NEC Article 440 (Air Conditioning)
What Size Wire for a Mini Split?
A ductless mini split is sized to the outdoor unit's nameplate, not the BTU. Here is how to read the MCA and max breaker, the typical ranges by size, and the calculator.
Wire from the MCA, Breaker from the Max Breaker
The outdoor condenser's data plate lists two numbers that set the circuit: the MCA (minimum circuit ampacity) sizes the conductor, and the maximum fuse/breaker (MOCP) sizes the overcurrent device. The MCA already includes the 125% factor for the compressor per NEC 440.32/440.33, so you just pick the smallest wire whose 75°C ampacity meets the MCA. Because mini splits are inverter-driven, the MCA is often surprisingly low, which is why a big-sounding 12,000 BTU unit can live on a 15A or 20A circuit.
Typical Mini Split Wire Size by BTU
Rough single-zone ranges only. Brand, voltage (115V vs 208-240V), and multi-zone configuration all shift the MCA, so the nameplate always wins over this table.
| Unit Size | Typical MCA | Max Breaker | Copper Wire |
|---|---|---|---|
| 9,000 BTU (3/4 ton) | ~8 - 12A | 15A | #14 |
| 12,000 BTU (1 ton) | ~12 - 15A | 15 - 20A | #14 |
| 18,000 BTU (1.5 ton) | ~15 - 18A | 20 - 25A | #12 |
| 24,000 BTU (2 ton) | ~18 - 22A | 25 - 30A | #12 - #10 |
| 36,000 BTU (multi-zone) | ~25 - 30A | 30 - 40A | #10 |
Wire at the 75°C column of NEC Table 310.16 sized to the MCA; ground per NEC 250.122. Small 115V units may run a 20A single-pole circuit. These are typical values, not code values: the outdoor unit's data plate carries the exact MCA and max breaker.
Size It to Your Nameplate
Enter your unit's MCA as the load to get the exact wire, or work from the compressor and fan data with the MCA/MOCP calculator.
Need the MCA itself? Use the MCA / MOCP calculator →
Frequently Asked Questions
What size wire do I need for a mini split?
Size the wire to the outdoor unit's nameplate MCA (minimum circuit ampacity), not to the BTU rating. Mini splits are inverter-driven and efficient, so their MCA is often lower than a conventional AC of the same capacity. As a rough guide, a 9,000-12,000 BTU (3/4 to 1 ton) unit runs an MCA around 10-15A and takes #14 copper on a 15-20A breaker; an 18,000-24,000 BTU unit runs 15-22A and needs #12 or #10. Multi-zone condensers run higher. Always read the data plate: the MCA and the 'maximum fuse/breaker' are printed there.
What breaker size for a mini split?
Use a standard breaker at or below the nameplate 'maximum overcurrent protection' (MOCP, sometimes labeled max fuse/breaker). For most single-zone mini splits that is a 15A, 20A, or 25-30A double-pole breaker at 208-240V. Do not exceed the nameplate maximum, and do not size the breaker to the BTU: a 12,000 BTU unit is commonly a 15A or 20A circuit despite the large cooling number.
Can a mini split run on a 15 amp circuit?
Many smaller mini splits can. A 9,000-12,000 BTU single-zone unit often has an MCA under 15A and a max breaker of 15A or 20A, so a dedicated 15A (#14) or 20A (#12) 208-240V circuit is typical. Confirm on the nameplate: if the MCA exceeds 15A or the max breaker is higher, step up. Larger and multi-zone units need 20-30A circuits.
Does a mini split need a dedicated circuit and disconnect?
Yes. The outdoor condenser must be on its own dedicated branch circuit (NEC 440.6/440.31), and a disconnecting means must be within sight of and readily accessible to it (NEC 440.14), which is the pull-out disconnect box mounted near the unit. The small interconnect cable between the indoor and outdoor units is separate from this branch circuit and is sized per the manufacturer.
Is mini split wire different from central AC wire?
The method is identical (size to nameplate MCA and MOCP per NEC Article 440), but the numbers differ: an inverter mini split usually draws less than a conventional single-stage AC of the same tonnage, so a 1-ton mini split may sit on a 15A circuit while a 1-ton conventional condenser might want a 20-30A circuit. Always use each unit's own nameplate.
Related
Central AC Wire Size
Same MCA/MOCP method for a conventional central air conditioner or heat pump.
MCA / MOCP Calculator
Compute minimum circuit ampacity and max breaker from the unit data.
Wire Size for Appliances
Dryer, range, water heater, hot tub, and more: the circuit for each.
R-454B Superheat & Subcooling
Charge check for the A2L refrigerant in new mini splits.