R-410A (Puron)

R-410A Superheat & Subcooling Calculator

Check charge on R-410A systems, still the biggest installed base in the field. The calculator opens preloaded for R-410A with a full PT chart, TXV and fixed orifice targets, and the four-quadrant diagnostic that turns two readings into a diagnosis.

Quick answer: Target superheat for R-410A with a TXV is 8–15°F and target subcooling is 8–14°F. R-410A saturates at 40°F at 118 psig suction and 100°F at 317 psig liquid. Superheat = suction line temp − saturated suction temp. Subcooling = saturated liquid temp − liquid line temp. Read both together: high superheat with low subcooling means low charge, low superheat with high subcooling means overcharge.

R-410A Pressure-Temperature Chart

R-410A saturation temperature at gauge pressure. Single column, near-zero glide.
Pressure (psig)Sat. Temp (°F)Publisher spread (°F)
26.9-20°F0.74
36.8-10°F0.45
48.60°F0.31
55.25°F0.21
62.310°F0.07
7015°F0
78.320°F0.06
87.325°F0.03
96.830°F0.10
10735°F0.16
11840°F0.18
13045°F0.06
14250°F0.24
15555°F0.35
17060°F0.04
18565°F0.06
20170°F0.03
21775°F0.28
23580°F0.22
25485°F0.15
27490°F0.12
29595°F0.12
317100°F0.13
340105°F0.19
365110°F0.08
391115°F0.04
418120°F0.06
446125°F0.14
476130°F0.13

About the spread column. It is the widest gap in saturation temperature between the published tables we hold, at that pressure, on the saturation column. Across this chart the widest is 0.74°F, at 26.9 psig. Our table and 1 other published table are compared here: 1 is a separate publisher. A narrow spread means the charts agree, which is not the same as the charts being right: they are all computed from equations of state fitted to lab data, and no field measurement settles it.

Where this table comes from. Hudson Technologies R-410A PT chart, verified cell by cell.
  • Checked against Arkema Forane R-410A, all 29 shipped cells within 1.0 psig [same printing as Weitron]
  • Checked against CoolProp-derived tables, anchor points agree [same model]
  • Checked against Weitron, reprinted as Daikin/Goodman PM-A2LPTC-USA_04-24, within 0.75 F across the shipped range [separate publisher]

R-410A is carried as a single-column near-azeotrope. Forane prints a real 0.0 to 1.2 psig liquid and vapor split, which biases subcooling by about 0.2 F across 90 to 130 F condensing. That sits inside the 1.0 F manufacturer tolerance and is left unmodelled and disclosed here rather than silently corrected.

A separate publisher can catch a transcription, edition or rounding error. A cross-check marked same model resolves to the same equation of state as the base table, so it is a consistency check rather than independent confirmation. One marked same printing prints numbers identical to another table listed here, so the two are one witness and we do not count them twice. Sources last re-verified 2026-08-05.

The two anchor points worth memorizing: 118 psig is a 40°F evaporator, and 317 psig is a 100°F condenser. Everything else on a residential cooling call is a short interpolation from one of those.


R-410A Target Superheat & Subcooling

Typical field targets (°F). Always verify against the equipment nameplate or manufacturer charging chart.
Metering deviceTarget superheatTarget subcoolingCharging method
TXV815°F814°FCharge by subcooling; the TXV holds superheat
Fixed orifice (piston)520°F410°FCharge by superheat from the manufacturer charging chart

R-410A: The Installed Base You Service Every Day

R-410A carried residential air conditioning from roughly 2010 to 2025. After R-22 equipment ended in 2010, virtually every ducted split system, package unit, and heat pump installed in the US shipped on R-410A, which means tens of millions of systems in the 10-to-15-year-old range that you will be diagnosing and recharging for another decade. It is a near-azeotropic blend of R-32 and R-125 (50/50 by weight) running on POE oil, with a GWP of 2,088, which is why the AIM Act phasedown pushed new equipment to R-454B and R-32 starting with January 2025 manufacture.

