R-410A (Puron)

R-410A Superheat & Subcooling Calculator

Check charge on R-410A systems, still the biggest installed base in the field. The calculator opens preloaded for R-410A with a full PT chart, every grade cited to its source, and the four-quadrant diagnostic that turns two readings into a diagnosis.

Quick answer: The target comes from the equipment maker. Where it publishes no superheat, California Title 24 Table RA3.2-1 sets 4-25°F for residential ducted split systems with a TXV or other variable metering device, installer testing: outdoor air dry bulb 55°F to 120°F, return air dry bulb at least 70°F; subcooling is checked within ±3°F of the unit’s own target in cooling, at an outdoor air dry bulb of 55°F to 120°F and a return air dry bulb of at least 70°F. R-410A saturates at 40°F at 118 psig suction and 100°F at 317 psig liquid. Superheat = suction line temp − saturated suction temp. Subcooling = saturated liquid temp − liquid line temp. Read both together: high superheat with low subcooling means low charge, low superheat with high subcooling means overcharge.

R-410A Pressure-Temperature Chart

R-410A saturation temperature at gauge pressure. Single column, near-zero glide.

Swipe the table sideways to see the rest of its columns. →

R-410A
Pressure (psig)Sat. Temp (°F)Publisher spread (°F)
11.6-40°FNo other published table is compared at this pressure: none we hold reaches it, or this row is that table's own cell.
14.9-35°F1.27
18.5-30°F1.00
22.5-25°F0.88
26.9-20°F0.74
31.7-15°F0.70
36.8-10°F0.45
42.5-5°F0.42
48.60°F0.31
55.25°F0.21
62.310°F0.07
7015°F0
78.320°F0.06
87.325°F0.03
96.830°F0.10
10735°F0.16
11840°F0.18
13045°F0.06
14250°F0.24
15555°F0.35
17060°F0.04
18565°F0.06
20170°F0.03
21775°F0.28
23580°F0.22
25485°F0.15
27490°F0.12
29595°F0.12
317100°F0.13
340105°F0.19
365110°F0.08
391115°F0.04
418120°F0.06
446125°F0.14
476130°F0.13
507135°F0.21
539140°F0.36
573145°F0.47
608150°F0.68

About the spread column. It is the widest gap in saturation temperature between the published tables we hold, at that pressure, on the saturation column. Across this chart the widest is 1.27°F, at 14.9 psig. Our table and 1 other published table are compared here: 1 is a separate publisher. A dash in the column: no other published table is compared at this pressure: none we hold reaches it, or this row is that table's own cell. A narrow spread means the charts agree, which is not the same as the charts being right: they are all computed from equations of state fitted to lab data, and no field measurement settles it.

Where this table comes from. Hudson Technologies R-410A PT chart, verified cell by cell.
  • Checked against Arkema Forane R-410A, all 31 shipped cells within 1.0 psig on its vapor column, the column Hudson tracks; widest gap 1.0 psig at 55F [same printing as Weitron]
  • Checked against CoolProp-derived tables, anchor points agree [same model]
  • Checked against Weitron, reprinted as Daikin/Goodman PM-A2LPTC-USA_04-24, within 0.75 F across the shipped range [separate publisher]

The comparisons above cover the 31 cells from -20 to 130 F. The eight cells Hudson prints outside that span sit 0.7 to 0.9 psig above Forane's vapor column from -40 to -25 F and 1.3 to 5.0 psig below it from 135 to 150 F.

R-410A is carried as a single-column near-azeotrope. Forane prints a real 0.0 to 1.2 psig liquid and vapor split, which biases subcooling by about 0.2 F across 90 to 130 F condensing. That sits inside the 1.0 F manufacturer tolerance and is left unmodelled and disclosed here rather than silently corrected.

A separate publisher can catch a copying, edition or rounding error. A cross-check marked same model resolves to the same equation of state as the base table, so it is a consistency check rather than independent confirmation. One marked same printing prints numbers identical to another table listed here, so the two are one witness and we do not count them twice. Sources last changed 2026-10-25.

