NEC Article 625 EV Charging

ChargePoint Home Flex Wire Size

The Home Flex is adjustable from 16 to 50 amps, so the wire follows the amperage you set. Here is the 48A spec, every setting ChargePoint's guide prints, and the plug-in versus hardwired difference.

Quick answer: At the 48A hardwired setting, the ChargePoint Home Flex needs #6 copper on a 60A breaker, on a 75°C-rated breaker only (its terminals take nothing larger than 6 AWG, and at 60°C the code needs more), with a #10 ground. Copper only. Any setting below the unit's 50A rating, including this 48A one, sizes the circuit only where NEC 625.42(B) and NEC 750.30(C) are satisfied on the installed equipment (see the conditions under the table). At its full 50A rating the circuit is a 70A breaker. Plug-in is allowed only at 40A and 32A.

Wire and Breaker by Amperage Setting

A setting sizes the circuit only where NEC 625.42(B) and NEC 750.30(C) are satisfied on the installed unit. ChargePoint Home Flex circuit by setting, from ChargePoint's guide (pdf 10 / printed 4), hardwired, copper

Swipe the table sideways to see the rest of its columns. →

SettingPower (240V)BreakerCopper, 75°C-rated breakerCopper, 60°C-rated breakerGround
16A3.8 kW20A#12#12#12
24A5.8 kW30A#10#10#10
32A7.7 kW40A#8#8#10
40A9.6 kW50A#8#6#10
48A11.5 kW60A#6does not land#10
50A (max)12.0 kW70A#6does not land#8
What has to be true before a setting sizes the circuit

Sizing a circuit from a dialled-down setting rather than from the unit's 50 A rating is NEC 625.42(B), and 625.42(B) attaches conditions. They are facts about the installed equipment, so no calculator can check them and this page does not claim they hold on your job. A qualified person verifies them on site, or the circuit is sized from the full rating:

  • Where the adjusting means is part of an energy management system, that system uses monitoring and controls to automatically cease current flow if it malfunctions. 750.30(C) applies its subdivisions where an EMS is used to limit the current on a conductor. (NEC 750.30(C)(2))
  • Access to the ampere adjusting means is restricted by at least one of the five means 750.30(C)(3) names: behind a removable and sealable cover over the adjustment, behind a cover or door that needs a tool to open, behind a locked door accessible only to qualified personnel, password protected with the password held by qualified personnel only, or software whose access to the adjusting means is password protected for qualified personnel only. (NEC 750.30(C)(3))
  • The equipment supplying the branch circuit is field marked with the maximum current setting, the date of the calculation and setting, identification of the loads and sources associated with the current limiting feature, and the words "The setting for the EMS current limiting feature shall not be bypassed". Those markings meet the requirements in 110.21(B) and are located so they are clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment. (NEC 750.30(C)(4))
  • The adjustment was made in accordance with the manufacturer's instructions, and the adjusted rating appears on the rating label with enough durability to withstand the environment involved. (NEC 625.42(B) / 110.3(B))

NEC 625.42(B) + 750.30(C) + 110.3(B). NEC 625.42(A) reaches the service and feeder load calculation; only (B) changes the EVSE's own ampere rating, which is what 625.41 sizes the branch from.

The copper columns are NEC Table 310.16 at the termination temperature NEC 110.14(C)(1) allows. “Does not land” marks a setting where the code's 60°C conductor is larger than the Home Flex terminal takes (“The field-wiring terminal is rated to 105 °C (221 °F) and accepts a maximum of 16 mm2 (6 AWG) wire.”, pdf 10 / printed 4): there, only a 75°C-rated breaker with 75°C-rated conductors works. The 50A row uses #6 on a 70A breaker via the NEC 240.4(B) next-standard-size allowance.