Phasedown changes the economics of a service call more than the technique. HFC production allowances step down on a schedule, so R-410A per-pound cost keeps rising. That makes "find the leak" the professional answer where "add a couple pounds" used to slide by, and it makes accurate charge verification worth the extra ten minutes: overcharging a system now wastes real money on both sides of the invoice.

R-410A Charging Notes

Charge R-410A as liquid from the cylinder, throttled slowly into the suction side. As a blend it should always be liquid-charged, even though its near-zero glide means fractionation is a technicality rather than a field problem. On TXV systems, charge to subcooling: get the system stable at steady-state, verify airflow first (a matted filter fakes a charge problem), then trim charge until subcooling lands on the nameplate value. On fixed-orifice systems, charge to the superheat chart using outdoor ambient and indoor wet bulb.

The most common R-410A misdiagnosis is charging by pressure alone. A 40°F evaporator at 118 psig is only meaningful once you know the suction line temperature; without it, low pressure could be low charge, low airflow, or a cold day. Superheat and subcooling turn raw pressures into a diagnosis, which is exactly what this calculator automates.


Worked Example: R-410A Split System with TXV

A 12-year-old R-410A split system, TXV metering, on a 90°F afternoon. Field readings: suction pressure 118 psig, suction line temperature 51°F, liquid pressure 317 psig, liquid line temperature 96°F.

Saturated suction temp at 118 psig = 40°F

Superheat = 51°F − 40°F = 11°F

Saturated liquid temp at 317 psig = 100°F

Subcooling = 100°F − 96°F = 4°F

Diagnosis: Superheat 11°F is inside the 8–15°F TXV target, but subcooling 4°F is below the 8–14°F target. Normal superheat with low subcooling on a TXV system means the valve is still compensating while the condenser runs short of liquid: the system is slightly low on charge. On a unit this age, leak-search the coils and service valves before adding refrigerant, then charge until subcooling reaches the nameplate target.


R-410A Charging FAQs

What should superheat be for R-410A?

On an R-410A TXV or EEV system, target roughly 8 to 12F of evaporator superheat measured at the coil outlet. Fixed-orifice and piston systems do not run a single number: you charge to a target superheat pulled off the manufacturer's target-superheat chart, which cross-references indoor return-air wet-bulb against outdoor dry-bulb and can land anywhere from about 5F on a hot, humid day to 25F or more on a cool, dry one. Confirm the reading with a P-T chart, converting suction saturation temperature at the measured low-side pressure (R-410A is near-azeotropic, so glide is negligible) and subtracting it from the actual suction-line temperature. Charge to superheat on fixed-orifice metering and to subcooling on TXV/EEV systems, but always verify superheat stays in range so the compressor never sees liquid floodback.

What is a good subcooling for R-410A?

A good subcooling for R-410A is 8 to 14F measured at the liquid-line service valve, which is a field rule of thumb rather than a figure any manufacturer publishes; the equipment’s own nameplate or charging chart is the target. On a metering-valve system subcooling is your primary charge indicator: the TXV holds evaporator superheat fixed, so you set the charge by adding refrigerant until liquid-line subcooling reaches the rated value. Always weigh the nameplate spec over any rule of thumb, since some high-efficiency condensers call for subcooling above this range. Subcooling is calculated as the saturated condensing temperature (from R-410A PT data at the measured liquid-line pressure) minus the actual liquid-line temperature.

What is normal superheat for R-410A?

With a TXV, target superheat for R-410A is 8-15°F measured at the suction line near the outdoor unit. With a fixed orifice (piston), target superheat depends on outdoor ambient and indoor wet bulb, typically 5-20°F, so use the manufacturer charging chart. Below 5°F superheat, liquid floodback to the compressor becomes a real risk.

What is normal subcooling for R-410A?

Target subcooling for R-410A with a TXV is 8-14°F, and the equipment's own nameplate or charging chart is the target when it prints one. Subcooling is the primary charging indicator on TXV systems because the valve holds superheat steady while charge level shows up in the condenser. Low subcooling means low charge; high subcooling means overcharge or a restriction.

What pressures should R-410A run at?

