannot be bent in any EMT size this calculator carries, because the 30 degree outer arc and the 60 degree center arc on the Table 2 radius overlap before the marks are 2 inches apart, and the calculator says so instead of printing it. No held document prints a saddle row for a 30 or 22.5 degree center, so those saddles apply the exact 1/sin and say so. The saddle shrink is the offset chart's shrink at the outer angle, which is also what the same tables print in their shrink column.
- Bender-manufacturer shrink-per-inch table
- Shrink per inch of offset: 1/16 in at 10 degrees, 3/16 in at 22.5, 1/4 in at 30, 3/8 in at 45, 1/2 in at 60. Fetched from three bender-manufacturer guides that agree cell for cell: the Greenlee Offset Table (Hand Bender Instruction Manual IM 1071 REV 4 5/98), the Gardner Bender 960-Series How to Bend guide, and the Klein Tools Conduit Bender and Angle Setter Guide (MKT200815 Rev. 09/20 A). Greenlee and Klein additionally print the same absolute shrink-per-depth table as each other, cell for cell, including a shared rounding anomaly at 22.5 degrees and 9 inches of depth where both print 1-3/4 inch against a pattern value of 1-11/16. Two documents carrying one anomaly is a common convention, not independent confirmation, so treat the three guides as corroborating the trade standard rather than as three separate derivations of it. The 15 degree row is the one value none of the three publishes, and it is marked as unsourced rather than attributed. This is the field table. It does not equal tan(half the bend angle), and that difference is published beside it on the shrink chart rather than smoothed over: tan(half-angle) is the shrink of a bend modelled as a sharp corner with no radius, so it runs above the chart, while a real bender lays an arc and shrinks slightly less than the sharp-corner figure. We apply the manufacturer chart wherever one exists, and fall back to the sharp-corner geometry only for angles no manufacturer publishes, which is what lets the calculator answer any angle.
- Hand-bender take-up (EMT) and gain (every type)
- Take-up is the distance from your mark to the start of the bend. Two held guides print the same three EMT values and both match this engine exactly, 1/2 in at 5 in, 3/4 in at 6 in and 1 in at 8 in: the Klein Tools Conduit Bender and Angle Setter Guide (MKT200815 Rev. 09/20 A) in its Bender Take Up Table, and the Gardner Bender 960-Series How to Bend Guide in its deduct chart. Both of those tables stop at 1 in, so the 1-1/4 in take-up is covered by neither, is carried as a field value, and is marked as unconfirmed everywhere it is printed. Greenlee is deliberately not cited for take-up: both Greenlee manuals we hold publish no take-up or deduct value at all and instruct the electrician to read the deduct off the bender casting, which is why the calculator also accepts a deduct you enter from your own tool. A deduct you enter replaces the take-up and nothing else, because it does not tell us your shoe's radius, and the answer says which of the two produced it. The field gain the engine subtracts from leg lengths is derived from the radius and the outside diameter, never hand-typed, so the two gain references cannot be mixed up.
These are geometry and published field-chart values, computed and applied by the engine, not a laboratory measurement. Bender take-up varies by tool and shoe, so field-verify the first bend of a new setup against the actual conduit. The bender in your hand has the final say.
The full receipt, with every source and how each is cross-checked, is on the interactive Saddle Bend Calculator.
Ask your assistant
The one rule that makes it reliable: name Intry in your question. That is what tells Claude to run the saddle_bend tool and answer with the real number, the verdict, and the citation. Leave Intry out and Claude may just guess from memory, which is exactly what you are trying to avoid. Type something like:
Inputs
| Field | Required | Accepts | What it is |
|---|---|---|---|
| points | optional | 3, 4 | 3 for a 3-point saddle (round obstruction), 4 for a 4-point saddle (wide/flat obstruction). Default 3. |
| depth | yes | number | Saddle depth (obstruction height) in inches, as the bender saddle tables enter it. For a 3-point saddle the readout prints the centerline peak these marks reach, which sits at or below the entered depth once the center bend is laid at the bend radius; for a 4-point saddle it prints the flat top these marks reach, which the chart multiplier's rounding puts slightly under the entered depth at 22.5 and 45 degrees, so raise the depth until the printed flat top clears. |
| angle | yes | number | For a 3-point saddle, the CENTER bend angle (typically 45; outer bends are half). For a 4-point saddle, the angle of all four bends (typically 22.5 or 30). |
| width | optional | number | 4-point only: the obstruction width in inches (the flat-top span between the two inner marks). Ignored for a 3-point saddle. |
| conduitSize | optional | 1/2", 3/4", 1", 1-1/4" | Trade size (default 3/4"). 1-1/4" is EMT only; IMC and RMC carry 1/2", 3/4" and 1". The marks do not depend on it; whether the bend can be made does, through the size's NEC Chapter 9 Table 2 bend radius. |
| conduitType | optional | EMT, IMC, RMC | Conduit type (default EMT). Greenlee's SITE-RITE hand-bender manual rates the same benders for 1/2" through 1-1/4" EMT and 1/2" through 1" rigid and IMC, and its older IM 1071 manual says 1/2" through 1" rigid; this tool carries IMC and RMC in 1/2", 3/4" and 1" (1-1/4" is not carried in IMC or RMC: no held bender document bends it by hand) at the NEC Chapter 9 Table 2 radius by trade size (342.24(A), 344.24(A)). No rigid take-up is carried: no rigid size has two held primaries that agree: Klein prints 6" and 8" for 1/2" and 3/4" rigid on its 3/4" and 1" EMT benders, and Gardner Bender's rigid column prints 3-3/4", 7" and an unusable 38-1/2" under a "Conduit Size" row key its document never defines, so the two cannot even be lined up. A stub, back-to-back, kick or stick in IMC or RMC needs `deduct`. |
Add Intry to Claude
One paste and Claude can run this tool and every other Intry calculator, right from your phone.
- Claude opens with the Intry connector already filled in. Review it and click Add.
- (If a field is blank, paste the link below into the URL field.)
- In any chat, tap + then Connectors and switch Intry on. Then name Intry in your question (“use Intry to…”) so Claude runs the tool instead of guessing.
https://www.intrysys.com/api/mcpNo login, no API key, and it works on every Claude plan, right from your phone.
Using ChatGPT, Cursor, or a dev tool? See the developer setup on the main page. The endpoint is https://www.intrysys.com/api/mcp.
Every answer comes with the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius, so you can check it or show an inspector. The numbers come from the same calculator we run on intrysys.com, and we re-check every one automatically before anything goes live, so the number Claude hands you matches the code.