Electrical / runnable MCP tool
Run the Voltage Drop Calculator in your AI assistant
Through the free Intry MCP server, Claude, ChatGPT, or Cursor runs this exact calculator and hands back a verdict and the cited source, not a guess. Tool name: voltage_drop.
What you get back: THREE sizes and they are not interchangeable: the voltage-drop-only minimum (a recommendation), the ampacity minimum at standard conditions (a requirement), and the minimum overall, which is the LARGER of the two (this tool's recommendation: the ampacity minimum is required, the voltage-drop minimum is advised). Where no single conductor carries the load, the last two say so and name conductors in parallel. Where voltage drop sets a larger single conductor than the ampacity minimum, a row states that a wire-type ground goes up too, in proportion to the circular mils (NEC 250.122(B)), with no ground size.
How it computes the answer
Computed from NEC Chapter 9 Table 9 (effective-Z) or Table 8 (K-method); the 3%/5% flag is the advisory 210.19/215.2 recommendation, not a code limit.
What it cites
Your assistant calls the same engine the interactive calculator calls, with the inputs listed under Inputs. It takes no conduit type or power factor and computes by the K-factor method; the interactive calculator takes both and computes by NEC Chapter 9 Table 9, so on a long run the two can give a different drop and a different minimum size. These are the interactive calculator's sources, including the ones for inputs only it takes.
- NEC Chapter 9, Table 9
- AC resistance and reactance (ohms per 1000 ft) for building conductors, used for the effective-Z method. The effective impedance is computed from the table's R and XL at your power factor (0.85 by default, the table's own basis). Fetched verbatim two-pass from the NFPA 70 primary and cross-checked against the 2005-cycle CEC.
- NEC Chapter 9, Table 8
- Conductor circular-mil area, used for the simple K-method (2 × K × I × L / CM single-phase, √3 for three-phase; K = 12.9 copper, 21.2 aluminum). Read from the primary.
- NEC 210.19 and 215.2 Informational Notes
- The 3% branch-circuit and 5% total voltage-drop figures are an NEC recommendation, not an enforceable limit. We flag against that recommendation and say so; the honest ceiling is that this is advisory guidance, not a code maximum.
- NEC 250.122(B)
- Where voltage drop sets a larger single conductor than the ampacity minimum, the voltage drop calculator and the assistant tool each tell you the ground wire goes up too, from their own drop calculation (the calculator by Chapter 9 Table 9 for your conduit and power factor, the assistant tool by the K-factor method), and the calculator carries it into the copied, saved and sent reading. 250.122(B) says that where ungrounded conductors are "increased in size for any reason other than as required in 310.15(B) or 310.15(C), wire-type equipment grounding conductors, if installed, shall be increased in size proportionately to the increase in circular mil area of the ungrounded conductors" (NFPA 70, 2023 edition, page 70-157). Its Exception lets a qualified person size the grounding conductor instead to provide an effective ground-fault current path under 250.4(A)(5) or 250.4(B)(4) (page 70-138). The tool names the rule and does not size that conductor: Table 250.122 is entered by the breaker, which this tool does not ask for, so the ground wire size chart, linked beside the sizing mode's answer, takes the breaker and computes the increase.
- NEC 210.19(A), 215.2(A) and 430.22, by circuit
- In check mode you pick the circuit, and the wire you name is checked against that circuit's own rule. A branch circuit takes 210.19(A) (page 70-83), with 240.4(D)'s limit on small conductors. A feeder takes 215.2(A), "not less than the larger of 215.2(A)(1) or (A)(2)" (page 70-90), with the same 240.4(D) limit. A motor branch circuit takes 430.22, "not less than 125 percent of the motor full-load current rating" for a single motor in continuous duty (page 70-344), in the column 110.14(C)(1)(a) sets for the motor, and 240.4(D) does not limit it, because 240.4(G) and Table 240.4(G) send motor circuit conductors to Article 430 (pages 70-123 and 70-124).
The code sections those sources name, each with the edition and the page the book prints it on:
Swipe the table sideways to see the rest of its columns. →
| Code and edition | Section | Printed page |
|---|---|---|
| NEC 2023 | Chapter 9 Table 9 | 70-726 |
| NEC 2023 | Chapter 9 Table 8 | 70-725 |
| NEC 2023 | 210.19 | 70-83 |
| NEC 2023 | 215.2 | 70-90 |
| NEC 2023 | 250.122(B) | 70-157 |
| NEC 2023 | 210.19(A) | 70-83 |
| NEC 2023 | 215.2(A) | 70-90 |
| NEC 2023 | 430.22 | 70-344 |
The resistance and reactance are NEC table values looked up by the engine; the drop and percentage are computed from them and the run you enter. The 3%/5% verdict is advisory guidance, not a code limit, and is labeled that way.
The full receipt, with every source and how each is cross-checked, is on the interactive Voltage Drop Calculator.
Ask your assistant
The one rule that makes it reliable: name Intry in your question. That is what tells Claude to run the voltage_drop tool and answer with the real number, the verdict, and the citation. Leave Intry out and Claude may just guess from memory, which is exactly what you are trying to avoid. Type something like:
What it refuses or sets aside
Run through its MCP tool, which takes no circuit, it checks the wire you name as a branch circuit: when that wire is too small to carry the load's current, it tells you not to use it and names NEC 210.19(A), whatever the voltage drop works out to.
Inputs
Swipe the table sideways to see the rest of its columns. →
| Field | Required | Accepts | Range | What it is |
|---|---|---|---|---|
| wireSize | yes | 14, 12, 10, 8, 6, 4, 3, 2, 1, 1/0, 2/0, 3/0, 4/0, 250, 300, 350, 400, 500, 600, 700, 750, 800, 900, 1000, 1250, 1500, 1750, 2000 | Conductor size, AWG or kcmil (e.g. '12', '1/0', '250'). | |
| amps | yes | number | more than 0 | Load current in amps. |
| length | yes | number | 0 or more | One-way run length in feet. |
| voltage | optional | number | more than 0 | System voltage (default 240). |
| phase | optional | single, three | single or three phase (default single). | |
| material | optional | cu, al | cu = copper, al = aluminum (default cu). |
Add Intry to Claude
One paste and Claude can run this tool and the other calculators on Intry's MCP server, right from your phone.
- Claude opens with the Intry connector already filled in. Review it and click Add.
- (If a field is blank, paste the link below into the URL field.)
- In any chat, tap + then Connectors and switch Intry on. Then name Intry in your question (“use Intry to…”) so Claude runs the tool instead of guessing.
https://www.intrysys.com/api/mcpNo login, no API key, and it works on every Claude plan, right from your phone.
Using ChatGPT, Cursor, or a dev tool? See the developer setup on the main page. The endpoint is https://www.intrysys.com/api/mcp.
Every answer comes with the cited NEC section, so you can check it or show an inspector. The numbers come from the same calculator we run on intrysys.com, and our automated checks hold its answers against their sources before anything goes live, for the cases the checks cover, not for every input you can enter.