On a typical cooling call, the evaporator runs around 40°F saturated, which is about 118 psig suction. The condenser runs roughly 15-25°F above outdoor ambient, so on a 95°F day condensing at 110-120°F puts liquid pressure around 365-418 psig. Pressures far outside those windows point to a charge, airflow, or component problem rather than a bad gauge.

Is R-410A discontinued? Can I still buy it?

R-410A is being phased down, not banned. New residential AC and heat pump equipment moved to A2L refrigerants (mostly R-454B and R-32) for units manufactured from January 1, 2025, but existing R-410A systems can be legally serviced indefinitely. Virgin and reclaimed R-410A remain available; prices are climbing as AIM Act production allowances step down, so leak repair matters more than it used to.

Can I top off an R-410A system with R-454B or R-32?

No. Mixing refrigerants contaminates the circuit, makes PT readings meaningless, and leaves refrigerant that no recovery processor will accept. R-410A equipment is also not listed for flammable A2L refrigerants. Top off R-410A systems with R-410A only, and if you do not know what is in a system, identify it before adding anything.

Why is my superheat high and subcooling low on R-410A?

High superheat with low subcooling is the classic low-charge signature: the evaporator is starved, so vapor superheats excessively, and the condenser lacks liquid, so subcooling collapses. On an R-410A system of any age, that charge went somewhere. Find and repair the leak before adding refrigerant, especially at current R-410A prices.

Does R-410A have temperature glide?

Effectively no. R-410A is a near-azeotropic 50/50 blend of R-32 and R-125 with less than 0.3°F of glide, so a single saturation temperature per pressure works for both superheat and subcooling. Liquid charging is still the standard practice for any blend, but fractionation on R-410A is negligible in the field.


Other Refrigerants & Related Tools

R-454B Superheat & Subcooling Calculator

The A2L replacement for R-410A in new ducted systems. PT chart, TXV targets, and A2L charging notes.

R-32 Superheat & Subcooling Calculator

Pure A2L refrigerant used in ductless mini splits. Zero glide, higher pressures, hotter discharge.

R-22 Superheat & Subcooling Calculator

Legacy HCFC on reclaimed supply only. PT chart and targets for servicing older systems.

R-134a Superheat & Subcooling Calculator

Medium-temp refrigeration, chillers, and automotive AC. PT chart and charging targets.

All-Refrigerant Calculator

The full calculator with 10+ refrigerants including R-407C with glide handling, plus the four-quadrant diagnostic guide.

Target Superheat Calculator

Charging a fixed-orifice (piston) system? Set the charge by target superheat from indoor wet-bulb and outdoor dry-bulb, compared to your measured superheat.

Normal Superheat & Subcooling Values

The target numbers by refrigerant and metering device, with what a high or low reading means. R-410A, R-454B, R-32, R-22, R-134a, and R-407C in one reference.

How to Calculate Superheat & Subcooling

The formulas, the step-by-step field method, and worked examples for R-410A and R-22. The math behind the calculator.

Printable Superheat & Subcooling Chart

Target ranges by refrigerant plus PT charts for R-410A, R-454B, and R-22, formatted to print or save as a PDF for the truck.

Subcooling on a Heat Pump

Why heat pumps have no subcooling target in heating mode, how to charge by weigh-in, and when the cooling-mode subcooling number still applies.

A2L Charge Limit Calculator

Maximum A2L charge for a room, or minimum room area for a charge, per UL 60335-2-40 and ASHRAE 15.2. Covers R-454B, R-32, and 6 more refrigerants.

EPA Refrigerant Leak Rate Calculator

Topping off a covered 15+ lb appliance triggers a leak rate calculation under 40 CFR 84.106 as of January 1, 2026. Residential and light commercial air conditioning and heat pumps are excluded by 84.106(a)(3)(ii), so on most split systems the rate is informational. Run the EPA math and check the thresholds.

BTU / HVAC Load Calculator

Size the system by climate zone, insulation, windows, and duct location with automatic tonnage recommendations.

Chronic charge complaints on the same unit? Check the sizing.

A short-cycling oversized system masquerades as a charge problem year after year. Run the load by climate zone, insulation, and windows and compare it to the nameplate tonnage.