NEC Article 440 (Air Conditioning)

What Size Wire for a Mini Split?

A ductless mini split is sized to the outdoor unit's nameplate, not the BTU. Here is how to read the MCA and max breaker, named models' figures by size, and the calculator.

Quick answer: Size the wire to the nameplate MCA and the breaker to the max fuse/breaker (MOCP), not the BTU. Gree and MrCool's 9,000 to 12,000 BTU units list MCA 9 to 19A and a 15 to 25A maximum breaker (#14 to #12 copper, the code minimum); their 18,000 to 24,000 BTU units list MCA 15 to 22A and 20 to 35A (#14 to #8 copper, where the code minimum alone is #14 to #10 and the maker's printed minimum is larger). Same size, different numbers, so read the data plate.

Wire from the MCA, Breaker from the Max Breaker

The outdoor condenser's data plate lists two numbers that set the circuit: the MCA (minimum circuit ampacity) sizes the conductor, and the maximum fuse/breaker (MOCP) sizes the overcurrent device. The MCA already includes the 125% factor for the compressor per NEC 440.32/440.33, so you just pick the smallest wire whose ampacity meets the MCA, on the 60°C column of NEC Table 310.16, or the 75°C column where the breaker and the unit are listed and identified for 75°C conductors (NEC 110.14(C)(1)(a)). The cooling number does not set the circuit: Gree's 12,000 BTU unit lists MCA 10A on a 15A maximum breaker, and MrCool's lists MCA 19A on a 25A maximum.


Mini Split Wire Size by BTU: Named Models

Each row is one maker's unit, its MCA and maximum breaker as printed in Gree's Vireo Gen3 submittals and MrCool's DIY 4th Gen manual. The breaker is the largest standard size at or below that maximum. The code minimum copper is the smallest size on the 60°C column of NEC Table 310.16 that meets the MCA; the maker's minimum is the copper its manual prints; the copper to run is the larger of the two (NEC 110.3(B)). Another unit of the same size can differ, so the nameplate wins over this table.

Named single-zone mini splits: the maker's MCA and max breaker, the breaker and code-minimum copper from them, the maker's minimum copper, and the larger of the two (nameplate governs)

Swipe the table sideways to see the rest of its columns. →

UnitSizeVoltsMCAMax BreakerBreakerCode Min. Copper (60°C)Maker's Min. CopperCopper to Run
Gree Vireo Gen3 3VIR09HP230V1A9,000 BTU (rated 9,100)208-230V9A15A15A#14per code#14
MrCool DIY 4th Gen 9K9,000 BTUdata plate19A25A25A#12#12#12
Gree Vireo Gen3 3VIR12HP230V1A12,000 BTU208-230V10A15A15A#14per code#14
MrCool DIY 4th Gen DIY-12-HP-C-115C12,000 BTU115V19A25A25A#12#12#12
Gree Vireo Gen3 3VIR18HP230V1A18,000 BTU208-230V15A20A20A#14per code#14
MrCool DIY 4th Gen DIY-18-HP-C-230C18,000 BTU208-230V18A30A30A#12#10#10
Gree Vireo Gen3 3VIR24HP230V1A24,000 BTU (rated 22,000)208-230V16A25A25A#12per code#12
MrCool DIY 4th Gen DIY-24-HP-C-230C24,000 BTU208-230V22A35A35A#10#8#8
MrCool DIY 4th Gen DIY-36-HP-C-230C36,000 BTU208-230V28A35A35A#10#8#8

The conductor has to carry the MCA where it is actually installed. Take its NEC Table 310.16 ampacity in the column matching the terminations (NEC 110.14(C)), correct it for the ambient (NEC 310.15(B)(1), plus the rooftop adder of NEC 310.15(B)(2) where the raceway sits in direct sun), adjust it for more than three current-carrying conductors (NEC Table 310.15(C)(1)), and compare THAT figure to the MCA. A conductor that clears the MCA on the printed table can be well under it on a hot roof or in a crowded raceway. Ground per NEC 250.122. A 115V unit takes a single-pole breaker: MrCool's 12,000 BTU unit is 115V with a 25A maximum. Where the maker prints a larger minimum copper than the code minimum (MrCool on its 18K #10 (code minimum #12), 24K #8 (code minimum #10) and 36K #8 (code minimum #10)), the maker's minimum governs (NEC 110.3(B)) and the copper to run column reads it; Gree's submittals say “Size Per Local Code”. MrCool's manual prints no voltage for its 9K, so that row reads the data plate.


