Fixed-orifice charging (piston / cap tube)
Target Superheat Calculator
Charge a fixed-orifice air conditioner the right way. Enter the indoor return-air wet-bulb and the outdoor dry-bulb, and the calculator reads target superheat from the Title 24 CEC RA3.2-2 chart, compares it to your measured superheat, and tells you to add, recover, or leave it alone. Full target superheat chart below.
Target Superheat Chart (Fixed Orifice)
Target superheat in °F by indoor return-air wet-bulb (columns) and outdoor dry-bulb at the condenser (rows). Read across to the wet-bulb you measured and down to the outdoor temperature. A dash means the target is below 5°F for those conditions, where a superheat charge check cannot be performed. The calculator above interpolates the full table between these points.
| Outdoor °F \ WB °F | 56 | 60 | 63 | 66 | 70 | 73 | 76 |
|---|---|---|---|---|---|---|---|
| 75 | 6 | 12 | 16 | 21 | 27 | 32 | 36 |
| 80 | – | 9 | 13 | 18 | 25 | 29 | 34 |
| 85 | – | – | 10 | 15 | 22 | 27 | 32 |
| 90 | – | – | 7 | 13 | 20 | 26 | 31 |
| 95 | – | – | – | 10 | 18 | 24 | 29 |
| 100 | – | – | – | 7 | 15 | 22 | 28 |
| 105 | – | – | – | – | 13 | 20 | 26 |
| 110 | – | – | – | – | 11 | 18 | 24 |
| 115 | – | – | – | – | 9 | 16 | 23 |
The target does not depend on the refrigerant: it is set by the load, so this one chart works for R-410A, R-454B, R-22, and R-32 on a fixed orifice. What changes per refrigerant is how you read the measured superheat, since saturated suction temperature comes from that refrigerant’s PT chart.
How to Calculate Target Superheat
- Confirm the metering device is a fixed orifice (piston or capillary tube). If it is a TXV or EXV, stop: charge that system by subcooling, not target superheat.
- Measure the indoor return-air wet-bulb with a wet-bulb thermometer or a psychrometer at the return grille or entering the evaporator coil.
- Measure the outdoor dry-bulb in the air entering the condenser, in shade, not in direct sun off the coil.
- Look up target superheat from the chart above (or let the calculator interpolate the CEC RA3.2-2 table for the exact wet-bulb and dry-bulb).
- Measure actual superheat: suction line temperature minus the saturated suction temperature read from the refrigerant’s PT chart at the suction pressure.
- Compare. Within ±5°F of target, the charge meets the CEC ±5°F charge-verification criterion. More than 5°F above target, confirm airflow and then add refrigerant. More than 5°F below target, recover. If measured superheat is at or below 3°F, stop: that is floodback, so recover before anything else. Re-check after every change, because the target moves as the indoor wet-bulb drops.
Worked Example: R-410A Piston System on a 90°F Day
A fixed-orifice R-410A condenser in cooling. Conditions: outdoor dry-bulb 90°F, indoor return-air wet-bulb 66°F. Field readings: suction pressure 118 psig, suction line temperature 62°F.
Target superheat (WB 66 / DB 90, CEC RA3.2-2) = 13°F
Saturated suction temp at 118 psig (R-410A) = 40°F
Measured superheat = 62°F − 40°F = 22°F
Difference = 22 − 13 = +9°F
Diagnosis: Measured superheat is 9°F above target, past the ±5°F tolerance. High superheat can also be low indoor airflow or a restriction, so confirm the filter, coil, and blower first. Once airflow checks out, the charge is low: add R-410A slowly and re-measure the wet-bulb and superheat after each addition. As you add refrigerant the coil pulls the indoor wet-bulb down, which lowers the target, so keep re-reading it.
Target Superheat vs Subcooling: Which One to Charge By
The metering device decides the method. A fixed orifice (piston or cap tube) does not control superheat, so superheat floats with the charge and the load. That makes superheat the charging signal, and you match it to the load-based target above. A thermostatic or electronic expansion valve actively holds superheat near a set value, so superheat barely moves with charge on those systems and tells you little. Charge a TXV or EXV by subcooling instead, which the valve does not regulate.
Get the method wrong and the numbers lie to you: reading target superheat on a TXV, or subcooling on a piston, sends you chasing a charge problem that is not there. Check the metering device first, then pick the method.
superheat_subcooling tool live, handing back the verdict with its cited source instead of a guess. Then keep the reading as one job in the Intry app.Target Superheat FAQs
What is target superheat?
Target superheat is the superheat a fixed-orifice (piston or capillary-tube) air conditioner should read for the current operating load. It is set by two things: the indoor return-air wet-bulb temperature and the outdoor dry-bulb temperature entering the condenser. You add or recover refrigerant until the measured superheat matches the target. It applies to fixed-orifice metering only; TXV and EXV systems are charged by subcooling, not target superheat.