The two anchor points worth memorizing: 118 psig is a 40°F evaporator, and 317 psig is a 100°F condenser. Everything else on a residential cooling call is a short interpolation from one of those.


What R-410A Superheat & Subcooling Are Graded Against

TXV superheat: California Energy Commission, 2025 Reference Appendices (CEC-400-2025-010-AP), Table RA3.2-1, page RA3-19, the installer default "Superheat meets the Manufacturer's specifications or 4°F ≤ Superheat ≤ 25°F", for residential ducted split systems with a TXV or other variable metering device, installer testing: outdoor air dry bulb 55°F to 120°F, return air dry bulb at least 70°F. TXV subcooling: the maker's own target, checked within ±3°F ("Subcooling tolerance ±3°F of the manufacturer-specified target", same table) in cooling, at an outdoor air dry bulb of 55°F to 120°F and a return air dry bulb of at least 70°F. Fixed orifice: superheat against the target Table RA3.2-2 computes from indoor wet bulb and outdoor dry bulb, within ±5°F ("Superheat tolerance ±5°F of the specified target", Table RA3.2-1); subcooling only against the maker's own target with the tolerance the maker prints beside it (Lennox 13ACC Installation Instructions (form 504726), page 14, Table 6: "Liquid Subcooling [± 1°F (.6°C)]"), otherwise not graded. Refrigeration fluids: the superheat is shown and not graded, on a TXV or a fixed orifice, because these figures are residential comfort-cooling figures. Where the equipment maker prints its own figure, it governs.

Swipe the table sideways to see the rest of its columns. →

Metering deviceSuperheat graded againstSubcooling graded againstCharging method
TXV4–25°Fmaker's target ±3°FCharge by subcooling; the TXV holds superheat
Fixed orifice (piston)RA3.2-2 target ±5°Fmaker's target and printed tolerance, else not gradedCharge by superheat against its target; where the maker sets the charge by subcooling, by its target and tolerance

R-410A: The Installed Base You Service Every Day

R-410A carried residential air conditioning from roughly 2010 to 2025, so a system you diagnose and recharge can be an R-410A unit in its second decade. It is a near-azeotropic blend of R-32 and R-125 (50/50 by weight) running on POE oil, with a GWP of 2,088, which is why EPA's Technology Transitions rule, with its January 2025 limits on installing new split systems, moved new equipment to R-454B and R-32.

Phasedown changes the economics of a service call more than the technique. HFC production allowances step down on a schedule, so R-410A per-pound cost keeps rising. That makes "find the leak" the professional answer where "add a couple pounds" used to slide by, and it makes accurate charge verification worth the extra ten minutes: overcharging a system now wastes real money on both sides of the invoice.

R-410A Charging Notes

Charge R-410A as liquid from the cylinder, throttled slowly into the suction side. As a blend it should always be liquid-charged, even though its near-zero glide means fractionation is a technicality rather than a field problem. On TXV systems, charge to subcooling: get the system stable at steady-state, verify airflow first (a matted filter fakes a charge problem), then trim charge until subcooling lands on the nameplate value. On fixed-orifice systems, charge to the superheat chart using outdoor ambient and indoor wet bulb.

One R-410A misdiagnosis is charging by pressure alone. A 40°F evaporator at 118 psig is only meaningful once you know the suction line temperature; without it, low pressure could be low charge, low airflow, or a cold day. Superheat and subcooling turn raw pressures into a diagnosis, which is exactly what this calculator automates.


Worked Example: R-410A Split System with TXV

A 12-year-old R-410A split system, TXV metering, on a 90°F afternoon. Field readings: suction pressure 118 psig, suction line temperature 51°F, liquid pressure 317 psig, liquid line temperature 96°F. The return air is inside Title 24’s conditions too (in cooling, at an outdoor air dry bulb of 55°F to 120°F and a return air dry bulb of at least 70°F).