Size It to Your Nameplate

It opens on the 15 A circuit of Gree's 9,000 and 12,000 BTU units. Enter your unit's MCA as the load and leave Continuous load off (the MCA already includes the 125%) to get the exact wire, or work from the compressor and fan data with the MCA/MOCP calculator. The breaker line is a general-circuit value, not the maximum breaker (MOCP) on the data plate.

Loading calculator...

Need the MCA itself? Use the MCA / MOCP calculator →

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

What size wire do I need for a mini split?

Size the wire to the outdoor unit's nameplate MCA (minimum circuit ampacity), not to the BTU rating. The BTU does not set it: Gree's 12,000 BTU Vireo Gen3 lists MCA 10A and MrCool's 12,000 BTU DIY 4th Gen lists 19A. Across Gree and MrCool's 9,000 to 12,000 BTU units the MCA runs 9 to 19A, and the units take #14 to #12 copper, the code minimum (60°C column of NEC Table 310.16); across their 18,000 to 24,000 BTU units it runs 15 to 22A, and they take #14 to #8 copper, where the code minimum alone is #14 to #10 and the maker's printed minimum is larger. MrCool's manual prints a larger minimum copper than the code's on its 18K #10 (code minimum #12), 24K #8 (code minimum #10) and 36K #8 (code minimum #10), and the maker's minimum governs (NEC 110.3(B)). Always read the data plate: the MCA and the 'maximum fuse/breaker' are printed there.

What breaker size for a mini split?

Use a standard breaker at or below the nameplate 'maximum overcurrent protection' (MOCP; Gree's submittals print it as MCA / MOCP and MrCool's manual as MOP): double-pole on a 208-230V unit, single-pole on a 115V one. Across the 9 named single-zone units in the table below, the maximum breaker runs 15 to 35A. Do not exceed the nameplate maximum, and do not size the breaker to the BTU: Gree's 12,000 BTU unit lists a 15A maximum and MrCool's 12,000 BTU unit a 25A maximum.

Can a mini split run on a 15 amp circuit?

Some can, and the nameplate decides. Gree's 9,000 and 12,000 BTU Vireo Gen3 units list MCA 9A and 10A with a 15A maximum breaker, so a 15A circuit on #14 copper meets them. MrCool's 9K and 12K list MCA 19A with a 25A maximum, which a 15A circuit does not carry. If the MCA exceeds 15A, step up the wire; never exceed the maximum breaker.

Does a mini split need a dedicated circuit and disconnect?

A disconnect, yes: a disconnecting means must be within sight of and readily accessible to the outdoor condenser (NEC 440.14), which is the pull-out disconnect box mounted near the unit. A circuit to itself is not something Article 440 requires: NEC 440.22(B) sets the breaker where the compressor shares a circuit with other loads, so a dedicated circuit comes from the manufacturer's instructions where they call for one. The small interconnect cable between the indoor and outdoor units is separate from this branch circuit and is sized per the manufacturer.

Does a mini split's outdoor unit need GFCI protection?

GFCI: at a dwelling, a mini split's outdoor outlet falls under NEC 2023 210.8(F): "For dwellings, all outdoor outlets, other than those covered in 210.8(A), Exception No. 1, including outlets installed in the following locations, and supplied by single-phase branch circuits rated 150 volts or less to ground, 50 amperes or less, shall be provided with GFCI protection:" The listed-HVAC exception expired on September 1, 2026 in the NEC's own text, but some states deleted that expiry and some never had the exception at all; the outdoor HVAC GFCI check answers it by state.

Is mini split wire different from central AC wire?

The method is identical (size to nameplate MCA and MOCP per NEC Article 440), and each unit has its own numbers. At 24,000 BTU (2 ton), Gree's and MrCool's mini splits list MCA 16A and 22A, while Goodman's and Daikin's 2 ton central condensers list 10.9A and 15.3A, so a mini split does not always draw less than a central unit of the same size. Always use each unit's own nameplate.


Related