NEC Article 625 EV Charging
What Size Wire for an 80 Amp EV Charger?
The breaker, copper and aluminum wire, and ground for an 80A (19.2 kW) Level 2 charger, sized for the 125% continuous load per NEC Article 625, with the parts list and the interactive calculator.
80 Amp EV Charger Circuit Spec
Circuit for an 80A (19.2 kW) Level 2 EV charger, NEC Article 625
Swipe the table sideways to see the rest of its columns. →
| Charger output (continuous) | 80A |
| Design load (125%) | 100A |
| Breaker (double-pole) | 100A |
| Copper wire (on 75°C-marked terminations) | #3 |
| Aluminum wire (on 75°C-marked terminations) | #1 |
| 60°C copper | #1 |
| 60°C aluminum | 1/0 |
| Equipment ground (Cu) | #8 |
Wire at the 75°C column of NEC Table 310.16, which on a circuit of 100A or less holds only where the breaker and the charger are both listed and identified for 75°C conductors (NEC 110.14(C)(1)(a)(3)). Unmarked terminations and NM-B cable (NEC 334.80) take the 60°C column. Continuous-load sizing per NEC 625.41 / 210.20(A); ground per NEC 250.122. Check voltage drop on long runs.
Your Exact Run: Wire, Panel, and Parts
Enter the distance, conductor material, and your panel to get the exact wire, voltage drop, panel-capacity check, GFCI requirement, and a parts list for this install.
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
What size wire do I need for a 80 amp EV charger?
An 80A EV charger needs #3 copper or #1 aluminum conductors on 75°C-marked terminations (#1 copper or 1/0 aluminum at 60°C) on a 100A breaker. Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)). EV charging is a continuous load, so the circuit is sized at 125% of the charger's output (80 × 1.25 = 100A, rounded up to a 100A standard breaker per NEC 625.41 and 210.20(A)). The wire is sized at the 75°C column of NEC Table 310.16, which on a circuit of 100A or less holds only where the breaker and the charger are both listed and identified for 75°C conductors (NEC 110.14(C)(1)(a)(3)). The equipment grounding conductor is #8 copper per NEC Table 250.122. These sizes are at 86 F ambient with 1-3 current-carrying conductors, which is the basis the ampacity tables are printed at. A hotter run, or more current-carrying conductors sharing the raceway, derates the conductor under NEC 310.15(B)(1) and NEC Table 310.15(C)(1) and can call for a larger one. The Intry EV charger calculator sizes for the conditions you enter. On 60°C terminations the 60°C column applies (NEC 110.14(C)(1)(a)), so use #1 copper instead; NM-B cable, held to 60°C by NEC 334.80, is made only through 2 AWG (NEC 334.104), so no NM-B cable serves this circuit.
What size breaker for a 80 amp EV charger?
A 100A double-pole breaker. Because EVSE is a continuous load, NEC 625.41 requires the overcurrent device to be rated at least 125% of the charger's output: 80 × 1.25 = 100A, and the next standard breaker size is 100A.
Does a 80 amp EV charger need a dedicated circuit?
Yes. An 80A Level 2 charger, whether hardwired or plug-in, must be on its own dedicated branch circuit that serves no other load (NEC 625.40). NEC 625.40's own Exception permits one branch circuit to feed multiple EVSEs where 625.42(A) or (B) allows it; it does not permit an EVSE to share a circuit with an ordinary appliance. A plug-in unit on a NEMA receptacle also needs GFCI protection at the breaker (NEC 625.54). NEC 625.54 covers receptacles, and a hardwired charger has none. At a dwelling, the 2023 NEC's 210.8(F) requires GFCI protection for an outdoor outlet and for an outlet in a garage with its floor at or below grade, an accessory building or a boathouse, on a single-phase circuit of 150 V or less to ground and 50 A or less; a hardwired charger's outlet there needs it.
How far can I run the wire for a 80 amp EV charger?
#3 Cu (75°C-marked terminations; #1 Cu at 60°C) carries a 100A circuit at ampacity, but on a long run voltage drop, not ampacity, can set a larger wire. Enter your exact distance in the calculator below: where it moves the wire up for voltage drop, it moves the ground wire up in proportion with it, as NEC 250.122(B) requires.
Other EV Charger Sizes
32 Amp EV Charger
#8 Cu on a 40A breaker (7.7 kW).
40 Amp EV Charger
#8 Cu (75°C-marked terminations; #6 Cu at 60°C or NM-B) on a 50A breaker (9.6 kW).
48 Amp EV Charger
#6 Cu (75°C-marked terminations; #4 Cu at 60°C or NM-B) on a 60A breaker (11.5 kW).
60 Amp EV Charger
#4 Cu (75°C-marked terminations; #3 Cu at 60°C or NM-B) on a 80A breaker (14.4 kW).
Will My Panel Handle It?
Load calculation to check if your 100A or 200A panel has room for the charger.
EV Charger Wire Size Chart
Every charger amperage 16A to 80A with wire, breaker, and NEMA plug.
Wire Size Calculator
General NEC 310.16 sizing for any breaker and load, with derating.