Saturated suction temp at 118 psig = 40°F

Superheat = 51°F − 40°F = 11°F

Saturated liquid temp at 317 psig = 100°F

Subcooling = 100°F − 96°F = 4°F

Diagnosis: Superheat 11°F is inside Title 24’s 4-25°F TXV default, but subcooling 4°F is below this unit’s 10°F nameplate target by more than ±3°F. Normal superheat with low subcooling on a TXV system means the valve is still compensating while the condenser runs short of liquid: the system is slightly low on charge. On a unit this age, leak-search the coils and service valves before adding refrigerant, then charge until subcooling reaches the nameplate target.


R-410A Charging FAQs

What should superheat be for R-410A?

On an R-410A TXV or EEV system the target is the equipment maker's; where the maker publishes none, California Title 24 Table RA3.2-1 sets 4 to 25F for a residential split system (outdoor 55 to 120F, return air at least 70F). Fixed-orifice and piston systems do not run a single number: you charge to a target superheat pulled off the manufacturer's target-superheat chart, which cross-references indoor return-air wet-bulb against outdoor dry-bulb, lower on a hot, humid day and higher on a cool, dry one. Confirm the reading with a P-T chart, converting suction saturation temperature at the measured low-side pressure (R-410A is near-azeotropic, so glide is negligible) and subtracting it from the actual suction-line temperature. Charge to superheat on fixed-orifice metering and to subcooling on TXV/EEV systems, but always verify superheat stays in range so the compressor never sees liquid floodback.

What is a good subcooling for R-410A?

The equipment’s own target, from its nameplate or charging chart, measured at the liquid-line service valve: no refrigerant-wide band is published, and California Title 24 Table RA3.2-1 checks the reading within ±3F of the manufacturer's target in cooling, at an outdoor air dry bulb of 55°F to 120°F and a return air dry bulb of at least 70°F. On a metering-valve system subcooling is your primary charge indicator: the TXV holds evaporator superheat fixed, so you set the charge by adding refrigerant until liquid-line subcooling reaches the rated value. Targets differ from one condenser to the next, which is why the nameplate figure is the grade. Subcooling is calculated as the saturated condensing temperature (from R-410A PT data at the measured liquid-line pressure) minus the actual liquid-line temperature.

What is normal superheat for R-410A?

With a TXV the target is the equipment maker's; where the maker publishes none, California Title 24 Table RA3.2-1 sets 4-25°F at the suction service valve of a residential split system. With a fixed orifice (piston), target superheat depends on outdoor ambient and indoor wet bulb (Title 24 Table RA3.2-2 computes it, checked within ±5°F), so use the manufacturer charging chart or enter both readings here. Below 5°F superheat, liquid floodback to the compressor becomes a real risk.

What is normal subcooling for R-410A?

The equipment's own nameplate or charging chart is the target when it prints one. No refrigerant-wide band is published; California Title 24 Table RA3.2-1 checks the reading within ±3°F of the manufacturer's target in cooling, at an outdoor air dry bulb of 55°F to 120°F and a return air dry bulb of at least 70°F. Subcooling is the primary charging indicator on TXV systems because the valve holds superheat steady while charge level shows up in the condenser. Low subcooling with high or normal superheat points to low charge, and high subcooling with low or normal superheat to overcharge or a condenser problem; with both low or both high the reading is not a charge level, so check airflow or a restriction first.

What pressures should R-410A run at?

There is no single right pressure: each is the chart pressure at the saturation temperature the coil runs at. A 40°F evaporator reads 118 psig suction on the R-410A chart. The liquid side reads the chart pressure at the condensing temperature, which rises with the outdoor temperature and with a dirty condenser: 365 psig at 110°F condensing and 418 psig at 120°F. Judge the charge by superheat and subcooling against the equipment maker's targets, not by pressure alone.

Is R-410A discontinued? Can I still buy it?

