Ductless Mini Split Sizing
What Size Mini Split Do I Need?
Size a ductless mini split by the room, at about 25 BTU per square foot. Here is the BTU by room size, single versus multi-zone, the heat-pump note, and the calculator.
Mini Split Size by Room (BTU Chart)
Common single-zone mini split sizes and the room each suits (~25 BTU/sq ft, moderate climate).
Swipe the table sideways to see the rest of its columns. →
| Mini Split Size | Tons | Room Size | Example Space |
|---|---|---|---|
| 9,000 BTU | 0.75 | ~360 sq ft | Bedroom, office, small room |
| 12,000 BTU | 1 | ~500 sq ft | Large bedroom, living room |
| 18,000 BTU | 1.5 | ~750 sq ft | Great room, open kitchen/living |
| 24,000 BTU | 2 | ~1,000 sq ft | Large open area, small apartment |
| 36,000 BTU | 3 | ~1,500 sq ft | Whole small home, big open space |
Use 27 BTU/sq ft in a warm climate, up to 30 if the unit is your heat source in a cold climate. Add capacity for vaulted ceilings, heavy sun, or a kitchen. These are the standard 9k/12k/18k/ 24k/36k sizes mini splits come in.
Single-Zone, Multi-Zone, and Heating
A single-zone system is one outdoor unit and one indoor head sized to one room (6,000 to 36,000 BTU). A multi-zone system runs several heads off one outdoor unit; size each head to its own room first, then choose an outdoor condenser that supports the combined total (up to about 55,000 BTU). Where a mini split is a heat pump, the same unit heats and cools, but heating output falls as it gets colder, so in a cold climate size to the heating load and pick a cold-climate model. And since inverter units modulate down to 15 to 20 percent, slight oversizing is tolerable, but a badly oversized unit still short-cycles and dehumidifies poorly, so size to the load.
Compute the Load for a Ductless House
Enter your ZIP code and the house for ACCA Manual J's heating and cooling loads at your weather station, with the ducts set to none for a ductless system. A single room's load is a room-by-room calculation this calculator does not run.
The documents behind these figures are listed in the source receipt.
Frequently Asked Questions
What size mini split do I need for a room?
Plan on about 25 BTU per square foot for a mini split, a little more than a whole-house rule because a ductless head conditions one room to its design temperature. So a 12,000 BTU (1 ton) unit suits about 500 sq ft, an 18,000 BTU about 750 sq ft, and a 24,000 BTU about 1,000 sq ft. Use 27 BTU per sq ft in a warm climate, or up to 30 if you are relying on it for heat in a cold climate. Add capacity for vaulted ceilings, a sunny room, or a kitchen.
What size room does a 12,000 BTU mini split cool?
About 480 to 500 square feet. A 12,000 BTU mini split is one ton of cooling, a single-room size for a large bedroom, a living room, or a small open area. A 9,000 BTU unit covers about 360 sq ft (a standard bedroom or office), and an 18,000 BTU covers about 720 to 750 sq ft (a large great room).
What is the difference between single-zone and multi-zone?
A single-zone mini split is one outdoor unit paired with one indoor head, sized to that room, and ranges from about 6,000 to 36,000 BTU. A multi-zone system is one outdoor unit feeding several indoor heads, each sized independently to its own room; the outdoor condenser is sized to support the combined heads (up to about 55,000 BTU). Size each room's head to that room first, then pick an outdoor unit that covers the total.
Can a mini split heat as well as cool?
Where the unit is a heat pump, yes: the same unit heats and cools, so check that the model you choose is one. Its heating output drops as the outdoor temperature falls, so in a cold climate you size to the heating load at your design temperature and choose a cold-climate (hyper-heat) model rated to hold capacity well below freezing. If you only need cooling, size to the cooling BTU; if heating is the harder job, size to that.
Is it bad to oversize a mini split?
Less bad than oversizing a conventional system, but still not ideal. Inverter mini splits modulate their output to a fraction of capacity, so a slightly oversized unit just runs at reduced output. But a badly oversized unit still short-cycles, controls humidity poorly, and costs more than needed. Size to the load and only round up one step if you are between sizes.
Related
What Size Air Conditioner?
AC sizing by room and house from the ENERGY STAR table.
How Many BTU to Heat a House?
The heating side: Bryant's furnace size per square foot by climate region, a starting estimate before a Manual J.
BTU Calculator
A house's heating and cooling loads by ACCA Manual J at your ZIP code's weather station.
Mini Split Wire Size
Once it is sized, the circuit: wire and breaker from the nameplate MCA.
The circuit your mini split needs
Sized the head? Cross to the electrical side for the wire, breaker, and panel capacity the condenser needs.