NEC 625 Reference
EV Charger Wire Size Chart
Copper and aluminum conductor, breaker, and ground wire size by EV charger amperage, sized at the NEC 625 continuous-load rule. Covers 16A through 80A chargers, the NEMA 14-50, and the 40A and 48A installs.
Wire, Breaker, and Ground by Charger Amperage
Conductors are the NEC Table 310.16 75°C column sized to 125% of the charger current; the breaker is the smallest standard rating at or above that value; the ground (EGC) is copper per NEC Table 250.122. These sizes are at 86 F ambient with 1-3 current-carrying conductors, which is the basis the ampacity tables are printed at. A hotter run, or more current-carrying conductors sharing the raceway, derates the conductor under NEC 310.15(B)(1) and NEC Table 310.15(C)(1) and can call for a larger one. The Intry EV charger calculator sizes for the conditions you enter.
EV charger conductor, breaker, and equipment grounding conductor by continuous charger current, per NEC Article 625
Swipe the table sideways to see the rest of its columns. →
| Charger | 125% (min) | Breaker | Copper, 75°C terminations | Copper, 60°C (NM-B through 2 AWG) | Aluminum, 75°C | Ground (Cu) | Example Use |
|---|---|---|---|---|---|---|---|
| 16A | 20A | 20A | #12 | #12 | #10 | #12 | NEMA 6-20, small Level 2 |
| 24A | 30A | 30A | #10 | #10 | #8 | #10 | NEMA 14-30 / 6-30 |
| 32A | 40A | 40A | #8 | #8 | #8 | #10 | Hardwired 32A EVSE |
| 40A | 50A | 50A | #8 | #6 | #6 | #10 | NEMA 14-50 (portable EVSE) |
| 48A | 60A | 60A | #6 | #4 | #4 | #10 | Hardwired 48A EVSE (check the unit's manual for its metal and terminals) |
| 50A | 62.5A | 70A | #6 | #4 | #4 | #8 | Hardwired 50A EVSE (check the unit's manual for its metal and terminals) |
| 60A | 75A | 80A | #4 | #3 | #3 | #8 | Hardwired 60A EVSE |
| 80A | 100A | 100A | #3 | #1 | #1 | #8 | Top of the range this calculator sizes |
At the 50A row and the 60A aluminum, the breaker is one standard size above the conductor's 75°C ampacity; NEC 240.4(B) permits that next-standard breaker size for a fixed continuous load whose conductor ampacity is not itself a standard breaker rating. Copper THHN/THWN-2 terminated at the 75°C column, which on a circuit of 100A or less holds only where the breaker and the equipment are both listed and identified for 75°C conductors (NEC 110.14(C)(1)(a)(3)); unmarked terminations and NM-B cable (NEC 334.80) take the 60°C column. Long runs may require a larger conductor for voltage drop even when ampacity is met. Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)). Always confirm against the manufacturer's installation instructions.
Wire Size for a Specific Charger Amperage
The full breakdown for each common charger output: copper and aluminum conductor, breaker, ground, and the NM-B (60°C) caveat, worked from the 125% continuous-load rule.
32A EV Charger (7.7 kW)
#8 Cu on a 40A breaker, #10 Cu ground.
40A EV Charger (9.6 kW)
#8 Cu (75°C-marked terminations; #6 Cu at 60°C or NM-B) on a 50A breaker, #10 Cu ground.
48A EV Charger (11.5 kW)
#6 Cu (75°C-marked terminations; #4 Cu at 60°C or NM-B) on a 60A breaker, #10 Cu ground.
60A EV Charger (14.4 kW)
#4 Cu (75°C-marked terminations; #3 Cu at 60°C or NM-B) on an 80A breaker, #8 Cu ground.
80A EV Charger (19.2 kW)
#3 Cu (75°C-marked terminations; #1 Cu at 60°C) on a 100A breaker, #8 Cu ground.
NEMA Plug Reference for Plug-In Chargers
A cord-and-plug Level 2 charger is limited to 80% of its receptacle rating. These are the common EV receptacles and the maximum continuous charger current each supports.
NEMA receptacle, circuit rating, maximum continuous charger current, and copper wire size
Swipe the table sideways to see the rest of its columns. →
| Receptacle | Circuit | Max Continuous | Copper Wire |
|---|---|---|---|
| NEMA 6-20 | 20A / 240V | 16A | #12 |
| NEMA 14-30 | 30A / 240V | 24A | #10 |
| NEMA 6-50 | 50A / 240V | 40A | #6 AWG copper, the size that holds on any termination and on NM-B cable (#8 AWG only on 75°C-marked terminations) |
| NEMA 14-50 | 50A / 240V | 40A | #6 AWG copper, the size that holds on any termination and on NM-B cable (#8 AWG only on 75°C-marked terminations) |
Cord-and-plug EVSE requires GFCI protection per NEC 625.54. NEC 625.54 covers receptacles, and a hardwired charger has none. At a dwelling, the 2023 NEC's 210.8(F) requires GFCI protection for an outdoor outlet and for an outlet in a garage with its floor at or below grade, an accessory building or a boathouse, on a single-phase circuit of 150 V or less to ground and 50 A or less; a hardwired charger's outlet there needs it. Check the maker's manual for its own ground-fault protection too (Tesla prints “Integrated CCID20”).