R-410A is being phased down, not banned. From January 1, 2025 a new residential split system (other than VRF) using R-410A may be installed only if all of its specified components (condensing unit, condenser, compressor, evaporator unit and evaporator, as 40 CFR 84.52 defines them) were made or imported before January 1, 2025 (self-contained units may no longer be manufactured or imported with it), so new installations moved to A2L refrigerants (R-454B and R-32 among them), but existing R-410A systems can be legally serviced indefinitely. Virgin and reclaimed R-410A remain available; prices are climbing as AIM Act production allowances step down, so leak repair matters more than it used to.

Can I top off an R-410A system with R-454B or R-32?

No. Mixing refrigerants contaminates the circuit, makes PT readings meaningless, and leaves refrigerant that no recovery processor will accept. R-410A equipment is also not listed for flammable A2L refrigerants. Top off R-410A systems with R-410A only, and if you do not know what is in a system, identify it before adding anything.

Why is my superheat high and subcooling low on R-410A?

High superheat with low subcooling is the classic low-charge signature: the evaporator is starved, so vapor superheats excessively, and the condenser lacks liquid, so subcooling collapses. On an R-410A system of any age, that charge went somewhere. Find and repair the leak before adding refrigerant, especially at current R-410A prices.

Does R-410A have temperature glide?

Effectively no. R-410A is a near-azeotropic 50/50 blend of R-32 and R-125 with less than 0.3°F of glide, so a single saturation temperature per pressure works for both superheat and subcooling. Liquid charging is still the standard practice for any blend, but fractionation on R-410A is negligible in the field.


Other Refrigerants & Related Tools

R-454B Superheat & Subcooling Calculator

The A2L replacement for R-410A in new ducted systems. PT chart, cited charge checks, and A2L charging notes.

R-32 Superheat & Subcooling Calculator

Pure A2L refrigerant used in ductless mini splits. Zero glide, higher pressures, hotter discharge.

R-22 Superheat & Subcooling Calculator

Legacy HCFC: serviced with recycled, reclaimed or previously produced R-22 since 2020. PT chart and cited charge checks for servicing older systems.

R-134a Superheat & Subcooling Calculator

Medium-temp refrigeration, chillers, and automotive AC. PT chart and cited reference figures.

All-Refrigerant Calculator

The full calculator with 10+ refrigerants including R-407C with glide handling, plus the four-quadrant diagnostic guide.

Target Superheat Calculator

Charging a fixed-orifice (piston) system? Set the charge by target superheat from indoor wet-bulb and outdoor dry-bulb, compared to your measured superheat.

Normal Superheat & Subcooling Values

What each reading is graded against, by metering device, each figure cited, with what a high or low reading means. R-410A, R-454B, R-32, R-22, R-134a, and R-407C in one reference.

How to Calculate Superheat & Subcooling

The formulas, the step-by-step field method, and worked examples for R-410A and R-22. The math behind the calculator.

Printable Superheat & Subcooling Chart

What each reading is graded against, with its source, plus PT charts for R-410A, R-454B, and R-22, formatted to print or save as a PDF for the truck.

Subcooling on a Heat Pump

Where to measure on a heat pump in each mode, each maker's own heating-mode charging rule, and when the cooling-mode subcooling number still applies.

A2L Charge Limit Calculator

Maximum A2L charge for a room, or minimum room area for a charge, per UL 60335-2-40 and ASHRAE 15.2. Covers R-454B, R-32, and 6 more refrigerants.

EPA Refrigerant Leak Rate Calculator

Topping off a covered 15+ lb appliance triggers a leak rate calculation under 40 CFR 84.106 as of January 1, 2026. Residential and light commercial air conditioning and heat pumps are excluded by 84.106(a)(3)(ii), so on most split systems the rate is informational. Run the EPA math and check the thresholds.

BTU / HVAC Load Calculator

A house's heating and cooling loads by ACCA Manual J at your ZIP code's weather station, with the size Manual S points to.

Chronic charge complaints on the same unit? Check the sizing.

A short-cycling oversized system masquerades as a charge problem year after year. Run the Manual J load at your ZIP code's weather station and compare it to the nameplate tonnage.