How do you calculate target superheat?
Target superheat is read from a charging chart indexed by indoor return-air wet-bulb and outdoor dry-bulb, not from a formula you keep in your head. The reverse-engineered field shortcut is [(3 x indoor wet-bulb) - 80 - outdoor dry-bulb] / 2, but it drifts up to about 7 degrees at the corners, so a chart is more accurate. This calculator interpolates the California Title 24 CEC RA3.2-2 target superheat table. Example: at 66F indoor wet-bulb and 90F outdoor dry-bulb, target superheat is about 13F.
What should target superheat be for R-410A?
Target superheat does not depend on the refrigerant. It is set by the load (indoor wet-bulb and outdoor dry-bulb), so the target for R-410A, R-454B, R-22, or R-32 on a fixed orifice is the same at the same conditions. What changes per refrigerant is how you read the measured superheat, because saturated suction temperature comes from that refrigerant's pressure-temperature chart. A chart labeled 410A target superheat is really the same load-based table with an R-410A PT scale attached.
What is a good target superheat number for a fixed orifice?
There is no single good number: target superheat ranges from about 5F on a hot, dry day into the low 30s in mild, humid conditions with a high indoor wet-bulb, as the chart on this page shows. It rises as indoor wet-bulb rises (more latent load) and falls as outdoor dry-bulb rises. That is why a fixed-orifice system charged to a flat number like 12F is often wrong for the conditions. Charge to the chart target for the wet-bulb and dry-bulb you actually measure.
What is the difference between target superheat and actual superheat?
Actual (measured) superheat is what the system is doing right now: suction line temperature minus the saturated suction temperature from the refrigerant PT chart. Target superheat is what it should be doing for the current load. You compare the two: if measured superheat is more than about 5F above target the charge is low (add refrigerant after confirming airflow); if it is more than 5F below target the system is overcharged (recover).
Do you use target superheat on a TXV system?
No. A thermostatic or electronic expansion valve actively holds superheat near a fixed value on its own, so superheat tells you almost nothing about the charge on a TXV or EXV system. Charge those by subcooling instead. Target superheat is the charging method for fixed-orifice metering (pistons and capillary tubes), where superheat floats with the charge and the load.
Why does target superheat change while I am charging?
As you add refrigerant the evaporator gets colder and pulls more moisture out of the indoor air, so the indoor return-air wet-bulb drops. A lower wet-bulb means a lower target superheat. Re-measure the wet-bulb and re-read the target after each addition rather than charging to the first number you looked up, or you will end up overcharged.
Why does the calculator sometimes say target superheat is below 5F?
When the outdoor dry-bulb is high and the indoor wet-bulb is low, the CEC RA3.2-2 table has no target value because superheat would be below 5F, and a valid superheat charge check cannot be performed that close to floodback. The honest answer is to let the system run closer to design conditions, or charge by subcooling or weigh-in instead of guessing a low number. The calculator reports below minimum rather than inventing a value.
Where does the target superheat chart come from?
The values in this calculator come from the California Energy Commission 2022 Reference Appendices (publication CEC-400-2022-010-AP), Reference Residential Appendix RA3, Table RA3.2-2 Target Superheat. The whole 61-row table was parsed from the source PDF and checked against AC Service Tech's independent chart at 66F wet-bulb / 90F dry-bulb, where both read 13F. The fixed-metering superheat pass tolerance is plus or minus 5F per Table RA3.2-1.
Related Calculators
Superheat & Subcooling Calculator
The full calculator with 10+ refrigerants, TXV and fixed-orifice targets, and the four-quadrant diagnostic guide.
R-410A Superheat & Subcooling
The dominant fixed-orifice and TXV installed base. PT chart and charging targets for R-410A.
R-454B Superheat & Subcooling
The A2L that replaced R-410A in new equipment. PT chart, targets, and A2L charging notes.
R-22 Superheat & Subcooling
Legacy fixed-orifice systems still in the field. PT chart and charging targets for R-22.
R-32 Superheat & Subcooling
The pure A2L in ductless mini splits. PT chart, higher pressures, and charging targets.
Subcooling on a Heat Pump
Why heat pumps have no subcooling target in heating mode, and when the cooling-mode number still applies.
BTU / HVAC Load Calculator
Size the system by climate zone, insulation, windows, and duct location before you trust the old tonnage.
A2L Charge Limit Calculator
Maximum A2L charge for a room per UL 60335-2-40 and ASHRAE 15.2. Covers R-454B, R-32, and more.
Charging by superheat? Keep the whole call as one job.
Save the target, the measured superheat, and the verdict to the unit, then hand the reading to your AI assistant for the next step. Free, no login.