NEC Article 625 EV Charging

Tesla Wall Connector Wire & Breaker Size

The Wall Connector is field-adjustable, so the wire and breaker follow the setting you commission. Here is the full-output spec, every setting Tesla's manual prints, and the install calculator, with Tesla's own rules on top of the NEC Article 625 continuous-load basis.

Quick answer: At its full 48A output, a Tesla Wall Connector needs a 60A breaker and #6 copper on a 75°C-rated breaker, or #4 copper on a 60°C-rated one (Tesla: 90°C THWN-2), with a #10 copper ground. Copper only: Tesla prints “COPPER WIRE TERMINATIONS ONLY for landing in Wall Connector wirebox terminals.” It is hardwired only. Set it to a lower amp limit and the circuit follows that setting, but only where NEC 625.42(B) and NEC 750.30(C) are satisfied on the installed equipment (see the conditions under the table).

Wall Connector Amp Setting to Wire & Breaker

Pick the setting your circuit supports and commission the charger to it. The breaker is the one Tesla's manual prints for each setting (pdf 9 / printed 7); the copper is the code's conductor for that breaker, with Tesla's own minimum applied at full power and its terminals' smallest size (12 AWG) where the code's is smaller. A setting sizes the circuit only where NEC 625.42(B) and NEC 750.30(C) are satisfied on the installed unit. The conditions are under the table.

Tesla Wall Connector setting, Tesla's breaker, and copper conductor by the breaker's temperature rating. Copper only. A setting sizes the circuit only where NEC 625.42(B) and NEC 750.30(C) are satisfied on the installed unit.

Swipe the table sideways to see the rest of its columns. →

SettingBreakerCopper, 75°C-rated breakerCopper, 60°C-rated breakerGround (Cu)
48A (max)60A#6#4#10
40A50A#8#6#10
32A40A#8#8#10
24A30A#10#10#10
16A20A#12#12#12
12A15A#12#12#12
What has to be true before a setting sizes the circuit

Sizing a circuit from a dialled-down setting rather than from the unit's 48 A rating is NEC 625.42(B), and 625.42(B) attaches conditions. They are facts about the installed equipment, so no calculator can check them and this page does not claim they hold on your job. A qualified person verifies them on site, or the circuit is sized from the full rating:

  • Where the adjusting means is part of an energy management system, that system uses monitoring and controls to automatically cease current flow if it malfunctions. 750.30(C) applies its subdivisions where an EMS is used to limit the current on a conductor. (NEC 750.30(C)(2))
  • Access to the ampere adjusting means is restricted by at least one of the five means 750.30(C)(3) names: behind a removable and sealable cover over the adjustment, behind a cover or door that needs a tool to open, behind a locked door accessible only to qualified personnel, password protected with the password held by qualified personnel only, or software whose access to the adjusting means is password protected for qualified personnel only. (NEC 750.30(C)(3))
  • The equipment supplying the branch circuit is field marked with the maximum current setting, the date of the calculation and setting, identification of the loads and sources associated with the current limiting feature, and the words "The setting for the EMS current limiting feature shall not be bypassed". Those markings meet the requirements in 110.21(B) and are located so they are clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment. (NEC 750.30(C)(4))
  • The adjustment was made in accordance with the manufacturer's instructions, and the adjusted rating appears on the rating label with enough durability to withstand the environment involved. (NEC 625.42(B) / 110.3(B))

NEC 625.42(B) + 750.30(C) + 110.3(B). NEC 625.42(A) reaches the service and feeder load calculation; only (B) changes the EVSE's own ampere rating, which is what 625.41 sizes the branch from.