Why EV Circuits Are Sized at 125%
Per NEC 625.42, electric vehicle supply equipment is a continuous load, meaning it can draw its maximum current for three hours or more. NEC 210.19(A) sizes the conductor and NEC 210.20(A) / 625.41 size the overcurrent protection at 125% of a continuous load. That is why a 48A charger needs a 60A breaker and 60A-rated wire (48 × 1.25 = 60), not a 50A breaker sized to the raw current.
The chart already bakes in the 125% factor: the “125% (min)” column is the minimum conductor ampacity and the breaker is the smallest standard size at or above it. You size the wire to that value at the 75°C column of NEC Table 310.16, then confirm the run length does not push you larger for voltage drop.
Size a Specific Install
Enter the charger, run length, and panel to get the wire, breaker, ground, GFCI requirement, voltage drop, and a parts list for your exact installation.
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
What size wire for a 48A EV charger?
A 48A EV charger needs #6 AWG copper conductors on a 60A breaker on 75°C-marked terminations (at 60°C or on NM-B cable, #4 AWG). EV charging is a continuous load, so the circuit is sized at 125%: 48 x 1.25 = 60A (NEC 625.42, 210.20(A)). #6 copper is rated 65A at the 75C column of NEC Table 310.16, which covers the 60A requirement. In aluminum, use #4 AWG where the charger's terminals take aluminum; the Tesla Wall Connector's do not (its manual prints "COPPER WIRE TERMINATIONS ONLY" and asks for 4 AWG copper on a 60°C-rated breaker). On a long run, check voltage drop and consider upsizing. These sizes are at 86 F ambient with 1-3 current-carrying conductors, which is the basis the ampacity tables are printed at. A hotter run, or more current-carrying conductors sharing the raceway, derates the conductor under NEC 310.15(B)(1) and NEC Table 310.15(C)(1) and can call for a larger one. The Intry EV charger calculator sizes for the conditions you enter.
What size wire for a 50 amp EV charger?
A true 50A continuous charger requires a 70A breaker (50 x 1.25 = 62.5A, rounded up to the 70A standard size) with #6 copper or #4 aluminum on 75°C-marked terminations (at 60°C or on NM-B cable, #4 AWG). Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)). A '50 amp' EV setup can instead be a 40A charger on a NEMA 14-50 outlet, which is a 50A circuit using #6 AWG copper, the size that holds on any termination and on NM-B cable (#8 AWG only on 75°C-marked terminations) and a 50A breaker. Confirm whether your 50 is the charger's continuous output or the receptacle rating.
What wire size for a NEMA 14-50 outlet?
A NEMA 14-50 receptacle is on a 50A circuit and takes #6 AWG copper, the size that holds on any termination and on NM-B cable (#8 AWG only on 75°C-marked terminations), with a 50A breaker and a #10 copper ground (#8 if the ground is aluminum). Aluminum on a receptacle: the receptacle's terminals must be identified for aluminum conductors (NEC 2023, 110.14(A)). A portable Level 2 charger plugged into it is limited to 40A continuous (80% of the 50A receptacle). If you want the full 48A from a hardwired charger, run #6 copper on a 60A breaker on 75°C-marked terminations (at 60°C or on NM-B cable, #4 AWG) instead of using a 14-50.
What size ground wire for an EV charger?
The equipment grounding conductor is sized by the breaker rating per NEC Table 250.122. A 30A to 60A EV circuit uses a #10 copper EGC (a 20A circuit uses #12); a 70A to 100A circuit uses #8 copper. The EGC does not carry normal current and is smaller than the circuit conductors. It is separate from the neutral and must land on the ground bar.
Can I use aluminum wire for an EV charger?
Where the charger's manual allows it: the code permits aluminum on terminals identified for it (NEC 110.14), and a charger's manual can print copper only (the Tesla Wall Connector's says "COPPER WIRE TERMINATIONS ONLY"); the calculator applies each manual it holds. Size it up from copper: #4 aluminum for a 48A charger versus #6 copper, or #3 aluminum for a 60A charger, all on 75°C-marked terminations (at 60°C or on NM-B cable: #4 Al becomes #3 Al, #6 Cu becomes #4 Cu, and #3 Al becomes #2 Al). Use antioxidant on the terminations and torque to spec. Aluminum also drops more voltage, so check the run length on long garage or detached-structure runs.
Does wire size change for a longer EV charger run?
It can. The chart sizes conductors for ampacity and the 125% continuous-load rule at normal distances. On long runs (roughly 50 feet and up for a 48A charger), voltage drop can force you a size larger even though the ampacity is fine. A 48A charger at the end of a 120-foot run can need #4 copper instead of #6. Check the run with the voltage drop chart.
Related Calculators
EV Charger Calculator
Full install sizing: wire, breaker, panel capacity, GFCI, voltage drop, and parts list.
Voltage Drop Chart
Maximum copper and aluminum run distances at 3% drop, for long garage and detached runs.
Wire Size Calculator
NEC 310.16 ampacity with derating and terminal temperature enforcement.
Load Calculator
Will the panel take the charger? Run the NEC 220.87 existing-load check before you quote.
Wire sized. Will the panel take it?
The conductor is only half the job. Confirm the service has room for the new load with the NEC 220.87 existing-load method before you commit the install.