Hardwired for 48A, or Plug-In for 40A

The Home Flex installs two ways. Hardwired, it reaches 48A (or 50A); on those 60A and 70A circuits neither NEC 625.54 nor 210.8(F) asks a GFCI breaker, while a hardwired install on 50A or less at a dwelling, outdoors or in a garage with its floor at or below grade, an accessory building or a boathouse, needs one (2023 NEC 210.8(F)). As a plug-in with a NEMA 14-50 or 6-50 plug, ChargePoint's table allows it only on a 50A circuit (40A) or a 40A circuit (32A), and being cord-and-plug it needs a GFCI breaker per NEC 625.54. So for the fastest charging, hardwire it; for an existing 14-50 outlet, plug it in and accept the 40A cap.


Size Your Home Flex Install

The calculator opens on the Home Flex at the 48A setting, and because the unit is a 50A model it asks you to check the rating. Enter the unit's full rating as the charger amps and the setting you dial it to in the adjusted-setting field, then your run and panel, to get the exact wire, voltage drop, panel-capacity check, and a parts list.

Loading calculator...

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

What size wire does a ChargePoint Home Flex need?

It depends on the amperage you set it to, because the Home Flex is adjustable from 16A up to 50A, and ChargePoint's guide prints no wire size: "Consult all applicable codes for breaker and wire sizing requirements." At 48A hardwired the code gives #6 copper on a 60A breaker with a #10 ground, on a 75°C-rated breaker only: at 60°C the code needs a larger conductor, and the guide says the terminal "is rated to 105 °C (221 °F) and accepts a maximum of 16 mm2 (6 AWG) wire." A lower setting goes with a smaller circuit: 40A needs #8 Cu (75°C-rated breaker; #6 Cu at 60°C) on a 50A breaker. Copper only: "Use 90°C wire copper conductors only." A setting sizes the circuit only where NEC 625.42(B) and NEC 750.30(C) are satisfied on the installed unit.

What breaker does a ChargePoint Home Flex use?

ChargePoint's guide prints the circuit for each setting: 70A for 50A, 60A for 48A, 50A for 40A, 40A for 32A, 30A for 24A, 20A for 16A (pdf 10 / printed 4), each at least 125% of the setting as its "continuous load device" caution requires. A plug-in install needs a GFCI breaker under NEC 625.54. A hardwired install on a 50A breaker or smaller falls under NEC 210.8(F) at a dwelling: At a dwelling, the 2023 NEC's 210.8(F) requires GFCI protection for an outdoor outlet and for an outlet in a garage with its floor at or below grade, an accessory building or a boathouse, on a single-phase circuit of 150 V or less to ground and 50 A or less; a hardwired charger's outlet there needs it. On the 60A and 70A circuits neither rule applies.

Can the ChargePoint Home Flex charge at 50 amps?

Yes, that is its maximum, on a 70A circuit (50 x 1.25 = 62.5A, rounded up), hardwired only. Because the Home Flex terminals take nothing larger than 6 AWG, a 50A install uses #6 copper on that 70A breaker under the NEC 240.4(B) next-standard-size rule, on 75°C-rated terminations only, and only on an individual branch circuit, not one supplying more than one receptacle for cord-and-plug-connected portable loads (NEC 240.4(B)(1)). ChargePoint notes "A junction box may be required when using breakers rated higher than 50 A."

Can I plug in a ChargePoint Home Flex instead of hardwiring?

Yes, at two settings only: ChargePoint's table allows plug-in on the 50A circuit (40A) and the 40A circuit (32A), with a NEMA 14-50 or 6-50 receptacle, and hardwire at every setting. A plug-in install on a 14-50 or 6-50 needs a GFCI breaker (NEC 625.54). To get 48A or 50A you must hardwire it.

Is the ChargePoint Home Flex wire size the same as a Tesla Wall Connector?

On a 75°C-rated breaker at 48A, yes: both take #6 copper on a 60A breaker. On a 60°C-rated breaker they differ: Tesla's manual asks for 4 AWG and its terminals take up to 4 AWG, while the Home Flex terminals take nothing larger than 6 AWG, so the Home Flex at 48A needs a 75°C-rated breaker. Both makers print copper only. The Home Flex also goes to 50A on a 70A circuit; the Tesla Wall Connector tops out at 48A.


Related EV References