Bending Reference

Conduit Bending Cheat Sheet

Every EMT hand-bender constant you use on the job, on one page. Offset multipliers, take-up and deduct, shrink per inch, saddle and kick math, and the NEC 360-degree rule. Print it, save the PDF, or download the image for your phone. No login.

Quick answer: Offset multipliers are 6.0 at 10°, 2.6 at 22.5°, 2.0 at 30°, 1.4 at 45°, and 1.2 at 60°, the bender-chart constants the calculator applies (15° has no chart row and uses the exact 1/sin, 3.86). Multiply the offset height by the multiplier to get the distance between marks. EMT take-up (deduct) is 5" for 1/2", 6" for 3/4", 8" for 1", 11" for 1-1/4" (unconfirmed); a 90° stub mark is stub height minus take-up. Shrink per inch runs 1/16" at 10° up to 1/2" at 60°. NEC 358.24(B) caps a run at 360° of total bends between pull points.

Print it, save the PDF, or download the image to keep on your phone. No login.

Download image

EMT Hand Bender · Field Reference

Conduit Bending

The One-Page Cheat Sheet

intrysys.com
No login
Bender marks
Tip / Rim90° stubs
Arrowoffsets & saddles
Starback-to-back 90s
Teardrop3-point saddle center

Offset Multipliers

× height = travel
Offset multiplier and shrink per inch by bend angle
AngleMult1/sinShrink/in
10°6.05.761/16"
15°3.863.860.132
22.5°2.62.613/16"
★ 30°2.02.001/4"
45°1.41.413/8"
60°1.21.151/2"
travelh

The charted multiplier & shrink/in are the same for every conduit size. Multipliers shown are the bender-manufacturer chart values (6.0 at 10°, 2.6 at 22.5°, 2.0 at 30°, 1.4 at 45°, and 1.2 at 60°), the rounded 1/sin, and they are what the calculator applies; 15° has no chart row, so it shows the exact 1/sin. Shrink shown is the bender-manufacturer chart value, which is what the calculator applies. Working it from the angle alone (height × tan(½ angle)) gives a higher number, because that treats the bend as a square corner with no radius; at 60° it runs about a third high against a real bend. Use the chart.

90° Stub · Take-Up

EMT
EMT hand bender take-up (deduct) by conduit size
SizeTake-up / Deduct
1/2"5"
3/4"6"
1"8"
1¼"11"
markstubtip

Mark = stub − take-up, measured to the back of the bend (not the floor). Deduct = take-up. Gain (outside corner, for developed length & back-to-back 90s): 1/2"=2.42" · 3/4"=2.85" · 1"=3.63" · 1¼"=4.62".

Core Formulas

Offset travel
height × multiplier
Offset shrink
height × shrink/in
90° stub mark
stub − take-up
Back-to-back 90
1st stub + gap − gain (from end, star mark)
Kick travel
kick ht × 1/sin(angle) (the 1/sin column, not Mult)

3-Point Saddle

over obstruction
Three point saddle center and outer angles with center-to-outer multiplier
CenterOutersMult1/sin
45°22.5°2.52.61
30°15°3.863.86
60°30°2.02.00

Center-to-outer = depth × mult (the bender saddle table at 45° and 60°; exact 1/sin elsewhere). Bend center first, then outers each way. A 45° saddle shrinks the center ~3/16"/in of depth, so recenter after.

Read this

The offset multiplier is the same for every conduit size. It is set by the angle, not the pipe. Take-up, deduct & gain change with size, and so does whether a bend can be made at all: the size's bend radius sets the smallest offset, saddle or kick.

Verify

Deducts here are Klein and Gardner Bender's published values for 1/2", 3/4", 1", and an unconfirmed field value for 1-1/4". They can vary slightly by model, so always trust the figure stamped on your own bender, or pull one test bend.

360°Max total bends between pull points. Every offset, saddle, 90 & kick counts.NEC 358.24(B) (EMT)
Sources: NEC §358.24(B) · NEC Ch.9 Table 2 radii · standard EMT hand-bender constantsintrysys.com · interactive calculator + SVG diagrams

The code sections this page cites are named in the source receipt.


Go deeper on any bend

The sheet is the quick reference. Each page below has the full chart, a live calculator, and worked examples for that bend.