The copper columns are NEC Table 310.16 at the termination temperature NEC 110.14(C)(1) allows: the 75°C column only where the breaker and the equipment are both listed and identified for it, otherwise the 60°C column (NM-B cable is always 60°C, NEC 334.80). Tesla prints a conductor only for full power; below it, “If installing for less than maximum power, refer to local electrical code to select correct conductors and ground wire size that are suitable for the chosen circuit breaker.” Tesla's terminal blocks take “Terminal Blocks: 12-4 AWG (3.5 - 25 mm2), copper only” (pdf 7 / printed 5). Continuous-load sizing per NEC 625.41; ground per NEC 250.122.


Your Exact Run: Wire, Panel, and Parts

It opens on the Wall Connector at 48A, the full-output install. Enter your run length, conductor material, and panel to get the exact wire, voltage drop, panel-capacity check, and a parts list.

Loading calculator...

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

What size breaker do I need for a Tesla Wall Connector?

At its maximum 48A output, a Tesla Wall Connector needs a 60A double-pole breaker. Tesla's manual prints the breaker for each setting (60A breaker = 48A, 50A breaker = 40A, 40A breaker = 32A, 30A breaker = 24A, 20A breaker = 16A, 15A breaker = 12A), and "Circuit breaker size is programmed during the commissioning process." Each is 125% of the output, rounded up to a standard breaker, as NEC 625.41 requires for this continuous load. The route this tool recognizes for a smaller branch is the EVSE's own restricted-access adjusted setting under NEC 625.42(B), and it is a route a calculator cannot take for you: the conditions it attaches, under 750.30(C) and the manufacturer's instructions, are facts about installed equipment. The 4 conditions this tool can name are not a full compliance checklist. Size from the full rating unless a qualified person has verified them, and 625.42(B) itself, on site.

What wire size for a Tesla Wall Connector?

At full power (48A on a 60A breaker), Tesla's current manual sets the conductor by the breaker's temperature rating: "For 60°C rated circuit breaker, use minimum 4AWG, 90°C THWN-2-rated copper wire for conductors." and "For 75°C rated circuit breaker, use minimum 6AWG, 90°C THWN-2-rated copper wire for conductors." The code gives the same pair: #6 copper on 75°C-rated terminations, #4 at 60°C. Copper only: "COPPER WIRE TERMINATIONS ONLY for landing in Wall Connector wirebox terminals." Below full power Tesla says to "refer to local electrical code"; the table above gives the code's conductor at each setting. Check voltage drop on a long run.

Does a Tesla Wall Connector need a GFCI breaker?

Tesla's current manual lists "Ground Fault Circuit Interrupter: Integrated CCID20" (pdf 7 / printed 5). NEC 625.54 requires GFCI protection for receptacles installed for electric vehicle charging, and the Wall Connector is hardwired only ("Hardwire branch circuits to disconnects or circuit breakers. Do NOT install cord-and-plug type connections."), so no receptacle is involved. On the full-output 60A breaker that is the end of it. On a 50A breaker or smaller (the 40A setting and below), NEC 210.8(F) applies: At a dwelling, the 2023 NEC's 210.8(F) requires GFCI protection for an outdoor outlet and for an outlet in a garage with its floor at or below grade, an accessory building or a boathouse, on a single-phase circuit of 150 V or less to ground and 50 A or less; a hardwired charger's outlet there needs it. The current manual prints no instruction about a GFCI breaker.

Can I put a Tesla Wall Connector on a 60 amp breaker?

Yes, that is the full-output install: a 60A breaker with #6 copper on a 75°C-rated breaker, or #4 copper on a 60°C-rated one, lets the Wall Connector run at 48A. The breaker size is then programmed during commissioning so the unit never exceeds what the circuit allows.

Do I need a dedicated circuit for a Tesla Wall Connector?

Yes. The Wall Connector must be on its own dedicated branch circuit that serves no other load (NEC 625.40). NEC 625.40's own Exception permits one branch circuit to feed multiple EVSEs where 625.42(A) or (B) allows it; it does not permit an EVSE to share a circuit with an ordinary appliance. It cannot share a circuit with outlets, lights, or another charger unless the two are coordinated by a listed load-management system.


Related EV References